Technical Guide: |
|
|
|
|
| Water Source Heat Pumps | ||||||||
BLOWER PERFORMANCE |
|
|
|
|
|
|
|
| ||||||
BLOWER PERFORMANCE |
|
|
|
|
|
|
|
|
|
| ||||
Unit | Rated | Min. | Max. | Motor |
|
| External Static Pressure (in w.g.) |
|
| |||||
Size | CFM | CFM | CFM | Speed | 0 | 0.1 | 0.2 | 0.3 | 0.4 | 0.5 |
| 0.6 | 0.7 | 0.8 |
|
|
|
| High | - | - | - | - | - | - |
| - | - | - |
007 | 260 | 182 | 299 | Med | - | - | 300 | 270 | 235 | 200 |
| - | - | - |
|
|
|
| Low | 275 | 260 | 240 | 210 | 180 | - |
| - | - | - |
|
|
|
| High | - | - | 380 | 360 | 330 | 290 |
| 240 | - | - |
009 | 320 | 235 | 368 | Med | 340 | 325 | 300 | 270 | 235 | - |
| - | - | - |
|
|
|
| Low | - | - | - | - | - | - |
| - | - | - |
|
|
|
| High | - | 475 | 450 | 420 | 385 | 345 |
| 300 | - | - |
012 | 400 | 300 | 460 | Med | 470 | 455 | 430 | 400 | 365 | 325 |
| - | - | - |
|
|
|
| Low | 385 | 370 | 355 | 330 | 300 | - |
| - | - | - |
|
|
|
| High | - | 750 | 710 | 660 | 610 | 555 |
| 495 | - | - |
018 | 640 | 495 | 736 | Med | 690 | 660 | 625 | 585 | 540 | 490 |
| - | - | - |
|
|
|
| Low | 600 | 570 | 535 | 495 | - | - |
| - | - | - |
|
|
|
| High | - | - | - | 950 | 890 | 820 |
| 740 | 650 | 550 |
024 | 800 | 560 | 920 | Med | 925 | 905 | 875 | 840 | 790 | 730 |
| 660 | 590 | - |
|
|
|
| Low | 810 | 795 | 780 | 765 | 725 | 660 |
| 590 | - | - |
|
|
|
| High | - | - | 1170 | 1120 | 1060 | 985 |
| 905 | 820 | 730 |
030 | 1000 | 730 | 1150 | Med | 1150 | 1125 | 1090 | 1045 | 990 | 925 |
| 850 | 765 | - |
|
|
|
| Low | 980 | 970 | 955 | 935 | 905 | 855 |
| 785 | - | - |
|
|
|
| High | - | 1390 | 1330 | 1270 | 1210 | 1140 |
| 1055 | 960 | 865 |
036 | 1200 | 865 | 1380 | Med | 1355 | 1320 | 1270 | 1215 | 1155 | 1085 |
| 1005 | 920 | - |
|
|
|
| Low | 1200 | 1190 | 1170 | 1130 | 1085 | 1020 |
| 950 | - | - |
|
|
|
| High | - | 1175 | 1160 | 1120 | 1075 | 1015 |
| 930 | - | - |
042 | 1400 | 980 | 1480 | Med | 1370 | 1320 | 1275 | 1210 | 1150 | 1070 |
| 925 | - | - |
|
|
|
| Low | 1480 | 1410 | 1350 | 1290 | 1220 | 1140 |
| 1050 | 950 | - |
|
|
|
| High | - | - | - | 1915 | 1835 | 1750 |
| 1660 | 1550 | 1415 |
048 | 1600 | 1160 | 1880 | Med | 1880 | 1860 | 1820 | 1770 | 1710 | 1640 |
| 1550 | 1450 | 1320 |
|
|
|
| Low | 1495 | 1490 | 1485 | 1480 | 1460 | 1420 |
| 1360 | 1285 | 1160 |
|
|
|
| High | - | 2320 | 2260 | 2200 | 2120 | 2040 |
| 1920 | 1840 | 1700 |
060 | 2000 | 1560 | 2300 | Med | 2040 | 2030 | 2005 | 1970 | 1925 | 1860 |
| 1785 | 1700 | 1610 |
|
|
|
| Low | 1760 | 1750 | 1730 | 1700 | 1660 | 1610 |
| 1560 | - | - |
|
|
|
| High | 2400 | 2320 | 2260 | 2200 | 2120 | 2040 |
| 1920 | 1840 | 1700 |
070 | 2200 | 1700 | 2400 | Med | 2040 | 2030 | 2005 | 1970 | 1925 | 1860 |
| 1785 | 1700 | - |
|
|
|
| Low | - | - | - | - | - | - |
| - | - | - |
Units are shipped
All airflow ratings are at lowest voltage rating of dual rating (ie. 208 volt)
Airflow ratings include resistance of wet coil and clean air filters.
20 | Johnson Controls |