York BQ 036, BQ 060 Field-Installedaccessories, 036-21508-005-A-0305, Unitary Products Group

Models: BQ 048 BQ 036 BQ 060

1 44
Download 44 pages 38.85 Kb
Page 13
Image 13

036-21508-005-A-0305

Air IAQ sensor. Construction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Com- fort™using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Out- side CO2 sensor to perform Differential Demand Ventila- tion. It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The pat- ented economizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLI-Start™ algorithm to maximize energy sav- ings by recovering the building from the Unoccupied Set- points to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity™ INTELLI-Comfort™ balances space temperature, venti- lation air temperature, CO2 and humidity for ultimate comfort.

Simplicity™ INTELLI-Comfort™ with MOD LINK CON- TROL - The York® Simplicity™ INTELLI-Comfort™ with Mod Link control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an addi- tional control to translate communications from MOD- BUS to the BACnet MSTP protocol.

Novar® BAS CONTROL - The Novar® ETC-3 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

JOHNSON CONTROLS BAS CONTROL - The Johnson Control YK-UNT-1126 building automation system con- troller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air prov- ing switch.

CPC BAS CONTROL - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building auto- mation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.

HONEYWELL BAS CONTROL - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.

SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.

STAINLESS STEEL DRAIN PAN - An optional rust- proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environ- ments.

BOTTOM DRAIN CONNECTION - An optional bottom drain connection is available for inside the curb connec- tions for applications in cold environments to reduce freezing drain lines.

COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of- phase condition.

DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.

HINGED FILTER DOOR/“TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.

NOTE:Knobs are shipped inside the unit to prevent ship- ping damage. These must be field installed for tool-less operation.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONO- MIZERS - Includes a slide-in /plug-in damper assembly with fully modulating spring-return motor actuator capa- ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in /plug-in damper assembly with a 2- position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field assembled before installing.

ELECTRIC HEATERS wired for single point power sup- ply. These nickel chromium heater elements are pro- vided with limit and automatic reset capability to prevent operation at excessive temperatures.

ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the fin- ished roof. These full perimeter curbs meet the require- ments of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assem- bly.

Unitary Products Group

13

Page 13
Image 13
York BQ 036, BQ 060, BQ 048 warranty Field-Installedaccessories, 036-21508-005-A-0305, Unitary Products Group