York K4EU120A50A Electrical Data, Accessory External Static Pressure Drop Resistance, Fla

Models: K4EU120A50A K5EU090A50A

1 12
Download 12 pages 34.45 Kb
Page 9
Image 9

550.39-N4YI

TABLE 5 - ACCESSORY STATIC RESISTANCE (IWG)

KEU090

ACCESSORY

EXTERNAL STATIC PRESSURE DROP RESISTANCE

 

 

IWG/pA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWER CFM/m3/s

2400 / 1.1

2700 / 1.3

3000 / 1.4

3300 / 1.6

3600 / 1.7

 

10k W

0.01 / 2.5

0.01 / 2.5

0.01/ 2.5

0.02 / 5.0

0.02/ 5.0

 

 

 

 

 

 

 

Electric

16 kW

0.01 / 2.5

0.02 / 5.0

0.02 / 5.0

0.03 / 7.4

0.04/ 10.0

 

 

 

 

 

 

Heat

26 kW

0.03 / 7.4

0.4/ 10.0

0.05 / 12.4

0.06/ 15.0

0.07 / 17.4

 

 

 

 

 

 

 

 

 

36 kW

0.05 / 12.4

0.07 / 17.4

0.08 / 20.0

0.10 / 25.0

0.11 / 27.0

 

 

 

 

 

 

 

Supply Air Plenum

0.03 / 7.4

0.03 / 7.4

0.04 / 10.0

0.05 / 12.4

0.06 / 15.0

 

 

 

 

 

 

 

Return Air Grille

0.02 / 5.0

0.03 / 7.4

0.04 / 10.0

0.05 / 12.4

0.06 / 15.0

 

 

 

 

 

 

 

Add these pressures to the ESP values in the respective blower performance table.

KEU120

ACCESSORY

EXTERNAL STATIC PRESSURE DROP RESISTANCE

 

 

IWG/pA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWER CFM/m3/s

3200 / 1.5

3600 / 1.7

4000 / 1.9

4400 / 2.1

4800 / 2.3

 

10 kW

0.02 / 5.0

0.02 / 5.0

0.03 / 7.4

0.03 / 7.4

0.04 / 10.0

 

 

 

 

 

 

 

Electric

16 kW

0.03 / 7.4

0.04 / 10.0

0.05 / 12.4

0.06 / 15.0

0.07 / 17.4

 

 

 

 

 

 

Heat

26 kW

0.06 / 15.0

0.07 / 17.4

0.09 / 22.3

0.11 / 27.0

0.13 / 32.2

 

 

 

 

 

 

 

 

 

36 kW

0.09 / 22.3

0.11 / 27.0

0.14 / 35.0

0.17 / 42.2

0.20 / 50.0

 

 

 

 

 

 

 

Supply Air Plenum

0.05 / 12.4

0.06 / 15.0

0.07 / 17.4

0.08 / 20.0

0.10 / 25.0

 

 

 

 

 

 

 

Return Air Grille

0.05 / 12.4

0.06 / 15.0

0.07 / 17.4

0.08 / 20.0

0.10 / 25.0

Add these pressures to the ESP values in the respective blower performance table.

TABLE 6 - ELECTRICAL DATA

Model

Blower Motor

Power Supply

FLA

Maximum

Maximum

HP/kW

Fuse Size* Amps

Wire Length* * Ft.(m)

 

 

 

 

 

 

 

 

 

KEU090

112 /1.1

380/415-3-50

3.7

5

650 / 197

 

 

 

 

 

 

KEU120

2 / 1.5

380/415-3-50

4.5

5

500 / 152

 

 

 

 

 

 

* Dual element, time delay fuses.

** Based on three 60° C, 14 AWG, insulated copper conductors in steel conduit and a 3% voltage drop.

Unitary Products Group

9

Page 9