matic reset to prevent the heating element system from oper- ating at an excessive temperature. The heating section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required).

UNIT OPERATING CHARACTERISTICS

a.Unit shall be capable of starting and running at 125°F outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240. The compres- sor, with standard controls, shall be capable of oper- ation down to 0°F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

STANDARD LIMITED WARRANTIES

Compressor 5 Years

Electric Heat Element 5 Years

Other Parts 1 Year

OPTIONAL OUTDOOR AIR (Shall be made available by either/or):

ELECTRONIC ENTHALPY AUTOMATIC ECONO- MIZER- Outdoor and return air dampers that are inter- locked and positioned by a fully-modulating, spring return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potenti- ometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi- tioned space during normal operation. During econo- mizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer oper- ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The out- door intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/fil- ters shall be provided. Simultaneous economizer/com- pressor operation is also possible. Dampers shall fully close on power loss.

036-21508-005-A-0305

MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air dampers are positioned by a 2-position,spring-return damper actuator. The maximum leakage rate for the out- door air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pres- sure differential of 0.5 IWG. A unit-mounted potentiome- ter shall be provided to adjust the outdoor damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

ROOF CURB - 14"and 8” high, full perimeter curb with wood nailer (shipped knocked-down).

BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit.

POWER EXHAUST OPTION - To work in conjunction with economizers.

ELECTRIC HEATERS

ECONOMIZER/MOTORIZED DAMPER RAIN HOOD - Contains all hood panels and the hardware for assem- bling.

MANUAL OUTDOOR AIR DAMPER

COIL GUARD KIT - Guard for cooling coil.

HAIL GUARD

OTHER FACTORY INSTALLED OPTIONS

POWER EXHAUST OPTION - To work in conjunction with economizers.

TECHNICOAT PHENOLIC COATED CONDENSER AND EVAPORATOR COIL

ELECTRONIC SINGLE ENTHALPY ECONOMIZER

DIRTY FILTER SWITCH

PHASE MONITOR

COIL GUARD

POWERED GFI CONVENIENCE OUTLET

NON-POWERED GFI CONVENIENCE OUTLET

42

Unitary Products Group

Page 42
Image 42
York BQ 060, BQ 036, BQ 048 warranty Manual Outdoor AIR Damper