628767-YTG-C-0910

YD360/ND360 (Continued)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

72

420.2

31.0

331.0

281.7

232.4

183.1

-

-

383.5

34.4

326.1

276.3

226.5

176.7

-

-

15000

 

67

389.7

30.6

389.7

343.5

294.2

244.9

195.6

-

355.8

34.0

355.8

332.7

288.7

239.0

189.2

-

 

62

334.9

30.1

334.9

334.9

327.6

278.3

229.0

179.7

312.5

33.5

312.5

312.5

308.9

259.1

209.3

159.5

 

 

 

 

57

356.6

29.9

356.6

356.6

356.6

307.3

257.9

208.6

327.0

33.5

327.0

327.0

327.0

277.2

227.4

177.6

 

 

 

 

 

 

115°F

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

77

368.1

37.4

189.9

156.2

122.6

-

-

-

347.5

40.7

180.6

148.0

115.4

-

-

-

 

 

72

343.5

37.0

238.5

204.8

171.2

137.5

-

-

324.5

40.2

228.6

196.0

163.4

130.8

-

-

9000

 

67

318.9

36.5

287.0

253.4

219.7

186.1

152.4

-

301.5

39.7

276.7

244.1

211.5

178.9

146.3

-

 

 

62

287.4

36.1

287.4

287.4

262.0

228.3

194.7

161.0

279.1

39.5

279.1

279.1

261.4

228.8

196.2

163.6

 

 

57

294.6

36.1

294.6

294.6

275.4

241.8

208.1

174.5

280.1

39.5

280.1

280.1

264.5

231.9

199.3

166.7

 

 

77

379.6

37.5

223.1

173.6

131.0

-

-

-

358.7

40.7

222.3

167.8

123.6

-

-

-

 

 

72

354.3

37.1

268.0

225.4

182.9

140.3

-

-

335.0

40.3

263.3

219.2

175.1

131.0

-

-

10500

 

67

328.9

36.6

313.0

277.3

234.8

192.2

149.6

-

311.2

39.8

304.4

270.6

226.5

182.4

138.3

-

 

 

62

296.4

36.3

296.4

296.4

279.9

237.3

194.7

152.2

288.1

39.5

288.1

288.1

280.0

236.6

191.7

147.6

 

 

57

303.9

36.2

303.9

303.9

294.3

251.7

209.1

166.5

289.1

39.6

289.1

289.1

283.4

240.6

195.1

151.0

 

 

77

391.2

37.6

256.2

190.9

139.4

-

-

-

369.9

40.8

264.0

187.5

131.9

-

-

-

 

 

72

365.1

37.2

297.6

246.1

194.6

143.1

-

-

345.4

40.3

298.0

242.4

186.7

131.1

-

-

12000

 

67

338.9

36.7

338.9

301.3

249.8

198.3

146.8

-

320.9

39.9

320.9

297.2

241.6

185.9

130.3

-

 

 

62

305.5

36.4

305.5

305.5

297.8

246.3

194.8

143.3

297.1

39.6

297.1

297.1

297.1

244.4

187.2

131.6

 

 

57

313.1

36.4

313.1

313.1

313.1

261.6

210.1

158.6

298.1

39.7

298.1

298.1

298.1

249.3

190.9

135.3

 

 

72

355.9

37.5

309.4

258.5

207.6

156.7

-

-

327.7

40.8

307.1

253.9

200.8

147.6

-

-

13500

 

67

330.4

37.0

330.4

311.6

266.5

215.7

164.8

-

304.5

40.3

304.5

304.2

259.7

206.5

153.3

-

 

62

297.8

36.7

297.8

297.8

294.0

243.1

192.2

141.4

282.4

40.0

282.4

282.4

282.4

232.5

178.6

125.4

 

 

 

 

57

305.2

36.7

305.2

305.2

305.2

254.4

203.5

152.6

282.9

40.1

282.9

282.9

282.9

233.2

178.6

125.5

 

 

72

346.7

37.8

321.1

270.9

220.7

170.4

-

-

310.0

41.2

310.0

265.5

214.8

164.1

-

-

15000

 

67

321.9

37.3

321.9

321.9

283.3

233.0

182.8

-

288.0

40.7

288.0

288.0

277.8

227.1

176.4

-

 

62

290.1

37.0

290.1

290.1

290.1

239.9

189.6

139.4

267.7

40.4

267.7

267.7

267.7

220.7

170.0

119.3

 

 

 

 

57

297.4

37.0

297.4

297.4

297.4

247.1

196.9

146.7

267.8

40.5

267.8

267.8

267.8

217.1

166.4

115.7

1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

2These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.