036-21508-005-A-0305

TABLE 12: STATIC RESISTANCES

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

1200

1400

1600

 

1800

 

2000

2200

2400

2600

 

 

 

 

 

 

 

 

 

 

 

 

ECONOMIZER1, 2

0.07

0.08

0.09

0.11

 

0.13

 

0.15

0.17

0.20

0.23

ELECTRIC

5-15KW

0.04

0.05

0.06

0.07

 

0.08

 

0.10

0.12

0.14

0.16

HEATERS1

 

 

 

 

 

 

 

 

 

 

 

 

20-30KW

0.06

0.07

0.08

0.09

 

0.11

 

0.13

0.15

0.17

0.20

BOTTOM DUCT CONNECTIONS1

0.06

0.07

0.08

0.09

 

0.10

 

0.11

0.12

0.14

0.16

1.Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.

2.The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 13: ELECTRIC HEATER CFM LIMITATIONS

UNIT MODEL SIZE NOMINAL

 

 

 

MINIMUM SUPPLY AIR CFM

 

 

VOLTAGE

 

 

 

 

 

 

 

 

HEATER SIZE NOMINAL KW

 

 

TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

5

7

10

15

20

30

 

208/230-1-60

1100

1100

1200

1200

1300

-

3

208/230-3-60

1100

1100

1200

1200

1300

-

 

 

 

 

 

 

 

460-3-60

-

1100

1200

1200

1300

-

 

 

 

 

 

 

 

 

 

 

575-3-60

-

-

1200

1200

1300

-

 

208/230-1-60

1300

1300

1300

1300

1300

-

 

 

 

 

 

 

 

 

4

208/230-3-60

1300

1300

1300

1300

1300

-

 

 

 

 

 

 

 

460-3-60

-

1300

1300

1300

1300

-

 

 

575-3-60

-

-

1300

1300

1400

-

 

208/230-1-60

1600

1600

1600

1600

1600

1600

 

 

 

 

 

 

 

 

5

208/230-3-60

1600

1600

1600

1600

1600

1600

460-3-60

-

1600

1600

1600

1600

1600

 

 

 

 

 

 

 

 

 

 

575-3-60

-

-

1600

1600

1600

1800

24

Unitary Products Group

Page 24
Image 24
York BQ 060, BQ 036, BQ 048 warranty Static Resistances, Electric Heater CFM Limitations