York R-410A Additional Static Resistance Continued, Electric Heat Minimum Supply Air, Tons

Models: R-410A

1 24
Download 24 pages 22.74 Kb
Page 15
Image 15
Table 9: Additional Static Resistance (Continued)

288429-YIM-A-0307

Table 9: Additional Static Resistance (Continued)

Size

Model

CFM

Wet Indoor Coil

Economizer1

Filter/Frame Kit

Electric Heat

(Tons)

 

 

 

 

 

 

 

 

1100

0.03

0.01

0.03

0.05

042

 

1200

0.04

0.02

0.03

0.06

DEX

1300

0.04

0.03

0.03

0.07

(3.5)

1400

0.04

0.04

0.03

0.08

 

 

 

1500

0.05

0.05

0.04

0.09

 

 

1600

0.06

0.06

0.05

0.10

 

 

1100

0.03

0.01

0.03

0.05

 

 

1200

0.04

0.02

0.03

0.06

 

 

1300

0.04

0.03

0.03

0.07

048

 

1400

0.04

0.04

0.03

0.08

DEX

1500

0.04

0.05

0.04

0.09

(4.0)

1600

0.04

0.06

0.05

0.10

 

 

 

1700

0.05

0.07

0.05

0.11

 

 

1800

0.05

0.07

0.06

0.11

 

 

1900

0.06

0.08

0.06

0.11

 

 

2000

0.07

0.08

0.07

0.12

 

 

1100

0.03

0.01

0.03

0.05

 

 

1200

0.04

0.02

0.03

0.06

 

 

1300

0.04

0.03

0.03

0.07

060

 

1400

0.04

0.04

0.03

0.08

DEY

1500

0.04

0.05

0.04

0.09

(5.0)

1600

0.04

0.06

0.05

0.10

 

 

 

1700

0.05

0.07

0.05

0.11

 

 

1800

0.05

0.07

0.06

0.11

 

 

1900

0.06

0.08

0.06

0.11

 

 

2000

0.07

0.08

0.07

0.12

1.The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

Table 10: Electric Heat Minimum Supply Air

Size

 

 

 

 

Minimum Supply Air (CFM)

 

 

Model

Voltage

 

 

 

Heater kW

 

 

(Tons)

 

 

 

 

 

 

 

 

5.0

7.5

 

10.0

15.0

 

20.0

25.0

024

DEX

208/230-1-60

630

630

 

800

-

 

-

-

(2.0)

 

 

 

 

 

 

 

 

 

 

 

 

030

DEX

208/230-1-60

630

630

 

800

800

 

-

-

(2.5)

 

 

 

 

 

 

 

 

 

 

 

 

036

 

208/230-1-60

1070

1070

 

1070

1070

 

-

-

DEX

208/230-3-60

1070

1070

 

1070

1070

 

-

-

(3.0)

 

 

 

460-3-60

1070

1070

 

1070

1070

 

-

-

 

 

 

 

042

 

208/230-1-60

1225

1225

 

1225

1225

 

-

-

DEX

208/230-3-60

1225

1225

 

1225

1225

 

-

-

(3.5)

 

 

 

460-3-60

1225

1225

 

1225

1225

 

-

-

 

 

 

 

048

 

208/230-1-60

-

-

 

1200

1430

 

1430

1430

DEX

208/230-3-60

-

-

 

1200

1430

 

1430

1430

(4.0)

 

 

 

460-3-60

-

-

 

1200

1430

 

1430

1430

 

 

 

 

060

 

208/230-1-60

-

-

 

1615

1615

 

1955

1955

DEY

208/230-3-60

-

-

 

1615

1615

 

1955

1955

(5.0)

 

 

 

460-3-60

-

-

 

1615

1615

 

1955

1955

 

 

 

 

Table 11: Indoor Blower Specifications

Size

Model

 

 

Motor

 

 

(Tons)

HP

RPM

Eff.

SF

Frame

 

024

DEX

1/2

Variable

0.8

1.0

48

(2.0)

 

 

 

 

 

 

030

DEX

1/2

Variable

0.8

1.0

48

(2.5)

 

 

 

 

 

 

036

DEX

1/2

Variable

0.8

1.0

48

(3.0)

 

 

 

 

 

 

042

DEX

3/4

Variable

0.8

1.0

48

(3.5)

 

 

 

 

 

 

048

DEX

3/4

Variable

0.8

1.0

48

(4.0)

 

 

 

 

 

 

060

DEY

1

Variable

0.8

1.0

48

(5.0)

 

 

 

 

 

 

Table 12: Electric Heat Multipliers

 

 

 

 

 

Voltage

kW Capacity Multipliers1

Nominal

 

Applied

 

 

240

 

208

0.75

 

230

0.92

 

 

480

 

460

0.92

1.Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for heaters applied at lower voltages.

Unitary Products Group

15

Page 15
Image 15
York R-410A Additional Static Resistance Continued, Electric Heat Minimum Supply Air, Indoor Blower Specifications, Tons