262675-UIM-A-0806

TABLE 13: Electrical Data - (For Single Source Power Supply) - Copper Wire 1 Ø - 208/230-1-60

 

 

 

 

 

 

 

 

 

 

 

 

Models

Heat Kit - Single

Heater

 

 

Field Wiring

 

 

 

 

 

 

 

 

 

Amps

Min. Circuit Ampacity

Max. O.C.P.1

Amps/Type

75°C Wire Size - AWG

MA

Phase*

240V

 

 

 

 

 

 

 

 

 

208V

240V

208V

 

240V

208V

240V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4HK*6500206

10.4

13.03

14.88

15

 

15

14

14

08BN21

4HK*6500506

20.0

23.42

26.88

30

 

30

10

10

4HK*6500806

31.3

35.60

41.00

40

 

45

8

8

 

 

 

4HK*6501006

40.0

45.08

51.88

50

 

60

8

6

 

4HK*6500506

20.0

25.79

29.38

30

 

30

10

10

12BN21

4HK*6500806

31.3

37.98

43.50

40

 

45

8

8

4HK*6501006

40.0

47.46

54.38

50

 

60

8

6

 

 

 

4HK165N1506

60.0

69.13

79.38

70

 

90

4

3

 

4HK*6500506

20.0

24.29

28.00

30

 

30

8

10

 

4HK*6500806

31.3

36.48

42.13

40

 

45

8

8

14DN21

4HK*6501006

40.0

45.96

53.00

50

 

60

8

6

4HK16501506

60.0

67.63

78.00

70

 

90

4

3

 

 

 

4HK16501806

73.3

82.07

94.63

90

 

100

4

3

 

4HK16502006

80.0

89.29

103.00

100

 

110

3

2

 

4HK*6500506

20.0

26.17

30.00

30

 

30

8

8

 

4HK*6500806

31.3

38.35

44.13

40

 

45

8

8

16CN21

4HK*6501006

40.0

47.83

55.00

50

 

60

8

6

4HK16501506

60.0

69.50

80.00

70

 

90

4

3

 

 

 

4HK16501806

73.3

83.94

96.63

90

 

100

4

3

 

4HK16502006

80.0

91.17

105.00

100

 

110

3

2

 

4HK*6500806

31.3

42.60

48.38

45

 

50

8

8

 

4HK*6501006

40.0

52.08

59.25

60

 

60

8

6

20DN21

4HK16501506

60.0

73.75

84.25

90

 

90

3

3

4HK16501806

73.3

88.19

100.88

90

 

110

3

2

 

 

 

4HK16502006

80.0

95.42

109.25

100

 

125

3

2

 

4HK16502506

100.0

117.08

134.25

125

 

150

1

1/0

1.O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse. * May be 0 (no breaker) or 1 (with breaker).

TABLE 14: Electrical Data - 3 Ø - 208/230-3-60

Models

Heat Kit -

Max.

Min.

 

Total Heat1

 

 

 

KW Staging

 

 

 

 

 

 

 

 

 

 

 

 

Speed

KW

MBH

W1 Only

W2 Only

W1 + W2

MA

Three Phase

Static

Tap

 

 

 

 

 

 

 

 

 

 

 

 

 

208V

240V

208V

240V

208V

240V

208V

240V

208V

240V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

08B

4HK06501025

0.5

Hi

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

12B

4HK06501025

0.5

Med

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

 

4HK06501025

0.5

Med

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

14D

 

 

 

 

 

 

 

 

 

 

 

 

 

4HK06501525

0.5

Med

10.8

14.4

36.9

49.1

10.8

14.4

10.8

14.4

10.8

14.4

 

4HK06501825

0.5

Hi

12.9

17.2

44.7

58.7

12.9

17.2

12.9

17.2

12.9

17.2

 

4HK06501025

0.5

Med

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

16C

 

 

 

 

 

 

 

 

 

 

 

 

 

4HK06501525

0.5

Med

10.8

14.4

36.9

49.1

10.8

14.4

10.8

14.4

10.8

14.4

 

4HK06501825

0.5

Hi

12.9

17.2

44.7

58.7

12.9

17.2

12.9

17.2

12.9

17.2

 

4HK06501025

0.5

Lo

7.2

9.6

24.6

32.8

7.2

9.6

7.2

9.6

7.2

9.6

20D

 

 

 

 

 

 

 

 

 

 

 

 

 

4HK06501525

0.5

Med

10.8

14.4

36.9

49.1

10.8

14.4

10.8

14.4

10.8

14.4

 

4HK16502525

0.5

Med

18.0

24.0

61.4

81.4

9.0

12.0

18.0

24.0

18.0

24.0