HORIZONTAL SUSPENSION
For suspension of these units in horizontal applications, it is recom- mended to use angle steel support brackets with threaded rods, sup- porting the units from the bottom, at the locations shown in Figure 4.
SUSPENSION SUPPORT LOCATIONS FOR HORIZONTAL APPLICATIONS | |||
MIN. 3/8” |
|
|
|
THREADED ROD |
|
|
|
MIN. |
|
| |
Recommended length |
|
|
|
26” minimum |
|
|
|
with 2” clearance on |
|
|
|
both sides of Air Handler |
|
|
|
2 |
|
| |
WW |
| YY |
|
|
| XX |
|
Units |
| Dimension |
|
(Nominal Tons) | WW | XX | YY |
16” | 48” | 22” | |
24” | 53” - 58” | 22” |
SECTION IV: ELECTRIC HEATER INSTALLATION
If the air handler requires electric heat, install the electric heat kit according to the installation instructions included with the kit. After installing the kit, mark the air handler nameplate to designate the heater kit that was installed. If no heater is installed, mark the name plate appropriately to indicate that no heat kit is installed.
The HEAT ENABLE jumper (See Figure 5) must be moved to the HEAT position to enable operation of the heater.
Use only 4HK heater kits, as listed on Air Handler name plate and in these Instructions. Use data from Tables 11 through 18 for information on required minimum motor speed tap to be used for heating operation, maximum
For Upflow, Downflow and Horizontal right hand applications the kits can be installed without modification.
Field modification is required for Horizontal
FIGURE 4: Typical Horizontal Installation
HEAT ENABLE | HUM OUT | EAC | |
RELAY OUTPUT | RELAY OUTPUT | ||
JUMPER | |||
|
|
LOW FAN
RELAY OUTPUT
MODE JUMPER
HUM STAT JUMPER
FUSE
SPARE JUMPER
FIGURE 5: Control Board
SECTION V: LOW VOLTAGE CONTROL CONNECTIONS
The 24 volt power supply is provided by an internally wired low voltage transformer which is standard on all models, However, if the unit is con- nected to a 208 volt power supply, the low voltage transformer must be rewired to the 208 volt tap. See the unit wiring label.
Field supplied low voltage wiring can exit the unit on the top right hand corner or the right hand side panel. Refer to Figure 3.
Remove desired knockout and pierce foil faced insulation to allow wir- ing to pass through. Use as small of a hole as possible to minimize air leakage.
Install a 7/8” plastic bushing in the selected hole and keep low voltage wiring as short as possible inside the control box.
To further minimize air leakage, seal the wiring entry point at the outside of the unit.
The field wiring is to be connected at the screw terminals of the control board. Refer to Figures 10 & 11.
Unitary Products Group | 5 |