036-21366-007-A-1205

TABLE 12: ADDITIONAL STATIC PRESSURE RESISTANCE - 2, 2-1/2, 3 TON

 

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

600

700

800

900

1,000

 

1,100

1,200

1,300

1,400

1,500

1,600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WET EVAPORATOR COIL

.01

.01

.01

.02

.03

.04

 

.05

.06

.07

.08

.09

.09

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECONOMIZER1

.00

.00

.00

.01

.01

.01

 

.01

.02

.03

.04

.05

.06

FILTER FRAME KIT

.01

.02

.04

.06

.08

.10

 

.13

.16

.17

.18

.19

.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 13: ADDITIONAL STATIC PRESSURE RESISTANCE - 3-1/2, 4 AND 5 TON

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1,100

1,200

1,300

1,400

1,500

 

1,600

1,700

1,800

1,900

2,000

 

 

 

 

 

 

 

 

 

 

 

 

WET EVAPORATOR COIL

.02

.03

.04

.05

.06

 

.07

.07

.08

.09

.09

 

 

 

 

 

 

 

 

 

 

 

 

ECONOMIZER1

.02

.02

.02

.03

.03

 

.04

.04

.04

.05

.05

FILTER FRAME KIT

.04

.04

.05

.05

.06

 

.07

.08

.09

.10

.11

 

 

 

 

 

 

 

 

 

 

 

 

1.The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

THERMOSTAT

UNIT TERMINAL STRIP

** = Minimum wire size of 18 AWG

R

**

R

wire should be used for all

 

 

 

field installed 24 volt wire.

G

 

G

 

 

 

Y

 

Y

 

W

 

W

 

C

 

C

PROGRAMMABLE

THERMOSTAT ONLY

FIGURE 3 - FIELD WIRING DIAGRAM CONTROL WIRING

NOTE:

HEAT ANTICIPATOR SHOULD BE SET AT 0.35 AMPS FOR ALL MODELS.

24VOLT TRANSFORMER

18

Unitary Products Group

Page 18
Image 18
York DNP060 Additional Static Pressure Resistance 2, 2-1/2, 3 TON, Resistance, Iwg, RESISTANCE, IWG Description CFM