246782-YTG-B-0407

246782-YTG-B-0407

 

 

 

 

22-3/4

 

 

 

 

7/8

 

 

A

 

7/8

T-STAT WIRING 7/8” K.O.

 

 

 

HORIZONTAL CONDENSATE

 

 

T-STAT WIRING 7/8” K.O.

 

 

 

 

13-7/8

DRAIN OPENING 1-3/4”

 

 

 

 

 

 

 

HORIZONTAL CONDENSATE

 

 

 

 

DRAIN OPENING 1-3/4”

HORIZONTAL CONDENSATE

 

 

40

HORIZONTAL

DRAIN OPENING 2”

 

 

 

 

 

 

CONDENSATE

 

 

 

 

JUNCTION BOX

29

 

29

DRAIN OPENING 1-3/4”

HOLE 7/8”

 

 

 

 

 

22-3/4

 

22-3/4

JUNCTION BOX

GAS PIPE ENTRY 1-1/2”

 

 

HOLE 7/8”

 

 

 

21-5/8

 

 

 

 

 

21-1/4

GAS PIPE

CONDENSATE DRAIN

18-1/2

 

18-1/2

 

ENTRY 1-1/2”

HOLE 7/8”

 

 

 

 

SIDE PIPING HOLE 3-3/8”

11-3/4

 

9-1/8

 

7-1/2

 

 

 

 

8-1/2

CONDENSATE DRAIN

 

 

 

HOLE 7/8”

 

2-1/4

 

 

 

 

 

 

22-1/4

 

 

FRONT

 

25-3/8

 

 

 

 

26-1/2

 

 

 

 

27-1/8

 

 

 

 

30-1/8

23-11/16

 

23-5/8

RIGHT SIDE

 

 

 

 

 

1-1/4

5/8

LEFT SIDE

19-1/4

 

 

 

 

 

1-1/4

 

D

5/8

 

 

 

 

 

 

 

E

 

 

 

 

B

 

 

C

 

 

 

 

 

 

20

 

 

 

 

2-1/4

 

 

 

 

23-1/4

 

 

BOTTOM IMAGE

 

TOP IMAGE

 

 

SUPPLY END

 

RETURN END

 

CABINET AND DUCT DIMENSIONS

Models

CFM

CABINET

 

CABINET DIMENSION

 

SIZE

A (IN.)

B (IN.)

C (IN.)

D (IN.)

E (IN.)

 

 

PT9B12N060DH11

1200

B

17-1/2

16-1/4

15

1-3/4

2-3/8

PT9B12N080DH11

1200

B

17-1/2

16-1/4

15

1-3/4

2-3/8

PT9C16N080DH11

1600

C

21

19-3/4

18-1/2

2-1/8

2-3/4

PT9C20N100DH11

2000

C

21

19-3/4

18-1/2

2-1/8

2-3/4

PT9D20N120DH11

2000

D

24-1/2

23-1/4

22

2-1/2

3

ELECTRICAL AND PERFORMANCE DATA

 

Input

Output

Nominal

Cabinet

Total Unit

AFUE

Air Temp.

Models

(High/Low)

(High/Low)

Airflow

Width

Rise

 

 

 

 

 

 

 

 

 

 

 

 

MBH

MBH

 

CFM

In.

Amps

%

°F

PT9B12N060DH11

60 / 39

56 / 36

 

1200

17-1/2

9

92

35 - 65

PT9B12N080DH11

80 / 52

75 / 49

 

1200

17-1/2

9

92

35 - 65

PT9C16N080DH11

80 / 52

75 / 49

 

1600

21

12

92

35 - 65

PT9C20N100DH11

100 / 65

93 / 61

 

2000

21

14

92

35 - 65

PT9D20N120DH11

120 / 78

112 / 74

 

2000

24-1/2

14

92

35 - 65

 

 

 

 

 

 

 

 

 

 

 

Input

Max. Outlet

Blower

Blower

Max.

Min. Wire Size

Operating

Models

(High/Low)

Air Temp.

Size

Over-current

(awg) @ 75 ft.

Weight

 

 

 

 

 

 

 

 

 

 

Protect

One Way

 

 

MBH

°F

HP

 

Amps

In.

Lbs.

PT9B12N060DH11

60 / 39

165

1/2

 

7.0

11 x 8

20

14

136

PT9B12N080DH11

80 / 52

165

1/2

 

7.0

11 x 8

20

14

143

PT9C16N080DH11

80 / 52

165

3/4

 

10.2

11 x 10

20

14

159

PT9C20N100DH11

100 / 65

165

1

 

12.7

11 x 11

20

12

164

PT9D20N120DH11

120 / 78

165

1

 

12.7

11 x 11

20

12

182

Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.

Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes. The furnace shall be installed so that the electrical components are protected from water.

*Wire size and overcurrent protection must comply with the National Electric Code.

NOTES:

1.For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea level.

2.Wire size based on copper conductors, 60°C, 3% voltage drop.

3.Continuous return air temperature must not be below 55°F.

4.All filters must be high velocity cleanable type.

2

Unitary Products Group

Page 2
Image 2
York PT9 warranty YTG-B-0407, Cabinet And Duct Dimensions, Electrical And Performance Data