York DNP060, DNP048, DNP030, DNP024 DNP042 COOLING CAPACITIES - 3-1/2TON, 036-21366-007-A-1205

Models: DNP036 DNP042 DNP024 DNP030 DNP048 DNP060

1 36
Download 36 pages 46.01 Kb
Page 12
Image 12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036-21366-007-A-1205

TABLE 6: DNP042 COOLING CAPACITIES - 3-1/2 TON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMPERATURE

 

 

 

 

 

 

AIR ON EVAPORATOR COIL

 

 

 

 

 

 

 

 

1,350 CFM

 

 

 

 

1,500 CFM

 

 

OF AIR ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB °F

 

 

 

 

 

 

WB °F

 

CONDENSER COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

67

 

62

 

57

72

 

67

 

62

57

 

 

 

NET CAP.

 

48.4

44.5

 

40.9

 

41.2

54.0

 

49.6

 

45.6

46.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TOTAL POWER

 

3.4

3.3

 

3.3

 

3.3

3.8

 

3.7

 

3.6

3.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

86

33.0

39.9

 

40.9

 

41.2

36.8

 

44.4

 

45.6

46.0

 

CapacitySensible

 

 

 

 

83

29.1

36.0

 

40.9

 

41.2

32.4

 

40.1

 

45.6

46.0

85 °F

MBH

 

DryEntering

°FBulb

80

25.2

32.0

 

38.1

 

40.4

28.1

 

35.7

 

42.4

45.0

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

77

21.3

28.1

 

34.2

 

36.5

23.7

 

31.3

 

38.1

40.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

74

17.3

24.2

 

30.2

 

32.6

19.3

 

27.0

 

33.7

36.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

71

N/A

20.3

 

26.3

 

28.7

N/A

 

22.6

 

29.3

31.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

68

N/A

16.4

 

22.4

 

24.7

N/A

 

18.2

 

25.0

27.6

 

 

 

NET CAP.

 

46.1

42.4

 

39.6

 

39.1

51.3

 

47.3

 

44.1

43.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TOTAL POWER

 

3.8

3.6

 

3.8

 

3.6

4.2

 

4.0

 

4.2

4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

86

32.2

38.8

 

39.6

 

39.1

35.9

 

43.3

 

44.1

43.5

 

CapacitySensible

 

 

 

 

83

28.3

34.9

 

39.6

 

39.1

31.6

 

38.9

 

44.1

43.5

95 °F

MBH

 

DryEntering

°FBulb

80

24.4

31.0

 

37.6

 

38.7

27.2

 

34.5

 

41.9

43.1

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

77

20.5

27.1

 

33.7

 

34.8

22.8

 

30.2

 

37.6

38.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

74

16.6

23.1

 

29.8

 

30.8

18.5

 

25.8

 

33.2

34.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

71

N/A

19.2

 

25.9

 

26.9

N/A

 

21.4

 

28.8

30.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

68

N/A

15.3

 

21.9

 

23.0

N/A

 

17.1

 

24.5

25.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NET CAP.

 

43.5

40.0

 

37.2

 

37.2

48.5

 

44.6

 

41.4

41.5

 

 

TOTAL POWER

 

4.2

4.1

 

4.1

 

4.0

4.6

 

4.5

 

4.6

4.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

86

31.3

38.0

 

37.2

 

37.2

34.9

 

42.3

 

41.4

41.5

 

CapacitySensible

 

 

 

 

83

27.4

34.1

 

37.2

 

37.2

30.6

 

38.0

 

41.4

41.5

105 °F

MBH

 

DryEntering

°FBulb

80

23.5

30.2

 

36.2

 

36.7

26.2

 

33.6

 

40.3

40.9

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

77

19.6

26.2

 

32.3

 

32.8

21.8

 

29.2

 

36.0

36.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

74

15.7

22.3

 

28.3

 

28.8

17.4

 

24.9

 

31.6

32.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

71

N/A

18.4

 

24.4

 

24.9

N/A

 

20.5

 

27.2

27.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

68

N/A

14.5

 

20.5

 

21.0

N/A

 

16.1

 

22.8

23.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NET CAP.

 

41.0

37.6

 

34.7

 

35.4

45.7

 

41.9

 

38.7

39.4

 

 

TOTAL POWER

 

4.6

4.5

 

4.5

 

4.5

5.1

 

5.0

 

5.1

5.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

86

30.4

37.2

 

34.7

 

35.4

33.9

 

41.4

 

38.7

39.4

 

CapacitySensible

 

 

 

 

83

26.5

33.3

 

34.7

 

35.4

29.5

 

37.1

 

38.7

39.4

115 °F

MBH

 

DryEntering

°FBulb

80

22.6

29.3

 

34.7

 

34.7

25.2

 

32.7

 

38.7

38.7

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

77

18.7

25.4

 

30.8

 

30.8

20.8

 

28.3

 

34.3

34.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

74

14.7

21.5

 

26.9

 

26.8

16.4

 

24.0

 

30.0

29.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

71

N/A

17.6

 

23.0

 

22.9

N/A

 

19.6

 

25.6

25.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

68

N/A

13.7

 

19.0

 

19.0

N/A

 

15.2

 

21.2

21.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NET CAP.

 

38.5

35.2

 

32.3

 

33.6

43.0

 

39.2

 

36.0

37.4

 

 

TOTAL POWER

 

5.0

5.0

 

4.9

 

4.9

5.6

 

5.5

 

5.5

5.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

86

29.5

36.3

 

32.3

 

33.6

32.9

 

40.5

 

36.0

37.4

 

CapacitySensible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

83

25.6

32.4

 

32.3

 

33.6

28.5

 

36.1

 

36.0

37.4

125 °F

MBH

 

DryEntering

°FBulb

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

21.7

28.5

 

33.3

 

32.7

24.1

 

31.8

 

37.1

36.4

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

77

17.7

24.6

 

29.4

 

28.8

19.8

 

27.4

 

32.7

32.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

74

13.8

20.7

 

25.4

 

24.9

15.4

 

23.0

 

28.3

27.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

71

N/A

16.7

 

21.5

 

20.9

N/A

 

18.7

 

24.0

23.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

68

N/A

12.8

 

17.6

 

17.0

N/A

 

14.3

 

19.6

19.0

1.These capacities are net capacities (the indoor fan heat is deducted)

TABLE 6: DNP042 COOLING CAPACITIES - 3-1/2 TON ALL SENSIBLE CAPACITY

12

Unitary Products Group

Page 12
Image 12
York DNP060, DNP048, DNP030, DNP024, DNP036 warranty DNP042 COOLING CAPACITIES - 3-1/2TON, 036-21366-007-A-1205