TABLE 2 - AIR FLOW LIMITATIONS
NOMINAL |
| UNIT MODEL SIZE, NOMINAL TONS | ||
HEATER | VOLTAGE | 4 | 5 | |
SIZE | MINIMUM SUPPLY AIR CFM | |||
| ||||
KW |
| |||
|
|
| ||
7 |
| 1,300 | 1,600 | |
10 |
| 1,300 | 1,600 | |
15 | 1,300 | 1,600 | ||
20 |
| 1,300 | 1,600 | |
30 |
| – | 1,600 |
CONTROL WIRING
1 Typical
2 Only required on units with supplemental electric heat.
TO REMOTE SENSOR
2ET04701324 IF USED
Note: The thermostat terminals shown above are typical. Check thermostat and unit wiring diagrams for correct wiring connections.
1 Typical Electronic programmable thermostat 2ET04701124 with subbase for either manual or automatic changeover.
2Only required on units with economizer. Remove jumper L2 from terminals
4 and 9 on jumper plug P7. The outdoor air intake dampers will return to their fully closed position when the thermostat switches to the “unoccupied” mode.
3Second stage cooling may be used on units with economizer. Remove jumper J1 from terminals 8 and 10 on jumper plug connector P7.
4Only required on units with supplemental electric heat.
POWER WIRING
NEUTRAL
CONTACTORTERMINAL
BLOCK
DISCONNECT
GROUND LUG
REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, THE WIRING AND THE OVERCURRENT PROTECTION.
FIG. 3 - TYPICAL FIELD WIRING
Unitary Products Group | 5 |