TABLE 19: Air Flow Data - 60 Hz Models (230 & 460 Volt)

Models

Models

Blower Motor

 

 

 

 

 

230 / 460 Volt - 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM1 @ External Static Pressure - IWC

 

 

 

MA

MC

Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.1

0.2

0.3

 

0.4

 

0.5

0.6

 

0.7

 

0.8

0.9

1

 

 

High

1102

986

870

 

754

 

638

521

 

405

 

289

173

57

 

MC18B**H

Med.

831

737

644

 

551

 

457

364

 

271

 

178

84

N/A

08B

 

Low

615

537

458

 

379

 

300

221

 

142

 

63

N/A

N/A

 

High

1112

1001

890

 

780

 

669

558

 

447

 

336

225

114

 

 

 

 

 

 

 

MC24B**H

Med.

851

759

667

 

576

 

484

392

 

300

 

208

116

25

 

 

Low

643

562

480

 

399

 

317

236

 

154

 

73

N/A

N/A

 

 

High

1511

1355

1199

 

1043

 

887

731

 

576

 

420

264

108

 

MC30B**H

Med.

1241

1107

973

 

839

 

705

572

 

438

 

304

170

36

12B

 

Low

1100

980

861

 

741

 

622

502

 

383

 

263

144

24

 

High

1464

1286

1108

 

929

 

751

573

 

394

 

216

38

N/A

 

 

 

 

 

 

 

MC36B**H

Med.

1195

1050

905

 

761

 

616

471

 

326

 

181

37

N/A

 

 

Low

1073

944

815

 

687

 

558

429

 

300

 

172

43

N/A

 

 

High

1959

1874

1802

 

1708

 

1606

1486

 

1408

 

1264

953

810

 

MC42C**H

Med.

1631

1587

1542

 

1473

 

1395

1315

 

1218

 

967

821

533

16C

 

Low

1447

1431

1401

 

1363

 

1304

1241

 

1098

 

844

751

712

 

High

2018

1895

1772

 

1649

 

1525

1402

 

1279

 

1156

1033

910

 

 

 

 

 

 

 

MC48C**H

Med.

1684

1595

1506

 

1417

 

1328

1240

 

1151

 

1062

973

884

 

 

Low

1561

1476

1392

 

1308

 

1223

1139

 

1055

 

970

896

801

 

 

High

1715

1671

1608

 

1547

 

1460

1338

 

1232

 

1003

727

508

 

MC48D**H

Med.

1471

1438

1367

 

1318

 

1263

1180

 

920

 

824

587

503

 

 

Low

1379

1330

1276

 

1227

 

1157

1047

 

866

 

681

567

392

 

 

High

1763

1713

1649

 

1581

 

1511

1407

 

1276

 

995

852

N/A

14D

MC60D**H

Med.

1487

1462

1412

 

1356

 

1280

1210

 

1087

 

795

726

N/A

 

 

Low

1381

1353

1292

 

1225

 

1186

1057

 

863

 

780

669

N/A

 

 

High

1746

1699

1655

 

1579

 

1486

1399

 

1264

 

1093

796

581

 

MC61D**H

Med.

1486

1442

1393

 

1333

 

1270

1189

 

1081

 

776

628

450

 

 

Low

1392

1336

1285

 

1226

 

1158

1061

 

882

 

740

680

445

 

 

High

2226

2190

2103

 

2035

 

1931

1845

 

1683

 

1541

1465

1328

 

MC48D**H

Med.

2115

2087

2017

 

1951

 

1851

1744

 

1542

 

1466

1406

1254

 

 

Low

N/A

N/A

N/A

 

1716

 

1643

1554

 

1451

 

1379

1292

1151

 

 

High

2326

2235

2192

 

2107

 

2027

1906

 

1786

 

1538

1469

1368

20D

MC60D**H

Med.

2150

2089

2036

 

2008

 

1944

1852

 

1692

 

1499

1416

1295

 

 

Low

1737

1752

1745

 

1718

 

1676

1600

 

1447

 

1389

1311

1200

 

 

High

2357

2321

2254

 

2191

 

2139

1951

 

1859

 

1656

1556

1472

 

MC61D**H

Med.

2212

2144

2111

 

2069

 

1986

1862

 

1727

 

1566

1498

1369

 

 

Low

1765

1783

1803

 

1779

 

1723

1646

 

1514

 

1442

1381

1245

1. Includes return air filter, coil, and 10kW electric heater.