TYPICAL WIRING DIAGRAM NOTES

TYPICAL WIRING DIAGRAM NOTES

1.All field wiring to be accomplished following city, local and/or national codes in effect at time of installation of this unit.

2.Caution: Label all wires prior to disconnection when ser- vicing controls. Wiring errors can cause improper and dangerous operation if any of the wire as supplied with this unit must be removed it must be replaced with type 105°C, 600V wire or equivalent clearly renumbered for identification. Verify proper operation after servicing.

3.Motors are inherently protected.

4.See unit nameplate for maximum fuse size and minimum circuit ampacity.

036-21366-007-A-1205

5.Select indoor blower cooling speed from unit wiring dia- gram Table 1. Heating speed is preset at the factory.

6.If both LR and ASCT are present, wire 801/BL and 805/ BL are connected to ASCT-3 if LR only is present wire 801/BL and 805/BL are connected to M1 coil. If ASCT only is present wire 202/Y is connected to ASCT-3. If neither LR or ASCT are present, Wire 202/Y is connect to M1 coil.

7.Shunt contact also used with crankcase heater. (Optional).

Open all disconnects before servicing this unit.

 

 

LEGEND :

ALS

AUXILLARY LIMIT SWITCH

ASCT

ANTI-SHORT CYCLE TIMER

 

 

(OPTIONAL ACCESSORY)

COMPR

COMPRESSOR

EAC

ELECTRIC AIR CLEANER RELAY OUTPUT

 

 

ON CONTROL BOARD, 24-1-60, 18VA MAX.

FS

FREEZESTAT SWITCH (OPTIONAL ACCESSORY)

 

 

OPEN @ 250 F

HP

HIGH PRESSURE SWITCH (OPTIONAL

 

 

ACCESSORY) OPENS @ 380 PSIG

HSP

HOT SURFACE TO PILOT

HUM

HUMIDIFER RELAY OUTPUT ON CONTROL

 

 

BOARD, 24-1-60, 18VA MAX.

LP

LOW PRESSURE SWITCH (OPTIONAL ACCESSORY)

 

 

OPEN @ 7 PSIG

LR

LOCK OUT RELAY (OPTIONAL ACCESSORY)

LS

LIMIT SWITCH

M1

CONTACTOR, COMPR. & O.D.FAN

M2

CONTACTOR, DRAFT INDUCER MOTOR

PS

PRESSURE SWITCH MAKES @

 

 

.193 IWC NOM. (.33 IWC MAX.)

RC1/RC2

COMPR. START & OUTDOOR FAN RUN CAPACITOR

RS

ROLL OUT SWITCH

T1

TRANSFORMER, 24V, 40VA

T2

TRANSFORMER, 480/240 VOLT

TB2

TERMINAL BLOCK, 24V, I.D.

 

 

MOTOR "SPEED" CONNECTION

 

 

IDENTIFIED TERMINAL ON CAPACITOR

 

 

ROOM THERMOSTAT 24V CONNECTIONS

 

 

TB1 ON CONTROL BOARD

 

 

FACTORY WIRING AND DEVICES

 

 

 

 

OPTIONAL WIRING AND DEVICES

 

 

FIELD WIRING

 

 

DNP LEGEND WIRING DIA.

 

 

 

FIGURE 21 - TYPICAL WIRING DIAGRAM LEGEND