Generac 0043736, 0046265 owner manual Troubleshooting Guide, Problem Cause Correction

Page 22

Section 5 — Troubleshooting

Guardian Liquid-cooled 40 kW Generator

5.1TROUBLESHOOTING GUIDE

PROBLEM

CAUSE

CORRECTION

The engine will not crank.

1.

Fuse blown

1.

Replace fuse.

 

2.

Loose, corroded or defective

2.

Tighten, clean or replace

 

 

battery cables

 

as necessary.

 

3.

Defective starter contactor

3.

*

 

4.

Defective starter motor

4.

*

 

5.

Dead Battery

5.

Charge or replace battery.

 

 

 

 

 

The engine cranks but

1.

Out of fuel

1.

Replenish fuel.

will not start.

2.

Defective fuel solenoid (FS)

2.

*

 

3.

Open #14 wire from

3.

*

 

 

engine control board

 

 

 

4.

Defective spark plug(s)

4.

Clean, re-gap or replace plug(s).

 

5.

Dirty/Blocked air filter

5.

Clean or replace as required.

 

 

 

 

 

The engine starts hard

1.

Air cleaner

1.

Check, clean or replace air cleaner.

and runs rough.

 

plugged or damaged

 

 

 

2.

Defective spark plug(s)

2.

Clean, re-gap or replace plug(s).

 

3.

Dirty/Blocked air filter

3.

Clean or replace as required.

 

 

 

 

 

The engine starts, but then

1.

Engine oil level low

1.

Check oil and add oil as needed.

shuts down.

2.

Defective low oil

2.

*

 

 

pressure switch

 

 

 

3.

Defective high temperature

3.

*

 

 

switch

 

 

 

4.

Defective control board

4.

*

 

5.

Low coolant level

5.

Check coolant level, repair leaks

 

 

 

 

and refill.

 

 

 

 

 

The AUTO/OFF/MANUAL switch

1.

Defective switch

1.

*

is set to OFF, but the engine

2.

Defective control board

2.

*

continues to run.

 

 

 

 

 

 

 

 

 

There is no AC output from

1.

Generator main line circuit

1.

Reset circuit breaker

the generator.

 

breaker open

 

to ON (or closed).

 

2.

Generator internal failure

2.

*

 

 

 

 

 

There is no transfer to

1.

Generator main line circuit

1.

Reset circuit breaker

STANDBY after UTILITY

 

breaker open

 

to ON (or closed).

source failure.

2.

Defective transfer switch coil

2.

*

 

3.

Defective transfer relay

3.

*

 

4.

Transfer relay circuit open

4.

*

 

5.

Defective control logic board

5.

*

*Contact the nearest Generac/Guardian Authorized Dealer for assistance.

20 Generac® Power Systems, Inc.

Image 22
Contents Liquid-cooled, Prepackaged Standby Generators Models Introduction Authorized Dealer LocationInstallation Diagram General Hazards Electrical Hazards Generator Prepackaged Transfer SwitchUNPACKING/INSPECTION Generator AC Connection SystemsMain Circuit Breaker SpecificationsEngine Protective Devices ‹ 1.8.2 Generator and Load Compatibility Fuel Requirements Recommendations‹ 1.9.1 Conversion to LP GAS Vapor Coolant Emissions Control System‹ 1.12.1 AIR Fuel Ratio Controller Nfpa Standards Standby Generator InstallationBasic Standby Electric System Other Published StandardsMethod Transfer Switch Start Signal Connections‹ 2.6.1 PRE-PACKAGED Type Switch Grounding the GeneratorBattery Installation ‹ 2.7.1 Vented BatteriesPreparation Before START-UP Using the AUTO/OFF/MANUAL Switch Engine Heater Sequence of Automatic Operation‹ 3.2.3 Manual Position Weekly Exercise Cycle Checking the Engine OIL LevelChanging the Engine OIL and Filter Changing the Engine AIR Cleaner‹ 4.2.2 OIL and Filter Change Procedure ‹ 4.2.1 Engine OIL RecommendationsSpark Plugs Battery Maintenance‹ 4.5.1 Battery Replacement Cooling System DC Fuse Miscellaneous Maintenance Overload Protection for Engine Coolant‹ 4.11.1 Removal from Service OUT of Service Procedure‹ 4.11.2 Return to Service Service Schedule SYSTEM/COMPONENT Procedure FrequencyTroubleshooting Guide Problem Cause CorrectionInstallation Diagram TS1 Generator D4992-A Guardian Liquid- Panel 4.3L Drawing No Section Wiring Diagram Control Panel Model No KW Generators No D6975 EC1 ACT 18 12 19 11 3529 QTY Description Base Frame Assembly M6 Hinge Panel Face Panel BTM & Back Control Exploded Views and Parts Lists Cover Plate AVR Exploded Views and Parts Lists QTY To Engine Flywheel Washer Lock M12 Exploded Views and Parts Lists Engine 4.3L GM Exploded Views and Parts Lists MOUNT, Engine R & L KIT Radiator Copper Brass DIA. Clamp Assembly 2 Compartment To Engine Front NUT Wing 1/4-20 Nylk To Stepper Motor Support Solenoid NAT GAS Assembly Elbow 90D 3/4NPT Exploded Views and Parts Lists Muffler Catalyst 4.3L Assembly Motor Stepper To Thermostat Housing Guardian Liquid-cooled 40 kW Generators Guardian Liquid-cooled 40 kW Generators MANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule This Warranty Shall not Apply to the Following