York YK145.00-EG4 manual RS*018 - 640 CFM, Performance Data

Models: YK145.00-EG4

1 28
Download 28 pages 44.88 Kb
Page 11
Image 11
RS*018 — 640 CFM

Water Source Heat Pumps

 

 

 

 

 

 

 

 

 

Technical Guide: YK145.00-EG4 (309)

PERFORMANCE DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

RS*018 — 640 CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EWT (F)

GPM

WPD

 

 

 

COOLING

 

 

 

 

HEATING

 

 

PSI

 

FT

TC

 

SC

 

kW

 

HR

EER

HTG

kW

 

HE

 

LAT (F)

COP

 

 

 

 

 

 

 

 

20

4.8

8.4

 

19.4

 

 

 

 

 

 

 

 

10.4

1.09

 

6.7

 

83

2.8

 

2.4

3.1

 

7.1

26.6

 

18.6

 

0.96

 

29.9

27.7

12.0

1.17

 

8.0

 

85

3.0

30

3.6

4.9

 

11.3

27.3

 

19.1

 

0.90

 

30.4

30.2

12.4

1.21

 

8.3

 

86

3.0

 

4.8

7.3

 

16.9

27.7

 

19.1

 

0.87

 

30.7

32.0

12.7

1.20

 

8.6

 

86

3.1

 

2.4

2.7

 

6.2

24.9

 

17.7

 

1.05

 

28.5

23.8

14.7

1.23

 

10.5

 

89

3.5

40

3.6

4.3

 

9.8

25.6

 

18.0

 

1.00

 

29.0

25.5

15.2

1.27

 

10.9

 

90

3.5

 

4.8

6.4

 

14.7

25.9

 

18.1

 

0.96

 

29.2

27.0

15.7

1.28

 

11.3

 

91

3.6

 

2.4

2.4

 

5.5

24.3

 

17.5

 

1.15

 

28.2

21.1

17.3

1.33

 

12.7

 

93

3.8

50

3.6

3.8

 

8.7

24.5

 

17.5

 

1.14

 

28.4

21.5

18.0

1.35

 

13.4

 

94

3.9

 

4.8

5.6

 

13.0

24.9

 

17.7

 

1.09

 

28.6

22.8

18.8

1.41

 

14.0

 

95

3.9

 

2.4

2.1

 

4.8

21.3

 

15.7

 

1.22

 

25.5

17.4

19.2

1.41

 

14.4

 

96

4.0

60

3.6

3.3

 

7.5

22.0

 

16.1

 

1.21

 

26.1

18.2

20.1

1.44

 

15.2

 

97

4.1

 

4.8

4.9

 

11.3

22.8

 

16.6

 

1.13

 

26.7

20.2

20.8

1.45

 

15.8

 

98

4.2

 

2.4

1.9

 

4.4

20.2

 

15.0

 

1.34

 

24.8

15.1

22.0

1.47

 

17.0

 

100

4.4

70

3.6

3.0

 

6.9

20.5

 

15.1

 

1.27

 

24.8

16.2

23.1

1.50

 

18.0

 

101

4.5

 

4.8

4.5

 

10.4

21.0

 

15.3

 

1.24

 

25.2

17.0

23.9

1.56

 

18.6

 

103

4.5

 

2.4

1.7

 

3.9

18.6

 

14.4

 

1.44

 

23.5

12.9

23.3

1.48

 

18.2

 

102

4.6

80

3.6

2.6

 

6.1

19.3

 

14.8

 

1.39

 

24.0

13.9

24.6

1.50

 

19.5

 

104

4.8

 

4.8

4.0

 

9.1

19.8

 

15.1

 

1.37

 

24.5

14.5

25.4

1.51

 

20.2

 

105

4.9

 

2.4

1.5

 

3.4

17.4

 

13.7

 

1.55

 

22.7

11.2

25.8

1.49

 

20.7

 

105

5.1

90

3.6

2.3

 

5.4

18.1

 

14.2

 

1.52

 

23.3

11.9

27.0

1.52

 

21.8

 

107

5.2

 

4.8

3.5

 

8.1

18.6

 

14.6

 

1.50

 

23.7

12.4

28.1

1.55

 

22.8

 

109

5.3

 

2.4

1.3

 

3.1

16.6

 

13.8

 

1.84

 

22.9

9.7

 

 

 

 

 

 

 

100

3.6

2.1

 

4.8

17.2

 

14.3

 

1.82

 

23.4

10.3

 

 

 

 

 

 

 

 

4.8

3.1

 

7.2

17.7

 

14.6

 

1.79

 

23.8

10.6

 

 

 

 

 

 

 

 

2.4

1.2

 

2.7

15.1

 

13.1

 

1.91

 

21.6

8.4

 

 

 

 

 

 

 

110

3.6

1.9

 

4.3

15.8

 

13.5

 

1.87

 

22.2

8.9

 

 

 

 

 

 

 

 

4.8

2.8

 

6.5

16.1

 

13.5

 

1.84

 

22.4

9.2

 

 

 

 

 

 

 

Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT Tabulated data does not include ARI/ISO corrections for fan and pump power.

All capacities are expressed in MBH.

Insulated water circuit is recommended for operation below 60F EWT. See performance correction tables for conditions beyond what is listed. Extrapolation is not permissible.

Shaded areas indicate conditions where operation is not recommended.

Johnson Controls

11

Page 11
Image 11
York YK145.00-EG4 manual RS*018 - 640 CFM, Performance Data