TABLE 10: SIDE SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS1

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE - IWG

 

 

 

MODEL #

MODE

 

 

 

 

 

 

 

 

 

 

 

 

CFM

.20

.30

.40

 

.50

.60

.70

 

.80

.90

1.0

DNP

(COOLING / HEATING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

WATTS

WATTS

 

WATTS

WATTS

WATTS

 

WATTS

WATTS

WATTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

030

COOLING

1000

248

298

325

 

365

385

411

 

470

498

500

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

030

COOLING

1250

342

385

431

 

474

510

562

 

614

657

694

(FIELD SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

030

HEATING (2 TUBE)

850

169

217

237

 

278

302

334

 

374

401

431

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

030

HEATING (3 TUBE)

1100

300

338

378

 

416

447

493

 

539

576

609

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

COOLING

1200

354

396

436

 

511

548

599

 

641

677

721

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

COOLING

1350

442

503

563

 

606

648

685

 

721

774

826

(FIELD SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

HEATING (2 TUBE)

700

207

231

254

 

298

320

349

 

-

-

-

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

HEATING (3 TUBE)

1250

383

432

478

 

543

581

628

 

-

-

-

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

HEATING (4 TUBE)

1350

442

503

563

 

606

648

685

 

-

-

-

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

COOLING

1350

410

457

504

 

575

646

687

 

729

780

830

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

COOLING

1500

450

500

553

 

641

729

798

 

830

872

939

(FIELD SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

HEATING (3 TUBE)

1500

450

500

553

 

641

729

798

 

830

872

939

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

HEATING (4 TUBE)

1275

388

433

478

 

545

612

652

 

691

739

787

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048

COOLING

1400

427

476

525

 

599

673

716

 

759

812

865

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048

COOLING

1600

476

532

587

 

687

786

872

 

958

994

1030

(FIELD SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048

HEATING (3 TUBE)

1525

458

511

564

 

654

744

814

 

-

-

-

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048

HEATING (4 TUBE)

1600

476

532

587

 

687

786

872

 

-

-

-

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048

HEATING (5 TUBE)

1600

476

532

587

 

687

786

872

 

-

-

-

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

COOLING

1500

439

526

559

 

636

716

748

 

816

884

941

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

COOLING

1800

659

809

814

 

946

1001

1053

 

1124

1176

1180

(FIELD SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

HEATING (3 TUBE)

1500

439

526

559

 

636

716

748

 

816

884

941

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

HEATING (4 TUBE)

1700

576

757

788

 

872

929

979

 

1000

1121

1188

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

HEATING (5 TUBE)

1700

576

757

788

 

872

929

979

 

1000

1121

1188

(FACTORY SETTING)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Above data includes allowances for a dry coil, gas heat exchanger and no filters. For additional pressure drops, refer to Tables 11 and 12.