York DJ 150 Additional Static Resistance, Electric Heat Minimum Supply Air Cfm, Cooling Only1

Models: DJ 150

1 28
Download 28 pages 17.57 Kb
Page 15
Image 15

246695-YTG-C-0708

TABLE 11: ADDITIONAL STATIC RESISTANCE

CFM

Cooling Only1

Economizer2 3

 

Electric Heat KW2

 

18

24

36

54

 

 

 

 

 

 

 

 

 

 

3700

0.20

0.04

0.18

0.21

0.22

0.26

3900

0.23

0.04

0.20

0.23

0.24

0.28

4100

0.25

0.04

0.22

0.25

0.26

0.31

4300

0.28

0.05

0.24

0.28

0.29

0.34

4500

0.30

0.05

0.26

0.30

0.31

0.37

4700

0.33

0.05

0.29

0.33

0.34

0.40

4900

0.36

0.05

0.31

0.35

0.37

0.43

5100

0.39

0.06

0.34

0.38

0.40

0.46

5300

0.42

0.06

0.37

0.41

0.43

0.49

5500

0.45

0.06

0.40

0.44

0.46

0.53

5700

0.48

0.06

0.43

0.47

0.49

0.56

5900

0.52

0.07

0.46

0.50

0.53

0.59

6100

0.56

0.07

0.49

0.53

0.56

0.62

6300

0.60

0.07

0.53

0.56

0.59

0.65

1Add these resistance values to the available static resistance in the respective Blower Performance Tables.

2Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

3The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 12: ELECTRIC HEAT MINIMUM SUPPLY AIR CFM

 

HEATER

UNIT NOMINAL TONS

kW

 

VOLTAGE

12.5

 

MINIMUM SUPPLY AIR CFM

 

 

 

18

 

 

 

24

 

208/230

3750

36

 

 

 

 

54

 

 

 

18

 

 

 

24

 

480

3750

36

 

 

 

 

54

 

 

 

18

 

 

 

24

 

600

3750

 

 

36

 

 

 

 

54

 

 

 

TABLE 13: INDOOR BLOWER SPECIFICATIONS

MODEL

 

 

MOTOR

 

 

MOTOR SHEAVE

 

BLOWER SHEAVE

 

BELT

HP

RPM

Eff.

 

SF

Frame

Datum Dia. (in.)

Bore (in.)

Model

Datum Dia. (in.)

Bore (in.)

Model

 

 

 

DJ150

3

1725

80%

 

1.15

56

3.4 - 4.4

7/8

1VM50

7.0

1

AK74

A54

 

 

 

 

 

 

 

 

 

 

 

 

 

5

1725

87%

 

1.15

184T

4.3 - 5.3

1 1/8

1VP56

6.7

1

BK77

BX55

 

 

TABLE 14: POWER EXHAUST SPECIFICATIONS

POWER EXHAUST

VOLT

PHASE

 

MOTOR

 

 

ELECTRICAL

 

FUSE

CFM@

MODEL

HP

RPM1

QTY

LRA

 

FLA

 

MCA

SIZE

0.1 ESP

 

 

 

 

2PE0473125

208/230

1

 

1075

 

24.9

 

5.0

 

6.3

10

 

2PE0473146

460

1

0.75

1

N/A

 

2.2

 

2.8

5

3,800

 

 

 

2PE0473158

575

1

 

1050

 

 

1.5

 

1.9

4

 

 

 

 

 

 

 

1 Motors are multi-tapped and factory wired for high speed.

Johnson Controls Unitary Products

15

Page 15
Image 15
York DJ 150 Additional Static Resistance, Electric Heat Minimum Supply Air Cfm, Indoor Blower Specifications, Economizer2