TABLE 7: COOLING CAPACITY DR120 UNIT

Air On Evap. Coil

 

Temperature of Air on Condenser Coil 85°F

 

 

 

Temperature of Air on Condenser Coil 95°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

Tot.

 

 

Sensible Capacity (MBH)

 

 

Total

Tot.

 

 

Sensible Capacity (MBH)

 

 

CFM

WB (°F)

Cap.1

Input2

 

 

 

 

 

 

 

 

 

Cap.1

Input2

 

 

 

 

 

 

 

 

 

 

 

 

Return Dry Bulb (°F)

 

 

 

 

 

Return Dry Bulb (°F)

 

 

 

 

(MBH)

(kW)

86

83

 

80

77

74

 

71

68

(MBH)

(kW)

86

83

 

80

77

74

 

71

68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

134

8.6

80

72

 

63

54

46

 

37

29

126

9.4

76

67

 

59

50

42

 

33

24

3000

67

121

8.4

96

88

 

79

71

62

 

53

45

113

9.1

93

85

 

76

67

59

 

50

42

62

110

8.3

110

105

 

97

88

79

 

71

62

103

8.9

103

101

 

92

84

75

 

66

58

 

 

 

 

 

 

57

108

8.2

108

108

 

99

91

82

 

74

65

100

8.9

100

100

 

93

84

76

 

67

58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

139

8.7

89

79

 

68

58

48

 

38

28

130

9.4

84

74

 

63

53

43

 

33

23

3500

67

125

8.5

106

96

 

86

76

66

 

56

46

117

9.2

102

92

 

82

72

62

 

52

42

62

114

8.3

114

112

 

105

95

85

 

75

65

106

8.9

106

105

 

100

89

79

 

69

59

 

 

 

 

 

 

57

112

8.3

112

112

 

108

98

88

 

78

67

104

8.9

104

104

 

100

90

80

 

70

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

144

8.8

97

86

 

74

62

51

 

39

27

135

9.5

91

80

 

68

56

45

 

33

22

4000

67

130

8.6

116

105

 

93

81

70

 

58

46

121

9.2

112

100

 

88

77

65

 

53

42

62

119

8.4

119

119

 

113

102

90

 

78

67

110

9.0

110

110

 

107

95

84

 

72

60

 

 

 

 

 

 

57

117

8.4

117

117

 

117

105

93

 

82

70

108

8.9

108

108

 

108

96

84

 

73

61

 

72

147

8.8

105

92

 

78

65

52

 

39

25

137

9.6

99

86

 

73

59

46

 

33

20

4500

67

133

8.6

125

112

 

99

85

72

 

59

45

123

9.3

119

107

 

94

81

68

 

54

41

62

121

8.4

121

121

 

118

105

92

 

79

65

112

9.0

112

112

 

110

97

84

 

70

57

 

 

 

 

 

 

57

119

8.4

119

119

 

119

106

92

 

79

66

109

9.0

109

109

 

109

96

83

 

70

56

 

72

150

8.9

113

98

 

83

68

53

 

38

23

139

9.6

107

92

 

77

62

47

 

32

18

5000

67

135

8.7

134

119

 

104

89

74

 

59

45

125

9.3

125

115

 

100

85

70

 

55

40

62

123

8.5

123

123

 

123

109

94

 

79

64

113

9.1

113

113

 

113

98

84

 

69

54

 

 

 

 

 

 

57

121

8.4

121

121

 

121

107

92

 

77

62

111

9.1

111

111

 

111

96

81

 

66

51

 

 

 

Temperature of Air on Condenser Coil 105°F

 

 

 

Temperature of Air on Condenser Coil 115°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

117

10.0

73

64

 

55

47

38

 

30

21

108

10.6

69

61

 

52

44

35

 

27

18

3000

67

105

9.7

90

81

 

72

64

55

 

47

38

97

10.2

86

77

 

69

60

52

 

43

35

62

94

9.4

94

93

 

85

77

68

 

60

51

86

9.9

86

86

 

78

70

61

 

53

44

 

 

 

 

 

 

57

94

9.4

94

94

 

86

78

69

 

61

52

88

10.0

88

88

 

80

71

63

 

54

46

 

72

121

10.1

80

70

 

60

50

40

 

30

19

111

10.7

77

67

 

56

46

36

 

26

16

3500

67

109

9.7

98

88

 

78

68

58

 

48

38

100

10.3

94

85

 

74

64

54

 

44

34

62

97

9.5

97

97

 

92

82

72

 

62

52

88

10.0

88

88

 

85

74

64

 

54

44

 

 

 

 

 

 

57

97

9.5

97

97

 

93

83

73

 

63

53

90

10.1

90

90

 

86

76

66

 

56

46

 

72

124

10.1

88

76

 

64

53

41

 

29

18

114

10.8

84

72

 

61

49

37

 

26

14

4000

67

112

9.8

107

96

 

84

72

61

 

49

37

103

10.4

103

92

 

80

68

57

 

45

33

62

100

9.5

100

100

 

99

87

76

 

64

52

91

10.1

91

91

 

91

79

67

 

56

44

 

 

 

 

 

 

57

100

9.5

100

100

 

100

89

77

 

65

54

93

10.1

93

93

 

93

81

69

 

58

46

 

72

126

10.2

95

82

 

69

55

42

 

29

16

115

10.9

91

78

 

65

51

38

 

25

12

4500

67

114

9.9

111

103

 

90

76

63

 

50

37

104

10.5

104

98

 

85

72

59

 

45

32

62

102

9.6

102

102

 

101

88

74

 

61

48

92

10.1

92

92

 

92

79

65

 

52

39

 

 

 

 

 

 

57

102

9.6

102

102

 

102

88

75

 

62

48

94

10.2

94

94

 

94

81

67

 

54

41

 

72

128

10.3

103

88

 

73

58

43

 

28

13

117

10.9

98

84

 

69

54

39

 

24

9

5000

67

115

9.9

115

110

 

95

80

65

 

51

36

105

10.5

105

105

 

91

76

61

 

46

31

62

103

9.7

103

103

 

103

88

73

 

58

44

93

10.2

93

93

 

93

78

63

 

48

33

 

 

 

 

 

 

57

103

9.7

103

103

 

103

88

73

 

58

43

95

10.3

95

95

 

95

80

65

 

50

35

 

 

 

Temperature of Air on Condenser Coil 125°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

99

11.2

66

58

 

49

41

32

 

23

15

 

 

 

 

 

 

 

 

 

 

 

3000

67

89

10.8

82

74

 

65

57

48

 

40

31

 

 

 

 

 

 

 

 

 

 

 

62

78

10.4

78

78

 

71

63

54

 

46

37

1- These capacities are gross ratings. For net capacity,

 

 

 

 

 

 

 

 

57

82

10.6

82

82

 

74

65

57

 

48

40

 

deduct air blower motor, MBh = 3.415 x kW. Refer to the

 

 

72

102

11.3

73

63

 

53

43

33

 

23

13

 

appropriate Blower Performance Table for the kW of the

 

 

 

 

 

supply air blower motor.

 

 

 

 

 

 

 

3500

67

91

10.9

90

81

 

70

60

50

 

40

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

79

10.5

79

79

 

77

67

57

 

47

37

2- These ratings include the condenser fan motors (total 1

 

 

 

 

 

 

57

83

10.6

83

83

 

80

69

59

 

49

39

 

kW) and the compressor motors but not the supply air

 

 

 

72

104

11.4

80

68

 

57

45

33

 

22

10

 

blower motor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4000

67

94

11.0

94

87

 

76

64

52

 

41

29

 

 

 

 

 

 

 

 

 

 

 

 

62

81

10.6

81

81

 

81

71

59

 

48

36

 

-

-No sensible cooling capacity.

 

 

 

 

 

57

85

10.7

85

85

 

85

74

62

 

50

39

 

 

 

 

 

 

 

 

 

 

 

 

72

105

11.5

87

74

 

61

47

34

 

21

8

 

 

 

 

 

 

 

 

 

 

 

4500

67

94

11.0

94

94

 

81

67

54

 

41

28

 

 

 

 

 

 

 

 

 

 

 

62

82

10.7

82

82

 

82

69

56

 

43

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

86

10.8

86

86

 

86

73

60

 

46

33

 

 

 

 

 

 

 

 

 

 

 

 

72

106

11.6

94

79

 

64

50

35

 

20

5

 

 

 

 

 

 

 

 

 

 

 

5000

67

95

11.1

95

95

 

86

71

56

 

41

26

 

 

 

 

 

 

 

 

 

 

 

62

83

10.8

83

83

 

83

68

53

 

38

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

87

10.9

87

87

 

87

72

57

 

42

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unitary Products Group

19

Page 19
Image 19
York DR090, DR150 manual COOLING CAPACITY DR120 UNIT, YTG-C-0606, Unitary Products Group