TABLE 11: ADDITIONAL STATIC RESISTANCE
CFM | Cooling Only1 | Economizer2 3 |
| Electric Heat KW2 |
| ||
18 | 24 | 36 | 54 | ||||
|
|
| |||||
|
|
|
|
|
|
| |
3700 | 0.20 | 0.04 | 0.18 | 0.21 | 0.22 | 0.26 | |
3900 | 0.23 | 0.04 | 0.20 | 0.23 | 0.24 | 0.28 | |
4100 | 0.25 | 0.04 | 0.22 | 0.25 | 0.26 | 0.31 | |
4300 | 0.28 | 0.05 | 0.24 | 0.28 | 0.29 | 0.34 | |
4500 | 0.30 | 0.05 | 0.26 | 0.30 | 0.31 | 0.37 | |
4700 | 0.33 | 0.05 | 0.29 | 0.33 | 0.34 | 0.40 | |
4900 | 0.36 | 0.05 | 0.31 | 0.35 | 0.37 | 0.43 | |
5100 | 0.39 | 0.06 | 0.34 | 0.38 | 0.40 | 0.46 | |
5300 | 0.42 | 0.06 | 0.37 | 0.41 | 0.43 | 0.49 | |
5500 | 0.45 | 0.06 | 0.40 | 0.44 | 0.46 | 0.53 | |
5700 | 0.48 | 0.06 | 0.43 | 0.47 | 0.49 | 0.56 | |
5900 | 0.52 | 0.07 | 0.46 | 0.50 | 0.53 | 0.59 | |
6100 | 0.56 | 0.07 | 0.49 | 0.53 | 0.56 | 0.62 | |
6300 | 0.60 | 0.07 | 0.53 | 0.56 | 0.59 | 0.65 |
1Add these resistance values to the available static resistance in the respective Blower Performance Tables.
2Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
3The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 12: ELECTRIC HEAT MINIMUM SUPPLY AIR CFM
| HEATER | UNIT NOMINAL TONS | |
kW |
| VOLTAGE | 12.5 |
| MINIMUM SUPPLY AIR CFM | ||
|
|
| |
18 |
|
|
|
24 |
| 208/230 | 3750 |
36 |
| ||
|
|
| |
54 |
|
|
|
18 |
|
|
|
24 |
| 480 | 3750 |
36 |
| ||
|
|
| |
54 |
|
|
|
18 |
|
|
|
24 |
| 600 | 3750 |
|
| ||
36 |
| ||
|
|
| |
54 |
|
|
|
TABLE 13: INDOOR BLOWER SPECIFICATIONS
MODEL |
|
| MOTOR |
|
| MOTOR SHEAVE |
| BLOWER SHEAVE |
| BELT | |||
HP | RPM | Eff. |
| SF | Frame | Datum Dia. (in.) | Bore (in.) | Model | Datum Dia. (in.) | Bore (in.) | Model | ||
|
|
| |||||||||||
DJ150 | 3 | 1725 | 80% |
| 1.15 | 56 | 3.4 - 4.4 | 7/8 | 1VM50 | 7.0 | 1 | AK74 | A54 |
|
|
|
|
|
|
|
|
|
|
|
|
| |
5 | 1725 | 87% |
| 1.15 | 184T | 4.3 - 5.3 | 1 1/8 | 1VP56 | 6.7 | 1 | BK77 | BX55 | |
|
|
TABLE 14: POWER EXHAUST SPECIFICATIONS
POWER EXHAUST | VOLT | PHASE |
| MOTOR |
|
| ELECTRICAL |
| FUSE | CFM@ | ||
MODEL | HP | RPM1 | QTY | LRA |
| FLA |
| MCA | SIZE | 0.1 ESP | ||
|
|
|
| |||||||||
2PE0473125 | 208/230 | 1 |
| 1075 |
| 24.9 |
| 5.0 |
| 6.3 | 10 |
|
2PE0473146 | 460 | 1 | 0.75 | 1 | N/A |
| 2.2 |
| 2.8 | 5 | 3,800 | |
|
|
| ||||||||||
2PE0473158 | 575 | 1 |
| 1050 |
|
| 1.5 |
| 1.9 | 4 |
| |
|
|
|
|
|
|
1 Motors are
Johnson Controls Unitary Products | 15 |