York YK145.00-EG4 manual Correction Factors, Antifreeze Correction Table, Airflow Correction Table

Models: YK145.00-EG4

1 28
Download 28 pages 44.88 Kb
Page 19
Image 19
CORRECTION FACTORS

Water Source Heat Pumps

 

 

 

Technical Guide: YK145.00-EG4 (309)

CORRECTION FACTORS

 

 

 

 

 

 

ANTIFREEZE CORRECTION TABLE

 

 

 

 

 

 

 

 

 

 

Antifreeze Concentration

 

 

 

 

5%

10%

15%

20%

25%

30%

40%

 

Cooling

0.998

0.995

0.993

0.991

0.989

0.987

0.984

Ethylene Glycol

Heating

0.995

0.990

0.985

0.980

0.974

0.969

0.964

 

PD

1.040

1.055

1.080

1.105

1.135

1.165

1.210

 

Cooling

0.995

0.992

0.987

0.983

0.979

0.975

0.970

Propylene Glycol

Heating

0.989

0.982

0.975

0.967

0.958

0.951

0.943

 

PD

1.035

1.055

1.100

1.145

1.200

1.260

1.320

 

Cooling

0.999

0.995

0.990

0.986

0.982

0.980

0.978

Methanol

Heating

0.989

0.985

0.979

0.971

0.963

0.954

0.946

 

PD

1.050

1.072

1.094

1.116

1.140

1.165

1.196

AIRFLOW CORRECTION TABLE

Airflow %

 

 

Cooling

 

 

Heating

 

TC

SC

 

Power

THR

HC

Power

HE

 

 

70

0.931

0.847

 

0.964

0.946

0.942

1.075

0.940

75

0.941

0.872

 

0.969

0.956

0.953

1.059

0.949

80

0.950

0.896

 

0.979

0.961

0.960

1.039

0.958

85

0.966

0.923

 

0.983

0.971

0.970

1.023

0.969

90

0.977

0.948

 

0.989

0.981

0.979

1.015

0.979

95

0.989

0.974

 

0.995

0.990

0.989

1.007

0.989

100

1.000

1.000

 

1.000

1.000

1.000

1.000

1.000

105

1.008

1.025

 

1.006

1.010

1.009

0.994

1.010

110

1.018

1.048

 

1.013

1.017

1.019

0.992

1.018

115

1.026

1.070

 

1.019

1.026

1.029

0.991

1.028

COOLING PERFORMANCE CORRECTION TABLE

Entering Air

Total Clg

 

Entering Air DB (F) - Sensible Capacity

 

Heat

WB (F)

Capacity

70

75

80.6

85

90

95

Rejection

60

0.845

0.86

1.1

1.305

S

S

S

0.904

65

0.948

0.628

0.865

1.082

1.312

S

S

0.979

66.2

1

0.539

0.777

1

1.22

1.475

S

1

70

1.061

 

0.631

0.855

1.081

1.331

1.543

1.039

75

1.162

 

 

0.618

0.848

1.09

1.296

1.107

S = Sensible cooling is equal to Total Cooling

HEATING PERFORMANCE CORRECTION TABLE

EAT DB (F)

Heating Capacity

Power

Heat Extraction

45

1.101

0.785

1.162

50

1.080

0.832

1.125

55

1.059

0.878

1.079

60

1.039

0.926

1.064

65

1.019

0.960

1.023

68

1.000

1.000

1.000

70

0.990

1.028

0.983

75

0.974

1.064

0.957

80

0.951

1.111

0.918

Johnson Controls

19

Page 19
Image 19
York YK145.00-EG4 manual Correction Factors, Antifreeze Correction Table, Airflow Correction Table