FIRE OR ELECTRICAL HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
A fire or electrical hazard may result causing property damage, per- sonal injury or loss of life.
1.Install this air handler only in a location and position as specified in SECTION III of these instructions.
2.Always install the air handler to operate within the air handler’s intended maximum outlet air temperature. Only connect the air handler to a duct system which has an external static pressure within the allowable range, as specified on the air handler rating plate.
3.When an air handler is installed so that supply ducts carry air cir- culated by the air handler to areas outside the space containing the air handler, the return air shall also be handled by duct(s) sealed to the air handler casing and terminating outside the space containing the air handler.
4.The air handler is not to be used for temporary heating of buildings or structures under construction.
5.The size of the unit should be based on an acceptable heat loss or gain calculation for the structure. ACCA, Manual J or other approved methods may be used.
SAFETY REQUIREMENTS
1.This air handler should be installed in accordance with all national and local building/safety codes and requirements, local plumbing or wastewater codes, and other applicable codes.
2.Refer to the unit rating plate for the air handler model number, and then see the dimensions page of this instruction for supply air ple- num dimensions in Figure 3. The plenum must be installed accord- ing to the instructions.
3.Provide clearances from combustible materials as listed under Clearances to Combustibles.
4.Provide clearances for servicing ensuring that service access is allowed for electric heaters and blower.
5.Failure to carefully read and follow all instructions in this manual can result in air handler malfunction, death, personal injury and/or property damage.
6.Check the rating plate and power supply to be sure that the electri- cal characteristics match.
7.Air handler shall be installed so the electrical components are pro- tected from water.
8.Installing and servicing heating/cooling equipment can be hazard- ous due to the electrical components. Only trained and qualified personnel should install, repair, or service heating/cooling equip- ment. Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters. When working on heating/cooling equipment, observe precautions in the manuals and on the labels attached to the unit and other safety precautions that may apply.
9.These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances these instructions exceed certain local codes and ordinances, especially those who have not kept up with changing residential and non-HUD modular home construction practices. These instructions are required as a minimum for a safe installation.
INSPECTION
As soon as a unit is received, it should be inspected for possible dam- age during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing. Also, before installation the unit should be checked for screws or bolts, which may have loosened in transit. There are no shipping or spacer brackets which need to be removed.
Also check to be sure all accessories such as heater kits, suspension kits, and coils are available. Installation of these accessories or field conversion of the unit should be accomplished before setting the unit in place or connecting any wiring, electric heat, ducts or piping.
LIMITATIONS
These units must be wired and installed in accordance with all national and local safety codes.
Voltage limits are as follows:
| Air Handler Voltage | Voltage code | 1Normal Operating |
| Voltage Range |
| | |
| 208/230-1-60 | 21 | 187-253 |
| 460-3-60 | 41 | 432-504 |
1. Rated in accordance with ARI Standard 110, utilization range “A”.
Airflow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units.
| Entering Air Temperature Limits | |
Wet Bulb Temp.°F | Dry Bulb Temp. °F |
Min. | Max. | Min. | Max. |
57 | 72 | 65 | 95 |
SECTION III: UNIT INSTALLATION
CLEARANCES
Clearances must be taken into consideration, and provided for as fol- lows:
1.Refrigerant piping and connections - minimum 12” recommended.
2.Maintenance and servicing access - minimum 36” from front of unit recommended for blower motor / coil replacement.
3.Condensate drain lines routed to clear filter and panel access.
4.Filter removal - minimum 36” recommended.
5.A combustible floor base accessory is available for downflow applications of this unit, if required by local code.
LOCATION
Location is usually predetermined. Check with owner’s or dealer’s installation plans. If location has not been decided, consider the follow- ing in choosing a suitable location:
1.Select a location with adequate structural support, space for ser- vice access, clearance for air return and supply duct connections.
2.Use hanging brackets to wall mount unit as shown.
3.Normal operating sound levels may be objectionable if the air han- dler is placed directly over some rooms such as bedrooms, study, etc.
4.Select a location that will permit installation of condensate line to an open drain or outdoors allowing condensate to drain away from structure.
5.When an evaporator coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the air handler as is specified by most local building codes.
6.Proper electrical supply must be available.
NOTE: In severe high humidity, high temperature indoor unit environ- ments, seal completely with adequate fiberglass insulation using vapor barrier on the outside.