York YK145.00-EG4 manual RS*060 - 2000 CFM, Performance Data

Models: YK145.00-EG4

1 28
Download 28 pages 44.88 Kb
Page 17
Image 17
RS*060 — 2000 CFM

Water Source Heat Pumps

 

 

 

 

 

 

 

 

 

Technical Guide: YK145.00-EG4 (309)

PERFORMANCE DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

RS*060 — 2000 CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EWT (F)

GPM

WPD

 

 

 

COOLING

 

 

 

 

HEATING

 

 

PSI

 

FT

TC

 

SC

 

kW

 

HR

EER

HTG

kW

 

HE

 

LAT (F)

COP

 

 

 

 

 

 

 

 

20

15.0

17.8

 

41.1

 

 

 

 

 

 

 

 

38.2

3.32

 

26.8

 

86

2.9

 

7.5

5.9

 

13.5

72.6

 

50.8

 

2.77

 

82.1

26.2

43.2

3.90

 

29.9

 

88

3.2

30

11.2

7.5

 

17.3

73.8

 

51.4

 

2.60

 

82.7

28.4

45.2

3.96

 

31.7

 

89

3.3

 

15.0

15.6

 

36.0

74.5

 

51.6

 

2.48

 

83.0

30.0

46.0

4.00

 

32.3

 

89

3.4

 

7.5

5.1

 

11.8

68.9

 

49.3

 

3.25

 

80.0

21.2

50.3

4.05

 

36.5

 

91

3.6

40

11.2

6.5

 

15.1

70.1

 

49.9

 

3.08

 

80.6

22.8

52.0

4.12

 

37.9

 

92

3.7

 

15.0

13.6

 

31.4

71.9

 

51.0

 

2.96

 

82.0

24.3

53.5

4.17

 

39.3

 

93

3.8

 

7.5

4.5

 

10.4

66.2

 

47.7

 

3.60

 

78.5

18.4

54.2

4.21

 

39.8

 

93

3.8

50

11.2

5.8

 

13.3

67.5

 

48.3

 

3.43

 

79.2

19.7

56.8

4.28

 

42.2

 

94

3.9

 

15.0

12.0

 

27.7

68.2

 

48.4

 

3.32

 

79.5

20.5

59.0

4.35

 

44.2

 

95

4.0

 

7.5

3.9

 

9.0

63.3

 

46.5

 

3.85

 

76.4

16.4

61.4

4.39

 

46.4

 

96

4.1

60

11.2

5.0

 

11.5

65.6

 

47.9

 

3.67

 

78.1

17.9

63.4

4.44

 

48.2

 

97

4.2

 

15.0

10.4

 

24.0

66.4

 

48.3

 

3.35

 

77.8

19.8

64.9

4.47

 

49.6

 

98

4.3

 

7.5

3.6

 

8.3

62.5

 

46.6

 

4.38

 

77.4

14.3

66.3

4.52

 

50.9

 

99

4.3

70

11.2

4.6

 

10.6

63.8

 

46.9

 

4.18

 

78.1

15.3

69.8

4.56

 

54.2

 

100

4.5

 

15.0

9.6

 

22.2

64.7

 

47.2

 

3.90

 

78.0

16.6

72.9

4.62

 

57.1

 

102

4.6

 

7.5

3.2

 

7.3

59.4

 

45.9

 

4.84

 

75.9

12.3

73.2

4.70

 

57.2

 

102

4.6

80

11.2

4.0

 

9.3

60.8

 

46.6

 

4.60

 

76.5

13.2

78.1

4.84

 

61.6

 

104

4.7

 

15.0

8.4

 

19.5

61.7

 

47.1

 

4.46

 

76.9

13.8

82.3

5.01

 

65.2

 

106

4.8

 

7.5

2.8

 

6.5

56.9

 

45.0

 

5.33

 

75.1

10.7

84.2

5.09

 

66.8

 

107

4.8

90

11.2

3.6

 

8.3

57.5

 

45.1

 

5.20

 

75.2

11.1

88.6

5.25

 

70.7

 

109

4.9

 

15.0

7.5

 

17.3

58.4

 

45.7

 

5.05

 

75.6

11.6

93.5

5.37

 

75.2

 

111

5.1

 

7.5

2.5

 

5.8

51.9

 

43.3

 

6.04

 

72.5

8.6

 

 

 

 

 

 

 

100

11.2

3.2

 

7.4

53.6

 

44.4

 

5.75

 

73.2

9.3

 

 

 

 

 

 

 

 

15.0

6.7

 

15.4

54.5

 

45.0

 

5.57

 

73.5

9.8

 

 

 

 

 

 

 

 

7.5

2.5

 

5.7

48.6

 

41.3

 

6.65

 

71.3

7.3

 

 

 

 

 

 

 

110

11.2

3.2

 

7.3

49.2

 

41.5

 

6.41

 

71.1

7.7

 

 

 

 

 

 

 

 

15.0

6.6

 

15.2

50.3

 

41.7

 

6.21

 

71.5

8.1

 

 

 

 

 

 

 

Cooling Performance is tabulated at 80.6 F DB and 66.2 F WB entering air. Heating performance tabulated at 68 F EAT Tabulated data does not include ARI/ISO corrections for fan and pump power.

All capacities are expressed in MBH.

Insulated water circuit is recommended for operation below 60F EWT. See performance correction tables for conditions beyond what is listed. Extrapolation is not permissible.

Shaded areas indicate conditions where operation is not recommended.

Johnson Controls

17

Page 17
Image 17
York YK145.00-EG4 manual RS*060 - 2000 CFM, Performance Data