Guide Specifications
MILLENNIUM™
Split System
General
Units shall be manufactured by Johnson Controls, Unitary Products Group in an ISO 9001 certified facility. These
Description
The NC/ND indoor units are completely piped and wired at the factory and are shipped ready for immediate installation. Only the interconnecting liquid and suction lines, control wiring, and the main power wiring are required to complete the installation. Every coil is dehydrated, evacuated, leak tested and pressure tested at 450 psig before being pressurized with a holding charge of nitrogen for shipment and/or storage.
To eliminate the costly cabinet deterioration problems usually associated with outdoor equipment, all sheet metal parts are constructed of commercial grade (G90) galvanized steel.
After fabrication, each part is thoroughly cleaned to remove any grease or dirt from its surfaces. The parts that will be exposed to the weather are then coated with a powder paint to assure a quality finish for many years. This coating system has passed the
Unit Cabinet
Cabinet shall be constructed of 18 gauge, zinc coated steel, finished with a powder paint process capable of withstanding a minimum of 1000 salt spray hours according to ASTM B117. Cabinet screws shall comply with the ASTM B117 salt spray test for a minimum of 1000 hours. Panels shall be removable for easy access to all internal components during maintenance and service. A filter rack shall be included to accommodate 1" or 2" filters. Cabinet shall feature a separate access panel for the controls so that unit airflow need not be disturbed during servicing. The NC300, ND360- 480 units are shipped in the vertical position ready for field
installation. The blower module can be repositioned in the field for maximum flexibility. The ND600 product ships with a separate M1CZ600A evaporator coil and can be assembled in the vertical or horizontal position in the field.
Each unit shall have:
a. A steel angle frame to provide the rigid support required for shipping, rigging and years of dependable operation.
b. Exterior panels of 18 gauge steel, finished with baked enamel to provide a
c. Removable panels to provide easy access to the internal components for maintenance and service.
d. A filter rack with 1" or 2" filters.
Indoor (Evaporator) Fan Assembly
Fan shall be a belt drive assembly and include an adjustable pitch motor pulley. Job site selected brake horsepower shall not exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service factor. Fan wheel shall be
Refrigerant Components
Coils:
a. Evaporator coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed.
b. Evaporator coil shall be of the direct expansion, draw through design.
Refrigerant Circuit and Refrigerant Safety Components:
a. Include
b. Include factory installed auxiliary side connectors for the addition of field installed hot gas bypass.
c. Shall include filter/strainer to eliminate any foreign matter.
Controls
Unit controls shall include 208/230/460 or 575 volt transformer, blower motor contactor and relay, as well as a low voltage terminal block. Unit wiring shall be
Johnson Controls Unitary Products | 5 |