COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. | TCHD30S41S3 |
|
|
|
|
|
|
|
|
|
|
|
| ||||
INDOOR COIL MODEL NO. |
| FC/MC/PC35 |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
CONDENSING | IDCFM |
|
| 800 |
|
|
|
| 1000 |
|
|
|
| 1200 |
|
| |
ENTERING AIR |
| ID DB (°F) | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 |
TEMPERATURE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ID WB (°F) | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | |
|
| T.C. | 27.3 | 28.7 | 28.9 | 30.5 | 31.8 | 28.8 | 29.9 | 29.8 | 31.6 | 33.4 | 30.3 | 31.0 | 30.7 | 32.8 | 35.0 |
65 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| S.C. | 26.6 | 24.5 | 20.7 | 20.5 | 15.9 | 28.2 | 27.4 | 23.2 | 22.6 | 17.2 | 29.7 | 30.4 | 25.7 | 24.7 | 18.5 | |
|
| KW | 1.61 | 1.64 | 1.61 | 1.64 | 1.63 | 1.63 | 1.63 | 1.61 | 1.64 | 1.64 | 1.65 | 1.62 | 1.61 | 1.64 | 1.65 |
|
| T.C. | 26.2 | 27.0 | 27.1 | 29.4 | 31.2 | 27.8 | 28.3 | 28.3 | 30.4 | 32.2 | 29.5 | 29.5 | 29.5 | 31.5 | 33.2 |
75 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| S.C. | 25.6 | 23.9 | 19.9 | 19.8 | 15.4 | 27.2 | 26.4 | 22.3 | 22.0 | 16.8 | 28.8 | 28.9 | 24.6 | 24.1 | 18.1 | |
|
| KW | 1.88 | 1.88 | 1.89 | 1.88 | 1.86 | 1.87 | 1.87 | 1.88 | 1.87 | 1.86 | 1.87 | 1.87 | 1.88 | 1.87 | 1.86 |
|
| T.C. | 25.1 | 25.3 | 25.2 | 28.3 | 30.6 | 26.8 | 26.7 | 26.7 | 29.2 | 31.0 | 28.6 | 28.0 | 28.3 | 30.1 | 31.4 |
85 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| S.C. | 24.5 | 23.2 | 19.1 | 19.2 | 15.0 | 26.2 | 25.3 | 21.3 | 21.3 | 16.3 | 28.0 | 27.4 | 23.6 | 23.5 | 17.7 | |
|
| KW | 2.15 | 2.12 | 2.18 | 2.11 | 2.09 | 2.12 | 2.12 | 2.16 | 2.10 | 2.09 | 2.09 | 2.12 | 2.14 | 2.10 | 2.08 |
|
| T.C. | 23.9 | 23.7 | 23.3 | 27.2 | 30.0 | 25.8 | 25.1 | 25.2 | 28.0 | 29.8 | 27.8 | 26.5 | 27.1 | 28.8 | 29.6 |
95 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| S.C. | 23.5 | 22.6 | 18.2 | 18.5 | 14.5 | 25.3 | 24.3 | 20.4 | 20.7 | 15.9 | 27.1 | 25.9 | 22.5 | 22.9 | 17.3 | |
|
| KW | 2.41 | 2.36 | 2.46 | 2.34 | 2.32 | 2.37 | 2.36 | 2.43 | 2.33 | 2.31 | 2.32 | 2.36 | 2.41 | 2.32 | 2.30 |
|
| T.C. | 22.4 | 22.6 | 22.2 | 25.0 | 27.8 | 24.3 | 24.1 | 23.8 | 26.1 | 27.8 | 26.2 | 25.6 | 25.3 | 27.3 | 27.9 |
105 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| S.C. | 21.9 | 21.5 | 17.6 | 17.8 | 13.9 | 23.7 | 23.1 | 19.7 | 20.0 | 15.3 | 25.5 | 24.8 | 21.7 | 22.2 | 16.7 | |
|
| KW | 2.93 | 2.96 | 3.05 | 2.84 | 2.70 | 2.85 | 2.88 | 3.01 | 2.80 | 2.69 | 2.76 | 2.80 | 2.97 | 2.76 | 2.67 |
|
| T.C. | 20.9 | 21.5 | 21.2 | 22.9 | 25.6 | 22.8 | 23.1 | 22.4 | 24.4 | 26.0 | 24.7 | 24.7 | 23.5 | 25.8 | 26.3 |
115 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| S.C. | 20.5 | 20.4 | 17.0 | 17.1 | 13.4 | 22.2 | 22.0 | 19.0 | 19.3 | 14.7 | 24.0 | 23.6 | 20.9 | 21.5 | 16.1 | |
|
| KW | 3.44 | 3.54 | 3.61 | 3.32 | 3.07 | 3.31 | 3.38 | 3.56 | 3.25 | 3.05 | 3.19 | 3.22 | 3.51 | 3.18 | 3.03 |
|
| T.C. | 19.5 | 20.4 | 20.1 | 20.7 | 23.4 | 21.3 | 22.1 | 20.9 | 22.6 | 24.1 | 23.2 | 23.9 | 21.8 | 24.4 | 24.7 |
125 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| S.C. | 19.0 | 19.3 | 16.4 | 16.4 | 12.8 | 20.7 | 20.9 | 18.3 | 18.6 | 14.2 | 22.4 | 22.5 | 20.1 | 20.8 | 15.5 | |
|
| KW | 3.94 | 4.13 | 4.18 | 3.81 | 3.44 | 3.78 | 3.88 | 4.12 | 3.70 | 3.42 | 3.62 | 3.63 | 4.06 | 3.60 | 3.39 |
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between
Air Handlers | Coils | T.C. | S.C. | KW |
– | FC/MC/PC30 | 0.99 | 0.98 | 1.00 |
– | FC/MC/PC32 | 1.00 | 1.00 | 1.00 |
– | FC/MC/PC36 | 1.00 | 0.99 | 1.00 |
– | FC/MC/PC37 | 1.01 | 1.02 | 1.00 |
– | FC/MC/PC43 | 1.01 | 1.02 | 1.00 |
– | HC30 | 0.99 | 0.98 | 1.00 |
– | HC36 | 1.00 | 1.00 | 1.00 |
– | HC42 | 1.01 | 1.02 | 1.00 |
– | HD36 | 0.99 | 0.96 | 1.00 |
– | UC30 | 0.99 | 0.98 | 0.99 |
– | UC48 | 0.96 | 0.96 | 1.00 |
AHP36 | – | 1.01 | 1.02 | 1.00 |
AHX30 | – | 1.01 | 1.03 | 0.97 |
AHX36 | – | 1.04 | 1.04 | 0.94 |
AHX42 | – | 1.05 | 1.06 | 0.92 |
AHX48 | – | 1.06 | 1.11 | 0.93 |
Air Handlers | Coils | T.C. | S.C. | KW |
AV*36 | – | 1.03 | 1.03 | 0.93 |
F*FP030 | – | 0.99 | 0.96 | 1.00 |
F*FP036 | – | 0.99 | 0.99 | 0.99 |
F*FP040 | – | 0.99 | 0.98 | 0.99 |
F6FP030 | – | 1.01 | 1.01 | 1.01 |
F6FP036 | – | 1.01 | 1.00 | 0.95 |
F6FP042 | – | 1.06 | 1.08 | 0.94 |
F6FP048 | – | 1.00 | 1.02 | 0.96 |
MV12B | FC/MC30B | 1.01 | 1.00 | 0.93 |
MV12B | FC/MC35B | 1.02 | 1.02 | 0.93 |
MV16C | FC/MC35C | 1.02 | 1.02 | 0.93 |
MV12B | FC/MC36B | 1.02 | 1.01 | 0.93 |
MV16C | FC/MC36C | 1.02 | 1.01 | 0.93 |
MV12B | FC/MC43B | 1.04 | 1.04 | 0.93 |
MV16C | FC/MC43C | 1.04 | 1.04 | 0.92 |
MV16C | FC/MC48C | 1.05 | 1.05 | 0.92 |
Continued on next page.