MA SERIES - Air Handler Control Wiring
Typical A/C - Cooling only Applications
THERMOSTAT | AIR HANDLER |
| 1 - STAGE | |||||||
| BOARD |
| ||||||||
|
|
|
| AIR CONDITIONING | ||||||
| R |
|
| R |
| |||||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| G |
|
| G |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| Y |
|
| Y / Y2 |
|
| Y |
|
| |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| W1 |
|
| Y1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| W2 |
|
| W2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| C |
|
| W1 |
|
|
|
| HUMIDISTAT * | |
|
|
|
|
|
|
| ||||
|
|
|
| O |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HUM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| X / L |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| COM |
|
| C |
|
| |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
MA SERIES - Air Handler Control Wiring
Typical A/C with Electric Heat Applications
THERMOSTAT | AIR HANDLER |
| 1 - STAGE | ||||||||
| BOARD |
| |||||||||
|
|
|
|
|
|
| AIR CONDITIONING | ||||
| R |
|
|
| R |
| |||||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| G |
|
|
| G |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| Y |
|
|
| Y / Y2 |
|
| Y |
|
| |
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Y1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| W2 |
|
|
| W2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| W1 |
|
|
| W1 |
|
|
|
| HUMIDISTAT * | |
|
|
|
|
|
|
|
| ||||
| C |
|
|
| O |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HUM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| X / L |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| COM |
|
| C |
|
| |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
FIGURE 10: Cooling Models with Electric Heat Wiring
1.“Y” Terminal on Air Handler Control Board must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.
2.Optional humidity switch - contacts open on humidity rise.
3.Remove HUM STAT Jumper on AH Control Board
4.MODE Jumper on AH control board should be set to A/C for air conditioners and HP for heat pumps.
5.To change quantity of heat during HP defrost cycle - Reverse connections at W1 & W2 on Air Handler Control Board
CONTROL WIRING - MA Series - Air Handler & New UPG HP Systems
Two Stage H/P with York Guard VI Board & Copeland “Ultra Tech”
Conventional Application - Not Hot Heat Pump
|
|
| AIR HANDLER |
|
| 2 - STAGE SCROLL | ||||
THERMOSTAT |
| BOARD |
|
| HEAT PUMP | |||||
|
|
|
|
|
|
|
|
|
|
|
| R |
|
| R |
|
|
|
| R |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| G |
|
| G |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| Y2 |
|
|
|
|
|
|
| Y2 |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Y / Y2 |
|
|
|
| Y2 OUT |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| Y1 |
|
| Y1 |
|
|
|
| Y1 |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| W2 |
|
|
|
| W2 OUT |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| E |
|
| W1 |
|
|
|
| W1 OUT |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| W |
|
|
|
|
|
|
| W |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| O |
|
| O |
|
|
|
| O |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HUM |
| HUMIDISTAT * |
| BS |
| |
|
|
|
|
|
|
| ||||
| X / L |
|
| X / L |
|
|
|
| X / L |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| C |
|
| COM |
|
|
|
| C |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
FIGURE 11:
1.“Y” Terminal on Air Handler Control Board must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.
2.Optional humidity switch - contacts open on humidity rise.
3.Remove HUM STAT Jumper on AH Control Board
4.MODE Jumper on AH control board should be set to A/C for air conditioners and HP for heat pumps.
5.To change quantity of heat during HP defrost cycle - Reverse connections at W1 & W2 on Air Handler Control Board
SECTION X: MAINTENANCE
Filters must be cleaned or replaced when they become dirty. Inspect at least once per month. The frequency of cleaning depends upon the hours of operation and the local atmospheric conditions. Clean filters keep unit efficiency high.
LUBRICATION
The bearings of the blower motor are permanently lubricated.