Table 9: Additional Static Resistance (Continued)
Size | Model | CFM | Wet Indoor Coil | Economizer1 | Filter/Frame Kit | Electric Heat | |
(Tons) |
|
|
|
|
|
| |
|
| 1100 | 0.03 | 0.01 | 0.03 | 0.05 | |
042 |
| 1200 | 0.04 | 0.02 | 0.03 | 0.06 | |
DEX | 1300 | 0.04 | 0.03 | 0.03 | 0.07 | ||
(3.5) | 1400 | 0.04 | 0.04 | 0.03 | 0.08 | ||
| |||||||
|
| 1500 | 0.05 | 0.05 | 0.04 | 0.09 | |
|
| 1600 | 0.06 | 0.06 | 0.05 | 0.10 | |
|
| 1100 | 0.03 | 0.01 | 0.03 | 0.05 | |
|
| 1200 | 0.04 | 0.02 | 0.03 | 0.06 | |
|
| 1300 | 0.04 | 0.03 | 0.03 | 0.07 | |
048 |
| 1400 | 0.04 | 0.04 | 0.03 | 0.08 | |
DEX | 1500 | 0.04 | 0.05 | 0.04 | 0.09 | ||
(4.0) | 1600 | 0.04 | 0.06 | 0.05 | 0.10 | ||
| |||||||
|
| 1700 | 0.05 | 0.07 | 0.05 | 0.11 | |
|
| 1800 | 0.05 | 0.07 | 0.06 | 0.11 | |
|
| 1900 | 0.06 | 0.08 | 0.06 | 0.11 | |
|
| 2000 | 0.07 | 0.08 | 0.07 | 0.12 | |
|
| 1100 | 0.03 | 0.01 | 0.03 | 0.05 | |
|
| 1200 | 0.04 | 0.02 | 0.03 | 0.06 | |
|
| 1300 | 0.04 | 0.03 | 0.03 | 0.07 | |
060 |
| 1400 | 0.04 | 0.04 | 0.03 | 0.08 | |
DEY | 1500 | 0.04 | 0.05 | 0.04 | 0.09 | ||
(5.0) | 1600 | 0.04 | 0.06 | 0.05 | 0.10 | ||
| |||||||
|
| 1700 | 0.05 | 0.07 | 0.05 | 0.11 | |
|
| 1800 | 0.05 | 0.07 | 0.06 | 0.11 | |
|
| 1900 | 0.06 | 0.08 | 0.06 | 0.11 | |
|
| 2000 | 0.07 | 0.08 | 0.07 | 0.12 |
1.The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Table 10: Electric Heat Minimum Supply Air
Size |
|
|
|
| Minimum Supply Air (CFM) |
|
| |||
Model | Voltage |
|
|
| Heater kW |
|
| |||
(Tons) |
|
|
|
|
| |||||
|
|
| 5.0 | 7.5 |
| 10.0 | 15.0 |
| 20.0 | 25.0 |
024 | DEX | 630 | 630 |
| 800 | - |
| - | - | |
(2.0) |
|
| ||||||||
|
|
|
|
|
|
|
|
|
| |
030 | DEX | 630 | 630 |
| 800 | 800 |
| - | - | |
(2.5) |
|
| ||||||||
|
|
|
|
|
|
|
|
|
| |
036 |
| 1070 | 1070 |
| 1070 | 1070 |
| - | - | |
DEX | 1070 | 1070 |
| 1070 | 1070 |
| - | - | ||
(3.0) |
|
| ||||||||
| 1070 | 1070 |
| 1070 | 1070 |
| - | - | ||
|
|
|
| |||||||
042 |
| 1225 | 1225 |
| 1225 | 1225 |
| - | - | |
DEX | 1225 | 1225 |
| 1225 | 1225 |
| - | - | ||
(3.5) |
|
| ||||||||
| 1225 | 1225 |
| 1225 | 1225 |
| - | - | ||
|
|
|
| |||||||
048 |
| - | - |
| 1200 | 1430 |
| 1430 | 1430 | |
DEX | - | - |
| 1200 | 1430 |
| 1430 | 1430 | ||
(4.0) |
|
| ||||||||
| - | - |
| 1200 | 1430 |
| 1430 | 1430 | ||
|
|
|
| |||||||
060 |
| - | - |
| 1615 | 1615 |
| 1955 | 1955 | |
DEY | - | - |
| 1615 | 1615 |
| 1955 | 1955 | ||
(5.0) |
|
| ||||||||
| - | - |
| 1615 | 1615 |
| 1955 | 1955 | ||
|
|
|
|
Table 11: Indoor Blower Specifications
Size | Model |
|
| Motor |
|
| |
(Tons) | HP | RPM | Eff. | SF | Frame | ||
| |||||||
024 | DEX | 1/2 | Variable | 0.8 | 1.0 | 48 | |
(2.0) | |||||||
|
|
|
|
|
| ||
030 | DEX | 1/2 | Variable | 0.8 | 1.0 | 48 | |
(2.5) | |||||||
|
|
|
|
|
| ||
036 | DEX | 1/2 | Variable | 0.8 | 1.0 | 48 | |
(3.0) | |||||||
|
|
|
|
|
| ||
042 | DEX | 3/4 | Variable | 0.8 | 1.0 | 48 | |
(3.5) | |||||||
|
|
|
|
|
| ||
048 | DEX | 3/4 | Variable | 0.8 | 1.0 | 48 | |
(4.0) | |||||||
|
|
|
|
|
| ||
060 | DEY | 1 | Variable | 0.8 | 1.0 | 48 | |
(5.0) | |||||||
|
|
|
|
|
|
Table 12: Electric Heat Multipliers |
| ||
|
|
| |
| Voltage | kW Capacity Multipliers1 | |
Nominal |
| Applied | |
|
| ||
240 |
| 208 | 0.75 |
| 230 | 0.92 | |
|
| ||
480 |
| 460 | 0.92 |
1.Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for heaters applied at lower voltages.
Unitary Products Group | 15 |