TABLE 4 - BLOWER PERFORMANCE
KEU090 - SUPPLY AIR BLOWER PERFORMANCE1 - (CFM)
BLOWER |
|
|
|
|
|
|
|
|
|
|
|
| AIRFLOW |
|
|
|
|
|
|
|
|
|
|
| ||
SPEED | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT |
| INPUT | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT | INPUT | ||||||||||
RPM | (IWG) | (BHP) |
| (kW) | (IWG) | (BHP) |
| (KW) | (IWG) | (BHP) |
| (kW) | (IWG) | (BHP) |
| (kW) | (IWG) | (BHP) |
| (kW | ||||||
|
| 2400 CFM |
|
| 2700 CFM |
|
| 3000 CFM |
|
| 3300 CFM |
|
| 3600CFM |
| |||||||||||
600 | 0.35 | 0.62 |
|
| 0.59 | 0.26 | 0.70 |
|
| 0.66 | 0.13 | 0.78 |
|
| 0.73 | - | - |
|
| - | - | - |
|
| - | |
655 | 0.49 | 0.70 |
|
| 0.66 | 0.41 | 0.78 |
|
| 0.72 | 0.30 | 0.87 |
|
| 0.82 | 0.07 | 0.96 |
|
| 0.90 | - | - |
|
| - | |
700 | 0.60 | 0.77 |
|
| 0.73 | 053 | 0.85 |
|
| 0.80 | 043 | 0.95 |
|
| 0.89 | 0.29 | 1.06 |
|
| 0.99 | 0.12 | 1.17 |
|
| 1.09 | |
800 | 0.92 | 0.97 |
|
| 0.90 | 0.85 | 1.06 |
|
| 0.99 | 0.77 | 1.18 |
|
| 1.10 | 0.65 | 1.30 |
|
| 1.21 | 0.49 | 1.42 |
|
| 1.32 | |
880 | 1.18 | 1.11 |
|
| 1.04 | 1.11 | 1.24 |
|
| 1.16 | 1.03 | 1.37 |
|
| 1.28 | 0.91 | 1.50 |
|
| 1.38 | 0.77 | 1.64 |
|
| 1.53 | |
900 | 1.24 | 1.15 |
|
| 1.07 | 1.18 | 1.28 |
|
| 1.19 | 1.10 | 1.42 |
|
| 1.32 | 0.98 | 1.55 |
|
| 1.43 | 0.84- | 1.70 |
|
| 1.57 | |
1000 | 1.58 | 1.35 |
|
| 1.26 | 1.53 | 1.48 |
|
| 1.38 | 1.46 | 1.63 |
|
| 1.48 | 1.37 | 1.81 |
|
| 1.65 | 1.24 | 2.02 |
|
| 1.85 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
KEU090 - SUPPLY AIR BLOWER PERFORMANCE1 - (m3/s) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| AIRFLOW |
|
|
|
|
|
|
|
|
|
|
| ||
BLOWER | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT | INPUT | |||||||||||
SPEED | (Pa) | (kW) |
| (kW) | (Pa) | (kW) |
| (kW) | (Pa) | (kW) |
|
| (kW) | (Pa) | (kW) |
|
| (kW) | (Pa) | (kW) |
|
| (kW) | |||
RPM |
|
|
|
|
|
|
|
| ||||||||||||||||||
| 1.1 m3/s |
|
| 1.3 m3/s |
|
| 1.4 m3/s |
|
| 1.6 m3/s |
|
| 1.7 m3/s |
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||
600 | 87 | 0.46 |
|
| 0.59 | 64 | 0.52 |
|
| 0.66 | 32 | 0.45 |
|
| 0.73 | - | - |
|
| - | - | - |
|
| - | |
655 | 122 | 0.52 |
|
| 0.66 | 102 | 0.58 |
|
| 0.72 | 74 | 0.65 |
|
| 0.82 | 17 | 0.72 |
|
| 0.90 | - | - |
|
| - | |
700 | 149 | 0.57 |
|
| 0.73 | 131 | 0.63 |
|
| 0.80 | 107 | 0.71 |
|
| 0.89 | 72 | 0.79 |
|
| 0.99 | 30 | 0.87 |
|
| 1.09 | |
800 | 228 | 0.72 |
|
| 0.90 | 211 | 0.79 |
|
| 0.99 | 191 | 0.88 |
|
| 1.10 | 161 | 0.97 |
|
| 1.21 | 122 | 1.06 |
|
| 1.32 | |
880 | 293 | 0.83 |
|
| 1.04 | 275 | 0.92 |
|
| 1.16 | 255 | 1.02 |
|
| 1.28 | 226 | 1.12 |
|
| 1.38 | 191 | 1.22 |
|
| 1.53 | |
900 | 308 | 0.86 |
|
| 1.07 | 293 | 0.95 |
|
| 1.19 | 273 | 1.06 |
|
| 1.32 | 243 | 1.15 |
|
| 1.43 | 208 | 1.27 |
|
| 1.57 | |
1000 | 392 | 1.01 |
|
| 1.26 | 379 | 1.10 |
|
| 1.38 | 362 | 1.21 |
|
| 1.48 | 340 | 1.35 |
|
| 1.65 | 308 | 1.50 |
|
| 1.85 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
KEU120- SUPPLY AIR BLOWER PERFORMANCE1 (CFM) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
BLOWE |
|
|
|
|
|
|
|
|
|
|
|
| AIRFLOW |
|
|
|
|
|
|
|
|
|
|
| ||
R | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT | INPUT | |||||||||||
SPEED | (IWG) | (BHP) |
| (kW) | (IWG) | (BHP) |
| (kW) | (IWG) | (BHP) |
| (kW) | (IWG) | (BHP) |
| (kW) | (IWG) | (BHP) |
| (kW) | ||||||
RPM |
| 3200 |
|
|
| 3600 |
|
|
| 4000 |
|
|
| 4400 |
|
|
| 4800 |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
700 | 0.49 | 1.01 |
|
| 0.94 | 0.34 | 1.17 |
| 1.09 | 0.14 | 1.33 |
|
| 1.24 | - | - |
|
| - | - | - |
|
| - | ||
800 | 0.84 | 1.25 |
|
| 1.16 | 0.71 | 1.42 |
| 1.32 | 0.53 | 1.60 |
|
| 1.48 | 0.30 | 1.80 |
|
| 1.64 | - | - |
|
| - | ||
900 | 1.18 | 1.48 |
|
| 1.38 | 1.06 | 1.70 |
| 1.57 | 0.91 | 1.92 |
|
| 1.75 | 0.70 | 2.18 |
|
| 1.99 | 0.43 | 2.45 |
|
| 2.24 | ||
950 | 1.37 | 1.61 |
|
| 1.50 | 1.26 | 1.86 |
| 1.71 | 1.11 | 2.12 |
|
| 1.95 | 0.90 | 2.39 |
|
| 2.18 | 0.65 | 2.67 |
|
| 2.44 | ||
1000 | 1.56 | 1.75 |
|
| 1.62 | 1.46 | 2.02 |
| 1.85 | 1.32 | 2.30 |
|
| 2.10 | 1.13 | 2.60 |
|
| 2.38 | 0.87 | 2.90 |
|
| 2.65 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
KEU120 - SUPPPLY AIR BLOWER PERFORMANCE1 (m3/s) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
BLOWE |
|
|
|
|
|
|
|
|
|
|
|
| AIRFLOW |
|
|
|
|
|
|
|
|
|
|
| ||
R | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT | INPUT | ESP2 | OUTPUT | INPUT | |||||||||||
SPEED | (Pa) | (kW) |
| (kW) | (Pa) | (kW) |
| (kW) | (Pa) | (kW) |
| (kW) | (Pa) | (kW) |
| (kW) | (Pa) | (kW) |
| (kW) | ||||||
RPM |
| 3 | /s |
|
| 1.7m | 3 | /s |
|
| 3 | /s |
|
| 3 | /s |
|
| 3 | /s |
| |||||
|
| 1.5 m |
|
|
|
|
| 1.9 m |
|
| 2.0 m |
|
| 2.3 m |
| |||||||||||
700 | 122 | 0.75 |
|
| 0.94 | 84 | 0.87 |
| 1.09 | 35 | 0.99 |
|
| 1.24 | - | - |
|
| - | - | - |
|
| - | ||
800 | 208 | 0.93 |
|
| 1.16 | 176 | 1.05 |
| 1.32 | 131 | 1.19 |
|
| 1.48 | 74 | 1034 |
| 1.64 | - | - |
|
| - | |||
900 | 293 | 1.10 |
|
| 1.38 | 263 | 1.27 |
| 1.57 | 226 | 1.43 |
|
| 1.75 | 174 | 1.62 |
|
| 1.99 | 107 | 1.83 |
|
| 2.24 | ||
950 | 340 | 1.20 |
|
| 1.50 | 312 | 1.39 |
| 1.71 | 275 | 1.58 |
|
| 1.95 | 223 | 1.78 |
|
| 2.18 | 161 | 1.99 |
|
| 2.44 | ||
1000 | 387 | 1.30 |
|
| 1.62 | 362 | 1.50 |
| 1.85 | 327 | 1.71 |
|
| 2.10 | 280 | 1.94 |
|
| 2.38 | 216 | 2.16 |
|
| 2.65 |
1Unit resistance is based on a wet evaporator coil and clean filters.
2Available static pressure in IWG (Pa) to overcome the resistance of the duct system and any accessories added to the unit. Refer to Table 6 for the resistance of these accessories and to Table 7 for additional motor and drive data
NOTE: Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heating device.
LEGEND:
RPM range for the standard
Exceeds the BHP limitation of the standard
8 | Unitary Products Group |