628767-YTG-C-0910

YD480/ND480 (Continued) (Continued)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

 

 

 

 

115°F

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

77

443.0

46.3

267.5

224.4

181.3

-

-

-

423.8

50.8

278.9

236.2

193.6

-

-

-

 

 

72

430.0

46.0

320.6

277.6

234.5

191.5

-

-

413.6

50.3

325.5

282.8

240.1

197.4

-

-

12000

 

67

416.9

45.6

373.8

330.7

287.7

244.6

201.6

-

403.4

49.8

372.0

329.3

286.6

243.9

201.2

-

 

 

62

403.3

45.7

403.3

366.2

323.1

280.1

237.0

193.9

401.0

50.6

401.0

369.3

326.6

283.9

241.2

198.5

 

 

57

370.8

45.5

370.8

370.8

338.3

295.2

252.2

209.1

359.3

50.0

359.3

359.3

331.0

288.3

245.6

202.9

 

 

77

462.5

46.3

310.5

250.3

195.8

-

-

-

437.9

50.5

328.0

262.8

206.4

-

-

-

 

 

72

448.9

45.9

362.1

307.7

253.2

198.7

-

-

427.4

50.0

368.4

312.0

255.5

199.1

-

-

14000

 

67

435.3

45.6

413.8

365.1

310.6

256.1

201.6

-

417.0

49.6

408.9

361.1

304.7

248.2

191.8

-

 

 

62

421.1

45.7

421.1

402.5

348.8

294.4

239.9

185.4

414.8

50.3

414.8

402.6

347.4

291.5

234.5

178.1

 

 

57

387.1

45.5

387.1

387.1

365.2

310.8

256.3

201.8

371.4

49.8

371.4

371.4

351.5

296.3

238.6

182.2

 

 

77

482.1

46.3

353.6

276.1

210.2

-

-

-

452.0

50.2

377.0

289.4

219.2

-

-

-

 

 

72

467.9

45.9

403.6

337.7

271.9

206.0

-

-

441.3

49.8

411.4

341.2

271.0

200.8

-

-

16000

 

67

453.7

45.6

453.7

399.4

333.5

267.6

201.7

-

430.6

49.3

430.6

392.9

322.7

252.5

182.3

-

 

 

62

438.8

45.7

438.8

438.8

374.6

308.7

242.8

176.9

428.6

50.1

428.6

428.6

368.2

299.2

227.8

157.7

 

 

57

403.5

45.5

403.5

403.5

392.2

326.3

260.4

194.5

383.5

49.5

383.5

383.5

372.1

304.4

231.7

161.5

 

 

72

468.4

46.1

414.2

347.3

280.5

213.7

-

-

439.8

50.1

412.4

342.2

272.0

201.8

-

-

18000

 

67

454.2

45.7

454.2

410.9

344.1

277.3

210.4

-

429.2

49.6

429.2

393.3

323.1

252.9

182.7

-

 

62

439.3

45.9

439.3

439.3

386.5

319.6

252.8

186.0

427.4

50.4

427.4

427.4

369.2

299.5

228.8

158.5

 

 

 

 

57

403.9

45.6

403.9

403.9

398.3

331.4

264.6

197.8

382.3

49.8

382.3

382.3

376.6

307.6

236.2

165.9

 

 

72

469.0

46.2

424.7

356.9

289.1

221.4

-

-

438.4

50.4

413.5

343.2

273.0

202.8

-

-

20000

 

67

454.8

45.9

454.8

422.5

354.7

286.9

219.1

-

427.8

49.9

427.8

393.8

323.5

253.3

183.1

-

 

62

439.8

46.0

439.8

439.8

398.4

330.6

262.8

195.0

426.1

50.6

426.1

426.1

370.1

299.9

229.7

159.4

 

 

 

 

57

404.4

45.8

404.4

404.4

404.4

336.6

268.8

201.0

381.1

50.1

381.1

381.1

381.1

310.8

240.6

170.3

1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

2These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

12

Johnson Controls Unitary Products

Page 12
Image 12
York ND360, ND600 manual YD480/ND480