Generac QT06024ANAX Spark Plugs, Battery Maintenance, Battery Replacement, Battery Fluid

Page 25

Maintenance

Figure 10.3 – Engine Air Filter

Air Filter

SPARK PLUGS

Reset the spark plug gap or replace the spark plugs as neces- sary.

1.Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and commercial solvent. Do not blast the spark plugs to clean.

2.Remove the spark plugs and check the condition. Replace the spark plugs if worn or if reuse is questionable. See the “Service Schedule” section for recommended inspection.

3.Check the spark plug gap using a wire feeler gauge. See the Specifications section for the required spark plug gap.

BATTERY MAINTENANCE

The battery should be inspected per the Service Schedule section. The following procedure should be followed for inspection:

1.Inspect the battery posts and cables for tightness and corro- sion. Tighten and clean as necessary.

2.Check the battery fluid level of unsealed batteries and, if necessary, fill with DISTILLED WATER ONLY. DO NOT USE TAP WATER IN BATTERIES.

3.Have the state of charge and condition checked. This should be done with an automotive-type battery hydrometer.

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smok- ing, open flame, sparks or any spark producing tools or equipment near the battery.

nBattery electrolyte fluid is an extremely corro- sive sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.

nDo not use any jumper cables or booster bat- tery to crank and start the generator engine. If the battery has completely discharged, remove it from the generator for recharging.

nBe sure the AUTO/OFF/MANUAL switch is set to the OFF position, before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.

Be sure the 120VAC power supply to the battery is turned OFF, or sparking may occur at the bat- tery posts as the cables are attached and cause an explosion.

BATTERY REPLACEMENT

NOTE:

Unit DOES NOT include battery.

When supplying or replacing the battery, the recommended num- ber and type of battery is listed in the Specifications Section.

NOTE:

The BCI number should be located directly on the battery.

BATTERY FLUID

Check battery electrolyte fluid based on the Service Schedule. Fluid should cover separators in all battery cells. If fluid level is low, add distilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY.

CLEANING THE STATIONARY EMERGENCY GENERATOR

Keep the generator as clean and as dry as possible. Dirt and moisture that accumulates on internal generator windings have an adverse effect on insulation resistance.

Periodically clean generator exterior surfaces. A soft brush may be used to loosen caked on dirt. Use a vacuum system or dry, low pressure air to remove any accumulations of dirt. The generator is housed inside an all-weather enclosure, clean the enclosure with a soft, damp cloth or sponge and water.

Once each year have the generator cleaned and inspected by a Service Dealer. That dealer will use dry, low pressure air to clean internal windings.

Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low, the genera- tor may require drying.

10-3

05/10 A .Rev Maint026

Image 25
Contents Stationary Emergency Generator Table of Contents HOW to Obtain Service Operation and MaintenanceIntroduction Read this Manual ThoroughlyGeneral Hazards Safety RulesFire Hazards Data Label Identification RecordEngine OIL Recommendations Equipment DescriptionCoolant Recommendations Engine Protective Devices Natural GAS Fuel System Fuel RequirementsPropane Vapor Withdrawal Fuel System Generator SpecificationsEngine Cooling SystemWeather and Maintenance Kits FOUR-LEAD, SINGLE-PHASE Stator Alternator Power Winding ConnectionsPhase Alternators Y Configuration Alternator AC Lead ConnectionsStator Power Winding Connections 3-phase, 120/208V 6 Lead Control Panel Interface Using the AUTO/OFF/MANUAL SwitchChoose Language Troubleshooting Activation ChartAutomatic Transfer Operation LOW Speed ExerciseOvercrank Shutdown Alarm LOW OIL Pressure Shutdown AlarmOverspeed Shutdown Alarm RPM Sensor Failure Shutdown AlarmLOW Battery Alarm UNDER-FREQUENCY Shutdown AlarmLOW Battery Warning Missing CAM Pulse AlarmInternal Failure Shutdown Alarm Overvoltage AlarmCanbus Alarm Ignition AlarmCondition Chery Maintenance Alert ChartPanel Operating Unit with Automatic Transfer Switch Operating Unit with Manual Transfer SwitchStationary Emergency Generator Control and Operation Engine START-UP and TransferCheck Engine OIL General MaintenanceChanging Engine OIL Cooling INTAKE/OUTLETCoolant Change Engine CoolantOverload Protection for Engine DC Electrical System Exercise SystemBattery Replacement Battery MaintenanceBattery Fluid Spark PlugsSystem / Component Frequency Procedure Service ScheduleProblem Cause Correction Troubleshooting GuidePage Assy STR 390 25GD3 CPL Page Page Page Group a UL Circuit Breaker 225AF UL Circuit Breaker KG Group a This page Left Intentionally Blank Page NUT Flanged HEX M12-1.75 Page Battery TRAY, C1 & C2 Page Group D Page Page Weldment Radiator Support C2 Page Page Exploded View Turbo 2.4L G2 Page Group F Page Page Drawing #0H7323 COIL-2.4L G2 Ignition Page Flange Fuel Inlet Page FLANGE, Fuel Inlet Page Rear Wrap C2 G2 60KW Page Page Page Page Page Page Page Page Page Page Page Page Page Page 04/07 a .Rev BackPg001

QT06024ANAX, QT06024AVSX, QT06024ANSX, QT06024AVAX specifications

The Generac QT06024AVAX, QT06024ANSX, QT06024AVSX, and QT06024ANAX are powerful and versatile residential generators designed for those who want the peace of mind provided by reliable backup power. These models from Generac's Guardian Series are engineered for performance, efficiency, and ease of use, making them ideal solutions for homeowners looking to ensure uninterrupted power during outages.

One of the standout features of these generators is their robust 60 kW capacity, which allows them to power essential home appliances, HVAC systems, and even larger electricity-demanding devices without a hitch. This capacity makes them suitable for medium to large homes, providing enough energy to keep daily operations running smoothly even during extended outages.

The QT series incorporates Generac's advanced Quiet-Test technology, which reduces noise levels during self-testing. This feature enables the generator to perform regular self-diagnostic tests at a much quieter decibel level, ensuring it does not disrupt the household during these checks. Additionally, the generators are designed with a weather-resistant enclosure, providing durability and protection against various environmental conditions.

The models are equipped with an intuitive control panel featuring a user-friendly digital display that allows for easy monitoring of power usage and system status. They also feature an automatic transfer switch that seamlessly switches from grid power to generator power in case of an outage, ensuring that the transition is almost instantaneous and worry-free for homeowners.

Moreover, the QT series generators utilize a liquid-cooled engine, which provides greater efficiency and performance compared to air-cooled alternatives. This technology not only ensures longer run times but also contributes to a longer lifespan for the generator. The low-oil pressure shutdown feature is another critical safety aspect, protecting the engine from damage by automatically shutting it down when oil levels are too low.

Finally, these models are designed with flexibility in mind. They can be customized with various accessories and options to meet specific homeowner needs. Whether for full home backup or partial power, the Generac QT06024AVAX, QT06024ANSX, QT06024AVSX, and QT06024ANAX are reliable solutions that give homeowners the confidence to weather any storm without losing power. With their combination of advanced technology, powerful performance, and user-friendly features, Generac continues to set the standard in home standby power solutions.