TABLE 6: ELECTRICAL DATA DJ150
|
|
|
| Supply | Pwr | Pwr |
|
|
| Min. Circuit | MCA | Max | Max Fuse1 Size | |||||
|
|
| OD Fan |
|
|
| w/Power | Fuse1 | w/Power | |||||||||
| Compressors | Blower | Exh | Conv | Electric Heater | Actual | Heater | Ampacity | ||||||||||
Voltage |
|
| Motors | Motor FLA | Motor | Outlet | (Amps) | Exhaust | Size | Exhaust | ||||||||
|
|
|
|
|
|
|
| Model No. | KW | Amps |
|
| (Amps) | (Amps) | (Amps) | |||
| RLA | LRA | FLA | 3 | 5 | FLA | FLA |
|
|
| 3 | 5 | 3 | 5 | 3 | 5 | 3 | 5 |
| ea. | ea. | ea. | HP | HP |
|
|
| HP | HP | HP | HP | HP | HP | HP | HP | ||
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
| None | 61.9 | 67.1 | 67.4 | 72.6 | 80 | 80 | 80 | 90 | ||
208 | 20.0 | 146.0 | 1.5 | 10.9 | 16.1 | 5.5 | 0.0 | 2TP04521825 | 13.5 | 37.5 | 61.9 | 67.1 | 67.4 | 73.8 | 80 | 80 | 80 | 90 |
2TP04522425 | 18.0 | 50.0 | 76.1 | 82.6 | 83.0 | 89.5 | 80 | 90 | 90 | 90 | ||||||||
|
|
|
|
|
|
|
| 2TP04523625 | 25.5 | 70.8 | 102.1 | 108.6 | 109.0 | 115.5 | 110 | 110 | 110 | 125 |
|
|
|
|
|
|
|
| 2TP04525425 | 40.6 | 112.7 | 154.5 | 161.0 | 161.4 | 167.9 | 175 | 175 | 175 | 175 |
|
|
|
|
|
|
|
| None | 61.9 | 67.1 | 67.4 | 72.6 | 80 | 80 | 80 | 90 | ||
230 | 20.0 | 146.0 | 1.5 | 10.9 | 16.1 | 5.5 | 0.0 | 2TP04521825 | 18.0 | 43.3 | 67.8 | 74.3 | 74.6 | 81.1 | 80 | 80 | 80 | 90 |
2TP04522425 | 24.0 | 57.7 | 85.8 | 92.3 | 92.7 | 99.2 | 90 | 100 | 100 | 100 | ||||||||
|
|
|
|
|
|
|
| 2TP04523625 | 34.0 | 81.8 | 115.9 | 122.4 | 122.7 | 129.2 | 125 | 125 | 125 | 150 |
|
|
|
|
|
|
|
| 2TP04525425 | 54.0 | 129.9 | 143.5 | 150.0 | 150.4 | 156.9 | 175 | 175 | 175 | 175 |
|
|
|
|
|
|
|
| None | 27.4 | 30.2 | 29.6 | 32.4 | 35 | 35 | 35 | 40 | ||
460 | 8.4 | 73.0 | 0.8 | 5.3 | 8.1 | 2.2 | 0.0 | 2TP04521846 | 18 | 22.6 | 33.7 | 37.2 | 36.4 | 39.9 | 35 | 40 | 40 | 40 |
2TP04522446 | 24 | 30.1 | 42.7 | 46.2 | 45.5 | 49 | 45 | 50 | 50 | 50 | ||||||||
|
|
|
|
|
|
|
| 2TP04523646 | 34 | 42.7 | 57.7 | 61.2 | 60.5 | 64 | 60 | 70 | 70 | 70 |
|
|
|
|
|
|
|
| 2TP04525446 | 54 | 67.8 | 71.6 | 75.1 | 74.3 | 77.8 | 80 | 90 | 80 | 90 |
|
|
|
|
|
|
|
| None | 21.6 | 23.5 | 23.4 | 25.3 | 25 | 30 | 30 | 30 | ||
575 | 6.7 | 60.0 | 0.6 | 4.1 | 6.0 | 1.8 | 0.0 | 2TP04521858 | 18 | 18.1 | 26.8 | 29.2 | 29 | 31.4 | 30 | 30 | 30 | 35 |
2TP04522458 | 24 | 24.1 | 34 | 36.4 | 36.2 | 38.6 | 35 | 40 | 40 | 40 | ||||||||
|
|
|
|
|
|
|
| 2TP04523658 | 34 | 34.1 | 46 | 48.4 | 48.3 | 50.6 | 50 | 50 | 50 | 60 |
|
|
|
|
|
|
|
| 2TP04525458 | 54 | 54.2 | 57.1 | 59.5 | 59.3 | 61.7 | 70 | 70 | 70 | 70 |
1Maximum HACR breaker of the same AMP size is applicable.
TABLE 7: ELECTRICAL DATA DJ150
|
|
| OD Fan | Supply | Pwr | Pwr |
|
|
| Min. Circuit | MCA | Max | Max Fuse1 Size | |||||
|
|
|
|
|
| w/Power | Fuse1 | w/Power | ||||||||||
| Compressors | Blower | Exh | Conv | Electric Heater | Actual | Heater | Ampacity | ||||||||||
Voltage |
|
| Motors | Motor FLA | Motor | Outlet | (Amps) | Exhaust | Size | Exhaust | ||||||||
|
|
|
|
|
|
|
| Model No. | KW | Amps |
|
| (Amps) | (Amps) | (Amps) | |||
| RLA | LRA | FLA | 3 | 5 | FLA | FLA |
|
|
| 3 | 5 | 3 | 5 | 3 | 5 | 3 | 5 |
| ea. | ea. | ea. | HP | HP |
|
|
| HP | HP | HP | HP | HP | HP | HP | HP | ||
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
| None | 71.9 | 77.1 | 77.4 | 82.6 | 90 | 90 | 90 | 100 | ||
208 | 20.0 | 146.0 | 1.5 | 10.9 | 16.1 | 5.5 | 10.0 | 2TP04521825 | 13.5 | 37.5 | 73.0 | 79.5 | 79.8 | 86.3 | 90 | 90 | 90 | 100 |
2TP04522425 | 18.0 | 50.0 | 88.6 | 95.1 | 95.5 | 102.0 | 90 | 100 | 100 | 110 | ||||||||
|
|
|
|
|
|
|
| 2TP04523625 | 25.5 | 70.8 | 114.6 | 121.1 | 121.5 | 128.0 | 125 | 125 | 125 | 150 |
|
|
|
|
|
|
|
| 2TP04525425 | 40.6 | 112.7 | 167.0 | 173.5 | 173.9 | 180.4 | 175 | 175 | 175 | 200 |
|
|
|
|
|
|
|
| None | 71.9 | 77.1 | 77.4 | 82.6 | 90 | 90 | 90 | 100 | ||
230 | 20.0 | 146.0 | 1.5 | 10.9 | 16.1 | 5.5 | 10.0 | 2TP04521825 | 18.0 | 43.3 | 80.3 | 86.8 | 87.1 | 93.6 | 90 | 90 | 90 | 100 |
2TP04522425 | 24.0 | 57.7 | 98.3 | 104.8 | 105.2 | 111.7 | 100 | 110 | 110 | 125 | ||||||||
|
|
|
|
|
|
|
| 2TP04523625 | 34.0 | 81.8 | 128.4 | 134.9 | 135.2 | 141.7 | 150 | 150 | 150 | 150 |
|
|
|
|
|
|
|
| 2TP04525425 | 54.0 | 129.9 | 156.0 | 162.5 | 162.9 | 169.4 | 175 | 175 | 175 | 175 |
|
|
|
|
|
|
|
| None | 32.4 | 35.2 | 34.6 | 37.4 | 40 | 40 | 40 | 45 | ||
460 | 8.4 | 73.0 | 0.8 | 5.3 | 8.1 | 2.2 | 5.0 | 2TP04521846 | 18 | 22.6 | 39.9 | 43.4 | 42.7 | 46.2 | 40 | 45 | 45 | 50 |
2TP04522446 | 24 | 30.1 | 49 | 52.5 | 51.7 | 55.2 | 50 | 60 | 60 | 60 | ||||||||
|
|
|
|
|
|
|
| 2TP04523646 | 34 | 42.7 | 64 | 67.5 | 66.7 | 70.2 | 70 | 70 | 70 | 80 |
|
|
|
|
|
|
|
| 2TP04525446 | 54 | 67.8 | 77.8 | 81.3 | 80.6 | 84.1 | 90 | 90 | 90 | 90 |
|
|
|
|
|
|
|
| None | 25.6 | 27.5 | 27.4 | 29.3 | 30 | 30 | 30 | 35 | ||
575 | 6.7 | 60.0 | 0.6 | 4.1 | 6.0 | 1.8 | 4.0 | 2TP04521858 | 18 | 18.1 | 31.8 | 34.2 | 34 | 36.4 | 35 | 35 | 35 | 40 |
2TP04522458 | 24 | 24.1 | 39 | 41.4 | 41.2 | 43.6 | 40 | 45 | 45 | 45 | ||||||||
|
|
|
|
|
|
|
| 2TP04523658 | 34 | 34.1 | 51 | 53.4 | 53.3 | 55.6 | 60 | 60 | 60 | 60 |
|
|
|
|
|
|
|
| 2TP04525458 | 54 | 54.2 | 62.1 | 64.5 | 64.3 | 66.7 | 70 | 70 | 70 | 70 |
1Maximum HACR breaker of the same AMP size is applicable.
TABLE 8: ELECTRIC HEAT MULTIPLIERS
VOLTAGE |
| kW Cap. Multiplier | |
NOMINAL |
| RATING | |
|
| ||
240 |
| 208 | 0.75 |
| 230 | 0.92 | |
|
| ||
480 |
| 460 | 0.92 |
600 |
| 575 | 0.92 |
NOTE: Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for heaters supplied at lower voltages.
NOTES FOR TABLES 9 AND TABLE 10:
•Blower performance includes dry coil and 2” throwaway filters.
•Blower performance for gas heat includes the maximum number of heat tubes available for each tonnage.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been deducted from the total static pressure of the blower.
12 | Johnson Controls Unitary Products |