Water Source Heat Pumps | Technical Guide: |
ARI/ISO PERFORMANCE DATA
PERFORMANCE DATA - ARI/ISO
Unit Model | Flow Rate | Air Flow | Cooling | EER | Heating | COP | |
(USGPM) | (SCFM) | Capacity (Btuh) | Capacity (Btuh) | ||||
|
|
| |||||
007 | 1.8 | 260 | 6,800 | 12.5 | 8,700 | 4.5 | |
009 | 2.4 | 320 | 8,900 | 12.4 | 11,600 | 4.4 | |
012 | 3.0 | 400 | 12,400 | 12.2 | 15,600 | 4.2 | |
018 | 4.8 | 640 | 19,100 | 13.2 | 23,400 | 4.5 | |
024 | 6.0 | 800 | 24,600 | 13.5 | 29,300 | 4.4 | |
030 | 7.8 | 1000 | 29,800 | 13.3 | 35,300 | 4.5 | |
036 | 9.0 | 1200 | 36,200 | 13.0 | 45,100 | 4.6 | |
042 | 10.4 | 1400 | 42,700 | 12.7 | 50,600 | 4.4 | |
048 | 12.0 | 1600 | 48,300 | 13.1 | 57,200 | 4.5 | |
060 | 15.0 | 2000 | 60,500 | 13.4 | 70,800 | 4.6 | |
070 | 17.5 | 2200 | 67,700 | 12.9 | 79,500 | 4.3 |
*Water Loop capacities are rated at 86°F EWT Cooling, 68°F EWT Heating.
PERFORMANCE DATA - ARI/ISO
Unit Model | Flow Rate | Air Flow | Cooling | EER | Heating | COP | |
(USGPM) | (SCFM) | Capacity (Btuh) | Capacity (Btuh) | ||||
|
|
| |||||
007 | 1.8 | 260 | 7,700 | 18.4 | 6,900 | 3.9 | |
009 | 2.4 | 320 | 10,100 | 18.3 | 9,100 | 3.8 | |
012 | 3.0 | 400 | 14,200 | 18.1 | 12,900 | 3.6 | |
018 | 4.8 | 640 | 22,900 | 20.2 | 18,800 | 3.9 | |
024 | 6.0 | 800 | 28,700 | 20.8 | 23,600 | 3.8 | |
030 | 7.8 | 1000 | 33,600 | 20.0 | 29,100 | 3.8 | |
036 | 9.0 | 1200 | 39,800 | 18.8 | 37,200 | 3.9 | |
042 | 10.4 | 1400 | 45,800 | 19.1 | 42,300 | 3.9 | |
048 | 12.0 | 1600 | 52,500 | 19.3 | 47,400 | 3.8 | |
060 | 15.0 | 2000 | 66,400 | 19.8 | 59,000 | 4.0 | |
070 | 17.5 | 2200 | 73,600 | 18.7 | 66,800 | 3.8 |
*Ground Water capacities are rated at 59°F EWT Cooling, 50°F EWT Heating.
PERFORMANCE DATA - ARI/ISO
Unit Model | Flow Rate | Air Flow | Cooling | EER | Heating | COP | |
(USGPM) | (SCFM) | Capacity (Btuh) | Capacity (Btuh) | ||||
|
|
| |||||
007 | 1.8 | 260 | 7,100 | 14.6 | 5,500 | 3.4 | |
009 | 2.4 | 320 | 9,300 | 14.5 | 6,900 | 3.3 | |
012 | 3.0 | 400 | 13,000 | 14.3 | 10,200 | 3.1 | |
018 | 4.8 | 640 | 20,600 | 15.7 | 13,900 | 3.4 | |
024 | 6.0 | 800 | 26,400 | 16.1 | 17,400 | 3.3 | |
030 | 7.8 | 1000 | 31,100 | 15.3 | 22,500 | 3.3 | |
036 | 9.0 | 1200 | 37,500 | 14.8 | 28,600 | 3.3 | |
042 | 10.4 | 1400 | 43,900 | 14.6 | 32,300 | 3.4 | |
048 | 12.0 | 1600 | 49,800 | 15.0 | 37,800 | 3.3 | |
060 | 15.0 | 2000 | 62,900 | 15.6 | 47,200 | 3.5 | |
070 | 17.5 | 2200 | 70,100 | 14.7 | 52,400 | 3.3 |
*Ground Loop capacities are rated at 77°F EFT Cooling, 32°F EFT Heating.
NOTE:
1)All Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature.
2)All Heating capacities based upon 68°F DB, 59°F WB entering air temperature.
Johnson Controls | 7 |