York B3CH 048 and 060 installation instructions Enthalpy Set Point Adjustment, Physical Data

Models: B3CH 048 and 060

1 16
Download 16 pages 54.58 Kb
Page 7
Image 7
FIG. 5 - ENTHALPY SET POINT ADJUSTMENT

035-12984-001-A-0204

FIG. 5 - ENTHALPY SET POINT ADJUSTMENT

TABLE 3 - PHYSICAL DATA

 

MODELS

 

BCH

 

048

 

060

 

 

 

 

CENTRIFUGAL BLOWER (Dia. x

305 x254

 

305 x 254

SUPPLY AIR

Wd.,mm/in.)

12 x 10

 

12 x 10

BLOWER

FAN MOTOR HP (Direct-Drive Units)

0.75

 

NA

 

FAN MOTOR HP (Belt-Drive Units)

NA

 

1.5

INDOOR

ROWS DEEP

3

 

3

FINS PER 25mm (1 inch)

15

 

15

COIL

 

FACE AREA (m2/ft2)

0.47 / 5.1

 

0.47 / 5.1

OUTDOOR

PROPELLER DIA. (mm/in.)

610 / 24

 

610 / 24

FAN MOTOR kW/HP

0.37 / 0.5

 

0.37 / 0.5

FAN

 

NOM. CFM TOTAL

4,200

 

4,500

 

 

OUTDOOR

ROWS DEEP

1

 

1

FINS PER 25mm (1 inch)

20

 

20

COIL

 

FACE AREA (m2/ft2)

17.1

 

17.1

AIR

QUANTITY PER UNIT (14" x 20" x 1")

2

 

2

FILTERS

QUANTITY PER UNIT (14" X 25" X 1")

1

 

1

(SEE NOTE)

TOTAL FACE AREA (m2/ ft2.)

6.3

 

6.3

CHARGE

REFRIGERANT 22 (kg / lbs./oz.)

4.2 / 9.2

 

3.7 / 8/4

NOTE: Filter racks are adapted for 1" or 2" thick filters.

WEIGHTS (kg/lbs)

Basic Unit

 

048

270 / 595

 

 

 

 

 

060

281 / 620

 

 

OPTIONS / ACCESSORIES

 

 

 

 

 

Electric Heat

 

5 - 7 kW

8.2 / 18

 

 

 

 

 

10 - 15 kW

10.4

/ 23

(Nominal Kw)

 

 

 

 

 

 

20 - 30 kW

12.7

/ 28

 

 

 

 

 

 

 

Economizer

 

22.7

/ 50

Motorized Outdoor Air

21.8

/ 48

Damper

 

 

 

 

Barometric Relief/Fixed

4.5 / 10

Outdoor Air Intake Damper

 

 

Roof Mounting Curb

41.7

/ 92

Belt-Drive Blower

 

2.3

/ 5

Unitary Products Group

7