Table 1
RECOMMENDED INPUT WIRE AND FUSE SIZES (1)
Input Voltage / | Input Ampere Rating | Type 75°C Cu (Copper) | Grounding Wire | Fuse Size | |
Frequency | on Nameplate | Wire in Conduit | Cu (Copper) | (Super Lag) | |
|
|
|
|
|
|
208V | / 60 Hz | 130 | 1/0 | 6 | 200 |
|
|
|
|
|
|
230V | / 60 Hz | 117 | 1/0 | 6 | 175 |
|
|
|
|
|
|
460V | / 60 Hz | 59 | 4 | 8 | 100 |
|
|
|
|
|
|
575V | / 60 Hz | 47 | 6 | 8 | 75 |
200V / | 50/60 Hz | 138 | 2/0 | 4 | 225 |
220V / | 50/60 Hz | 125 | 1/0 | 6 | 200 |
380V / | 50/60 Hz | 73 | 4 | 6 | 125 |
400V / | 50/60 Hz | 69 | 4 | 8 | 100 |
415V / | 50/60 Hz | 66 | 4 | 8 | 100 |
440V / | 50/60 Hz | 63 | 4 | 8 | 100 |
500V / | 50/60 Hz | 55 | 6 | 8 | 75 |
|
|
|
|
|
|
(1)For a 600A / 44V / 100% duty cycle output in a 40°C ambient location. Refer to your local or national electrical code for other conditions.
MAY,95 | – 10 – |