York MH specifications Unitary Products Group, Cooling Capacity - Coil Only, Rated CFM, Wet Bulb

Models: MH

1 16
Download 16 pages 51.4 Kb
Page 3
Image 3

 

 

 

 

 

 

 

331471-YTG-A-0507

COOLING CAPACITY - COIL ONLY*

 

 

 

 

 

 

Model Coil

Rated CFM

 

Entering Air °F

MBH@ Evaporator Temperature and Corresponding Pressure °F / PSIG

 

(Wet Bulb)

35 / 61.5

40 / 68.5

45 / 76.0

 

50 / 84.0

 

 

 

 

 

 

 

FULL-CASED “A” TYPE MULTI-POSITION

 

 

 

 

 

 

72

25.8

23.5

21.0

 

18.2

MC18A

550

 

67

23.7

21.5

19.0

 

16.4

 

62

19.5

17.3

14.9

 

12.6

 

 

 

 

 

 

 

57

15.8

13.5

11.5

 

9.0

 

 

 

72

28.7

26.1

23.3

 

20.2

MC18B

650

 

67

26.4

23.9

21.1

 

18.2

 

62

21.6

19.2

16.6

 

14.0

 

 

 

 

 

 

 

57

17.5

15.2

12.8

 

10.0

MC24A

 

 

72

36.3

33.0

29.5

 

25.6

850

 

67

33.4

30.2

26.7

 

23.1

MC24B

 

62

27.4

24.3

21.0

 

17.7

 

 

 

 

 

 

57

22.2

19.3

16.2

 

12.6

MC30A

 

 

72

41.5

37.8

33.7

 

29.5

1025

 

67

36.2

32.4

28.6

 

24.5

MC30B

 

62

29.1

25.3

24.0

 

19.2

 

 

 

 

 

 

57

24.1

21.5

18.7

 

15.8

MC35B

 

 

72

59.9

51.5

42.9

 

33.9

1200

 

67

48.0

40.3

32.8

 

25.1

MC35C

 

 

 

 

 

 

 

 

62

37.4

29.8

24.3

 

20.3

 

 

 

 

 

 

57

32.1

28.1

22.9

 

19.2

 

 

 

72

46.8

42.6

38.1

 

33.6

MC36A

1150

 

67

37.5

33.1

29.1

 

24.7

 

62

29.3

24.6

26.8

 

20.0

 

 

 

 

 

 

 

57

25.1

23.2

21.4

 

20.0

 

 

 

72

52.0

47.3

42.3

 

37.3

MC36B

1250

 

67

41.7

36.8

32.3

 

27.4

 

62

32.5

27.3

29.8

 

22.2

 

 

 

 

 

 

 

57

27.9

25.8

23.8

 

22.2

 

 

 

72

53.4

48.6

43.4

 

38.3

MC36C

1250

 

67

42.8

37.8

33.1

 

28.2

 

62

33.4

28.1

30.6

 

22.8

 

 

 

 

 

 

 

57

28.7

26.5

24.5

 

22.8

MC42B

 

 

72

74.6

64.1

53.4

 

42.2

1400

 

67

59.8

50.1

40.8

 

31.2

MC42C

 

62

46.6

37.1

30.2

 

25.2

 

 

 

 

 

 

57

40.0

35.0

28.5

 

23.9

 

 

 

72

78.3

67.4

56.1

 

44.3

MC43C

1400

 

67

62.7

52.6

42.9

 

32.8

 

62

48.9

38.9

31.7

 

26.5

 

 

 

 

 

 

 

57

42.0

36.8

29.9

 

25.1

MC48C

 

 

72

83.9

72.1

60.1

 

47.4

1650

 

67

67.2

56.4

45.9

 

35.1

MC48D

 

 

 

 

 

 

 

 

62

52.4

41.7

33.9

 

28.4

 

 

 

 

 

 

57

45.0

39.4

33.0

 

27.0

 

 

 

72

102.9

86.7

70.3

 

53.3

MC60D

1825

 

67

82.4

68.0

53.7

 

39.4

 

62

64.2

50.3

39.6

 

31.8

 

 

 

 

 

 

 

57

55.1

47.5

38.1

 

30.3

 

 

 

72

106.0

89.3

72.4

 

54.9

MC61D

2000

 

67

84.8

70.0

55.3

 

40.5

 

62

66.1

51.8

40.8

 

32.8

 

 

 

 

 

 

 

57

56.8

48.9

39.3

 

31.3

 

 

 

72

106.0

89.3

72.4

 

54.9

MC62C

1800

 

67

84.8

70.0

55.3

 

40.5

 

62

66.1

51.8

40.8

 

32.8

 

 

 

 

 

 

 

57

56.8

48.9

39.3

 

31.2

 

 

 

72

107.0

90.2

73.1

 

55.5

MC62D

2000

 

67

85.7

70.7

55.8

 

40.9

 

62

66.7

52.3

41.2

 

33.1

 

 

 

 

 

 

 

57

57.4

49.4

39.7

 

31.6

*See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.

Notes:

MC coils available with a factory installed horizontal drain pan option (H).

Unitary Products Group

3

Page 3
Image 3
York MH specifications Unitary Products Group, Cooling Capacity - Coil Only, Rated CFM, Wet Bulb