York ND480, ND600 manual ND360 1NF0454, Steam Pressure Psig Capacity Correction Factor

Models: ND480 ND360 ND600

1 38
Download 38 pages 57.8 Kb
Page 16
Image 16

628767-YTG-C-0910

Air Handling Unit and Steam Coil Accessory Heating Capacity

ND360 / 1NF0454

UNIT

STEAM COIL

 

 

CAPACITY (MBH) @ 2 PSIG1

 

CFM

DRY BULB TEMPERATURE OF AIR ENTERING COIL (°F)

MODEL

MODEL

 

 

 

 

 

 

 

 

 

10

 

30

50

70

 

 

 

 

 

 

 

 

 

 

8,000

535

 

483

432

380

 

 

 

 

 

 

 

 

ND360

1NF0454

10,000

592

 

535

478

422

 

 

 

 

 

 

12,000

642

 

580

518

456

 

 

 

 

 

 

 

 

 

 

 

 

 

14,000

687

 

621

555

489

 

 

 

 

 

 

 

 

1These capacities do not include any blower motor heat.

Steam Coil Capacity Correction Factors For High Steam Pressure

STEAM PRESSURE (PSIG)

5

10

15

20

25

 

 

 

 

 

 

CAPACITY CORRECTION FACTOR

1.05

1.12

1.19

1.25

1.30

 

 

 

 

 

 

NOTE: Steam Rate = (lbs/Hr.) = 1.025 x MBH