COOLING CAPACITY - Coil Only*
| RATED | ENTERING |
| MBH @ Evaporator Temperature and Corresponding Pressure °F/ PSIG | ||||
MODEL | AIR °F |
|
|
|
|
|
| |
| CFM | (Wet Bulb) |
| 35 / 61.5 |
| 40 / 68.5 | 45 / 76.0 | 50 / 84.0 |
|
|
| HORIZONTAL DUCT TYPE |
|
|
| ||
|
| 72 |
| 35.3 |
| 32.4 | 28.7 | 24.9 |
HD24S**H1 | 815 | 67 |
| 32.6 |
| 29.4 | 26.0 | 22.5 |
62 |
| 26.7 |
| 23.7 | 20.5 | 17.2 | ||
|
|
|
| |||||
|
| 57 |
| 21.7 |
| 18.8 | 15.7 | 12.3 |
|
| 72 |
| 57.9 |
| 52.7 | 47.1 | 41.5 |
HD36S**H1 | 1192 | 67 |
| 46.4 |
| 41.1 | 35.9 | 30.4 |
62 |
| 36.2 |
| 30.4 | 26.5 | 24.7 | ||
|
|
|
| |||||
|
| 57 |
| 31.1 |
| 28.7 | 26.5 | 24.7 |
|
| 72 |
| 83.4 |
| 71.7 | 59.7 | 47.1 |
HD48S**H1 | 1610 | 67 |
| 66.8 |
| 56.1 | 45.6 | 34.9 |
62 |
| 52.1 |
| 41.5 | 33.7 | 28.3 | ||
|
|
|
| |||||
|
| 57 |
| 44.7 |
| 39.2 | 33.7 | 28.3 |
|
| 72 |
| 133.0 |
| 112.4 | 90.9 | 69.2 |
HD60S**H1 | 2100 | 67 |
| 106.5 |
| 87.9 | 69.4 | 50.0 |
62 |
| 83.0 |
| 65.0 | 51.3 | 41.1 | ||
|
|
|
| |||||
|
| 57 |
| 71.2 |
| 61.4 | 51.3 | 41.1 |
* See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.
COOLING CAPACITY - COIL ONLY*
Model | Rated | Entering Air °F |
| MBH @ EVAPORATOR TEMPERATURE AND |
| |||
|
| CORRESPONDING PRESSURE °F / PSIG |
| |||||
| CFM | (Wet Bulb) |
|
|
|
|
|
|
| 35/61.5 |
| 40/68.5 | 45/76.0 |
| 50/84.0 | ||
|
|
|
|
| ||||
|
| 72 | 26.4 |
| 24.0 | 21.5 |
| 18.6 |
HC18A | 600 | 67 | 24.3 |
| 22.0 | 19.4 |
| 16.8 |
62 | 20.0 |
| 17.7 | 15.3 |
| 12.9 | ||
|
|
|
| |||||
|
| 57 | 16.1 |
| 14.0 | 11.8 |
| 9.2 |
|
| 72 | 42.7 |
| 38.9 | 34.7 |
| 30.6 |
HC30A | 1000 | 67 | 34.3 |
| 30.3 | 26.5 |
| 22.5 |
62 | 26.7 |
| 22.5 | 24.5 |
| 19.8 | ||
|
|
|
| |||||
|
| 57 | 22.9 |
| 21.2 | 19.6 |
| 18.3 |
|
| 72 | 73.4 |
| 63.1 | 52.5 |
| 41.5 |
HC36B | 1200 | 67 | 58.8 |
| 49.3 | 40.2 |
| 30.7 |
62 | 45.8 |
| 36.4 | 29.7 |
| 24.8 | ||
|
|
|
| |||||
|
| 57 | 39.3 |
| 34.4 | 28.1 |
| 23.2 |
|
| 72 | 84.9 |
| 73.0 | 60.1 |
| 48.1 |
HC42C | 1400 | 67 | 68.0 |
| 58.9 | 46.5 |
| 35.6 |
62 | 53.1 |
| 42.2 | 34.4 |
| 28.8 | ||
|
|
|
| |||||
|
| 57 | 45.5 |
| 40.0 | 32.0 |
| 26.7 |
|
| 72 | 112.8 |
| 95.0 | 77.0 |
| 58.4 |
HC60D | 1800 | 67 | 90.3 |
| 74.5 | 58.8 |
| 43.1 |
62 | 70.3 |
| 55.1 | 43.4 |
| 34.9 | ||
|
|
|
| |||||
|
| 57 | 60.4 |
| 52.1 | 40.4 |
| 31.9 |
* See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.
APPLICATION FACTOR-RATED CFM VS. ACTUAL CFM
% OF RATED AIR FLOW | 80% | 90% | RATED CFM | 110% | 120% |
|
|
|
|
|
|
CAPACITY FACTOR | 0.96 | 0.98 | 1.00 | 1.02 | 1.03 |
|
|
|
|
|
|
NOTE:Do not exceed minimum/maximum CFM limits shown under Air Flow Data.
APPLICATION LIMITATIONS
These units must be installed in accordance with all national and local safety codes.
Air flow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units.
| Entering Air Temperature Limits |
| |
Wet Bulb Temp. ºF | Dry Bulb Temp. ºF | ||
Min. | Max. | Min. | Max. |
57 | 72 | 65 | 95 |
4 | Unitary Products Group |