York BQ 060, BQ 036, BQ 048 Physical Data, Electric Heat Correction Factors, VOLTAGE LIMITATIONS1

Models: BQ 048 BQ 036 BQ 060

1 44
Download 44 pages 38.85 Kb
Page 33
Image 33

036-21508-005-A-0305

TABLE 22: PHYSICAL DATA

 

MODELS

 

BQ

 

 

036

048

060

 

 

EVAPORATOR

Centrifugal Blower (Dia. x Wd. in.)

12 X 10

12 X 10

12 X 10

Fan Motor HP (Direct Drive)

1/2

3/4

1

BLOWER

 

 

 

 

Fan Motor HP (Belt Drive)

1 1/2

1 1/2

1 1/2

 

 

 

 

 

 

EVAPORATOR

Rows Deep

4

3

3

 

 

 

 

Fins Per Inch

16

15

15

COIL

 

 

 

 

Face Area (Sq. Ft.)

4.3

5.1

5.1

 

 

 

 

 

 

CONDENSER

Propeller Dia. (in.)

22

22

24

 

 

 

 

Fan Motor Hp

1/3

1/2

1/2

FANS

 

 

 

 

Nom. CFM

4300

4200

4500

 

 

 

 

 

 

CONDENSER

Rows Deep

1

1

1

 

 

 

 

Fins Per Inch

20

20

20

COILS

 

 

 

 

Face Area (Sq. Ft.)

17.1

17.1

17.1

 

 

 

 

 

 

COMPRESSOR

Reciprocating Type

1

1

1

(Qty. Per Unit)

 

 

 

 

AIR

Quantity Per Unit (15” X 20” X 1” or 2“)

2

2

2

 

 

 

 

Quantity Per Unit (14” X 25” X 1” or 2“)

1

1

1

FILTERS

 

 

 

 

Total Face Area (sq. ft.)

6.6

6.6

6.6

 

 

 

 

 

 

CHARGE

Refrigerant 22

7/12

9/2

8/4

(lbs./oz.)

 

 

 

 

 

 

 

 

 

TABLE 23: ELECTRIC HEAT CORRECTION FACTORS

NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTI-

PLIER

 

 

208

208

1.00

 

 

 

240

230

0.92

480

460

0.92

600

575

0.92

TABLE 24: VOLTAGE LIMITATIONS1

POWER SUPPLY

 

VOLTAGE

 

 

 

 

MIN.

 

MAX.

208/230-3-60

187

 

253

 

 

 

 

460-3-60

414

 

506

575-3-60

518

 

506

1.Utilization Range “A” in accordance with ARI Standard 110.

Unitary Products Group

33

Page 33
Image 33
York BQ 060, BQ 036, BQ 048 Physical Data, Electric Heat Correction Factors, VOLTAGE LIMITATIONS1, 036-21508-005-A-0305