036-21508-005-A-0305

TABLE 1: SOUND POWER RATING1

 

 

ESP

BLOWER

 

 

 

 

SOUND POWER (db 10-12

Watts)

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

Octave Band Centerline Frequency (Hz)

 

SWL

dB(A)

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

@

 

 

IWG

SPEED

KW

63

125

 

250

500

1,000

2,000

 

4,000

8,000

dB(A)

 

 

 

 

10Ft.2

 

 

 

 

 

036

1,200

0.6

LOW

0.60

84

84

 

74

67

69

62

 

57

52

74

41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048

1,600

0.55

HIGH

0.80

85

85

 

75

68

70

63

 

58

53

75

42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

2,000

0.45

HIGH

1.00

86

86

 

76

69

71

64

 

59

54

76

43

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran- tee requiring a dBA value or sound data in any other form than sound power level ratings.

2.At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS

 

 

 

 

 

ARI RATINGS1

 

 

 

 

 

 

UNIT SIZE

COOLING PERFORMANCE

SOUND

 

 

 

 

HEATING CAPACITY

 

 

(MBH)

RATING2

HSPF

 

47°F

 

 

17°F

 

 

 

 

 

 

 

MBH

SEER

EER

bels

 

 

MBH

 

COP

MBH

 

COP

036

39

10.00

9.20

8.6

7.3

 

39.0

 

3.0

23.0

 

2.1

048

48

10.20

9.25

8.6

6.7

 

48.0

 

3.0

26.4

 

2.0

060

59

10.00

9.20

8.4

7.0

 

59.0

 

3.0

36.0

 

2.1

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

1.Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.

2.Rated in accordance with ARI Standard 270.

SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hoursduring the same period.

EER = Energy Efficiency Ratio-the cooling capacity in BTU’s per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt).

COP = Coefficient of Performance - the total heating capacity provided by the refrigeration system, including circulating fan heat but excluding supplementary resistance (BTU’s per hour) divided by the total electric input (watts) x 3.412.

HSPF = Heating Seasonal Performance Factor - the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period. (Based on Region IV minimum design heating requirement).

Unitary Products Group

15

Page 15
Image 15
York BQ 060, BQ 036, BQ 048 warranty Sound Power RATING1, Capacity Ratings