Generac QT06024AVAX, QT06024ANAX, QT06024ANSX LOW Speed Exercise, Automatic Transfer Operation

Page 16

Control Panel

INSTALLATION ASSISTANT

Interconnect System Self Test Feature (follow the on-screen prompts).

Upon power up, this controller will go through a system self test which will check for the presence of utility voltage on the DC circuits. This is done to prevent damage if the installer mistakenly connects AC utility power sense wires into the DC terminal block. If utility voltage is detected, the controller will display a warning message and lock out the generator, preventing damage to the controller. Power to the controller must be removed to clear this warning.

Utility voltage must be turned on and present at the N1 and N2 terminals inside the generator control panel for this test to be performed and pass.

NOTE:

DAMAGE CAUSED BY MISWIRING OF THE INTERCONNECT WIRES IS NOT WARRANTABLE!

This test will be performed each time the controller is powered up.

Upon first power up of the generator, the display interface will begin an installation assistant. The assistant will prompt the user to set the minimum settings to operate. These settings are simply: Current Date/Time and Exercise Day/Time. The maintenance inter- vals will be initialized when the exercise time is entered.

The exercise settings can be changed at any time via the "EDIT" menu (see Appendix, "Menu System").

If the 12 volt battery is disconnected or the fuse removed, the Installation Assistant will operate upon power restoration. The only difference is the display will only prompt the customer for the current Time and Date.

IF THE INSTALLER TESTS THE GENERATOR PRIOR TO INSTALLATION, PRESS THE “ENTER” KEY TO AVOID SETTING UP THE EXERCISE TIME. THIS WILL ENSURE THAT WHEN THE CUSTOMER POWERS UP THE UNIT, HE WILL STILL BE PROMPTED TO ENTER AN EXERCISE TIME.

SETTING THE EXERCISE TIMER

This generator is equipped with an exercise timer. Once it is set, the generator will start and exercise every seven days, on the day of the week and at the time of day specified. During this exercise period, the unit runs for approximately 12 minutes and then shuts down. Transfer of loads to the generator output does not occur during the exercise cycle unless utility power is lost.

LOW SPEED EXERCISE

The standard start sequence will be initiated.

All 1800 rpm units will exercise at 1400 RPM

All 3600 rpm units will exercise at 1800 RPM

If utility is lost during exercise the controller will do the following:

Wait for the “line interrupt period” for utility to return. If utility returns within the “line interrupt period”, continue to exercise at low RPM.

8-3

If utility is still lost after the “line interrupt period”, run the engine up to normal RPM and transfer the load. At this time the con- troller will exit the exercise routine and assume full automatic operation.

USER ADJUSTABLE SETTINGS

Setting

Factory

Minimum

Maximum

Increment

Default

Setting

Setting

 

 

Exercise

2 pm

00:00 (12 am)

23:59

1 min

time

(11:59 pm)

 

 

 

 

 

 

 

 

Exercise

Wed

Sun

Sat

1 day

day

 

 

 

 

 

 

 

 

 

Current

12 am

00:00 (12 am)

23:59

1 min

Time

(11:59 pm)

 

 

 

 

 

 

 

 

Current

Sun

Sun

Sat

1 day

Day

 

 

 

 

 

 

 

 

 

Current

Jan

Jan

Dec

1 month

Month

 

 

 

 

 

 

 

 

 

Current

2008

2008

2100

1 year

Year

 

 

 

 

 

 

 

 

 

Language

English

French

Spanish

N/A

 

 

 

 

 

Contrast

80%

0%

100%

1%

 

 

 

 

 

FUEL CONVERSION

For fuel conversion steps, refer to the GenSpec section,

RECONFIGURING THE FUEL SYSTEM.

OPERATION

This system is intended to supply standby power in the event of a utility failure. The control system will monitor the utility voltage to determine if stand-by power is required. Should the utility voltage fail, the generator will start and run normally, detaching from the utility and supplying the customer load from the generator. When utility power returns, the controller will re-transfer the customer load back to utility and shut down the generator.

AUTOMATIC TRANSFER OPERATION

To select automatic operation, do the following:

1.Make sure the transfer switch main contacts are set to their UTILITY position, i.e., loads connected to the utility power source.

2.Be sure that normal UTILITY power source voltage is avail- able to transfer switch terminal lugs N1 and N2 (Refer to the Electrical Data section).

3.Set the generator’s AUTO/OFF/MANUAL switch to AUTO.

4.Set the generator’s main circuit breaker to its ON (or CLOSED) position.

With the preceding steps complete, the generator will start auto- matically when utility source voltage drops below a preset level. After the unit starts, loads are transferred to the standby power source. Refer to the Sequence of Automatic Operation section.

04/11 D .Rev CntrlNexus001

Image 16
Contents Stationary Emergency Generator Table of Contents Operation and Maintenance HOW to Obtain ServiceIntroduction Read this Manual ThoroughlySafety Rules General HazardsFire Hazards Identification Record Data LabelEngine OIL Recommendations Equipment DescriptionCoolant Recommendations Engine Protective Devices Natural GAS Fuel System Fuel RequirementsPropane Vapor Withdrawal Fuel System Specifications GeneratorEngine Cooling SystemWeather and Maintenance Kits Alternator Power Winding Connections FOUR-LEAD, SINGLE-PHASE StatorPhase Alternators Y Configuration Alternator AC Lead ConnectionsStator Power Winding Connections 3-phase, 120/208V 6 Lead Using the AUTO/OFF/MANUAL Switch Control Panel InterfaceActivation Chart Choose Language TroubleshootingLOW Speed Exercise Automatic Transfer OperationLOW OIL Pressure Shutdown Alarm Overcrank Shutdown AlarmOverspeed Shutdown Alarm RPM Sensor Failure Shutdown AlarmUNDER-FREQUENCY Shutdown Alarm LOW Battery AlarmLOW Battery Warning Missing CAM Pulse AlarmOvervoltage Alarm Internal Failure Shutdown AlarmCanbus Alarm Ignition AlarmMaintenance Alert Chart Condition CheryPanel Operating Unit with Manual Transfer Switch Operating Unit with Automatic Transfer SwitchStationary Emergency Generator Control and Operation Engine START-UP and TransferGeneral Maintenance Check Engine OILChanging Engine OIL Cooling INTAKE/OUTLETEngine Coolant Coolant ChangeOverload Protection for Engine DC Electrical System Exercise SystemBattery Maintenance Battery ReplacementBattery Fluid Spark PlugsService Schedule System / Component Frequency ProcedureTroubleshooting Guide Problem Cause CorrectionPage Assy STR 390 25GD3 CPL Page Page Page Group a UL Circuit Breaker 225AF UL Circuit Breaker KG Group a This page Left Intentionally Blank Page NUT Flanged HEX M12-1.75 Page Battery TRAY, C1 & C2 Page Group D Page Page Weldment Radiator Support C2 Page Page Exploded View Turbo 2.4L G2 Page Group F Page Page Drawing #0H7323 COIL-2.4L G2 Ignition Page Flange Fuel Inlet Page FLANGE, Fuel Inlet Page Rear Wrap C2 G2 60KW Page Page Page Page Page Page Page Page Page Page Page Page Page Page 04/07 a .Rev BackPg001

QT06024ANAX, QT06024AVSX, QT06024ANSX, QT06024AVAX specifications

The Generac QT06024AVAX, QT06024ANSX, QT06024AVSX, and QT06024ANAX are powerful and versatile residential generators designed for those who want the peace of mind provided by reliable backup power. These models from Generac's Guardian Series are engineered for performance, efficiency, and ease of use, making them ideal solutions for homeowners looking to ensure uninterrupted power during outages.

One of the standout features of these generators is their robust 60 kW capacity, which allows them to power essential home appliances, HVAC systems, and even larger electricity-demanding devices without a hitch. This capacity makes them suitable for medium to large homes, providing enough energy to keep daily operations running smoothly even during extended outages.

The QT series incorporates Generac's advanced Quiet-Test technology, which reduces noise levels during self-testing. This feature enables the generator to perform regular self-diagnostic tests at a much quieter decibel level, ensuring it does not disrupt the household during these checks. Additionally, the generators are designed with a weather-resistant enclosure, providing durability and protection against various environmental conditions.

The models are equipped with an intuitive control panel featuring a user-friendly digital display that allows for easy monitoring of power usage and system status. They also feature an automatic transfer switch that seamlessly switches from grid power to generator power in case of an outage, ensuring that the transition is almost instantaneous and worry-free for homeowners.

Moreover, the QT series generators utilize a liquid-cooled engine, which provides greater efficiency and performance compared to air-cooled alternatives. This technology not only ensures longer run times but also contributes to a longer lifespan for the generator. The low-oil pressure shutdown feature is another critical safety aspect, protecting the engine from damage by automatically shutting it down when oil levels are too low.

Finally, these models are designed with flexibility in mind. They can be customized with various accessories and options to meet specific homeowner needs. Whether for full home backup or partial power, the Generac QT06024AVAX, QT06024ANSX, QT06024AVSX, and QT06024ANAX are reliable solutions that give homeowners the confidence to weather any storm without losing power. With their combination of advanced technology, powerful performance, and user-friendly features, Generac continues to set the standard in home standby power solutions.