2.7BATTERY INSTALLATION

DANGER

Standby generators installed with automatic trans- ! fer switches will crank and start automatically

when NORMAL (UTILITY) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to personnel, do not connect battery cables until the NORMAL source voltage at the transfer switch is correct and the system is ready to be placed into operation.

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the bat- tery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks or any spark producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely caustic ! sulfuric acid solution that can cause severe burns.

Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.

Do not dispose of the battery in a fire. The battery is capable of exploding.

Do not open or mutilate the battery. Released ! electrolyte can be toxic and harmful to the skin

and eyes.

The battery represents a risk of high short circuit current. When working on the battery, always remove watches, rings or other metal objects, and only use tools that have insulated handles.

‹2.7.1 VENTED BATTERIES

The electrolyte is a dilute sulfuric acid that is

!harmful to the skin and eyes. It is electrically con- ductive and corrosive. The following procedures are to be observed:

Wear full eye protection and protective clothing,

Where electrolyte contacts the skin, wash it off immediately with water,

Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical atten- tion, and

Spilled electrolyte is to be washed down with an acid- neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbonate of soda to one gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.

Lead acid batteries present a risk of fire because they generate hydrogen gas. The following proce- dures are to be followed:

DO NOT SMOKE when near batteries,

DO NOT cause flame or spark in battery area, and

Discharge static electricity from body before touching batteries by first touching a grounded metal surface.

Servicing of batteries is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.

For recommended batteries, see Section 4.5, “Battery Maintenance”. All batteries must be at 100 percent state- of-charge before they are installed on the generator.

When using maintenance-free batteries, it is not neces- sary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals spec- ified in Section 4, “Maintenance.” A negative ground sys- tem is used. Battery connections are shown on the wiring diagrams. Make sure all batteries are correctly connected and terminals are tight. Observe battery polarity when connecting batteries to the generator set.

NOTE:

Damage will result if the battery connections are reversed.

10 Generac® Power Systems, Inc.

Image 12
Contents Liquid-cooled, Prepackaged Standby Generators Models Introduction Authorized Dealer LocationInstallation Diagram General Hazards Electrical Hazards Prepackaged Transfer Switch UNPACKING/INSPECTIONGenerator Generator AC Connection SystemsSpecifications Main Circuit BreakerEngine Protective Devices Fuel Requirements Recommendations ‹ 1.8.2 Generator and Load Compatibility‹ 1.9.1 Conversion to LP GAS Vapor Emissions Control System Coolant‹ 1.12.1 AIR Fuel Ratio Controller Standby Generator Installation Basic Standby Electric SystemNfpa Standards Other Published StandardsTransfer Switch Start Signal Connections ‹ 2.6.1 PRE-PACKAGED Type SwitchMethod Grounding the GeneratorBattery Installation ‹ 2.7.1 Vented BatteriesPreparation Before START-UP Using the AUTO/OFF/MANUAL Switch Sequence of Automatic Operation Engine Heater‹ 3.2.3 Manual Position Weekly Exercise Cycle Checking the Engine OIL LevelChanging the Engine AIR Cleaner ‹ 4.2.2 OIL and Filter Change ProcedureChanging the Engine OIL and Filter ‹ 4.2.1 Engine OIL RecommendationsBattery Maintenance ‹ 4.5.1 Battery ReplacementSpark Plugs Cooling SystemMiscellaneous Maintenance Overload Protection forDC Fuse Engine CoolantOUT of Service Procedure ‹ 4.11.1 Removal from Service‹ 4.11.2 Return to Service Service Schedule SYSTEM/COMPONENT Procedure FrequencyTroubleshooting Guide Problem Cause CorrectionInstallation Diagram TS1 Generator D4992-A Guardian Liquid- Panel 4.3L Drawing No Section Wiring Diagram Control Panel Model No KW Generators No D6975 EC1 ACT 18 12 19 11 3529 QTY Description Base Frame Assembly M6 Hinge Panel Face Panel BTM & Back Control Exploded Views and Parts Lists Cover Plate AVR Exploded Views and Parts Lists QTY To Engine Flywheel Washer Lock M12 Exploded Views and Parts Lists Engine 4.3L GM Exploded Views and Parts Lists MOUNT, Engine R & L KIT Radiator Copper Brass DIA. Clamp Assembly 2 Compartment To Engine Front NUT Wing 1/4-20 Nylk To Stepper Motor Support Solenoid NAT GAS Assembly Elbow 90D 3/4NPT Exploded Views and Parts Lists Muffler Catalyst 4.3L Assembly Motor Stepper To Thermostat Housing Guardian Liquid-cooled 40 kW Generators Guardian Liquid-cooled 40 kW Generators Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule This Warranty Shall not Apply to the Following