Generac 0043736, 0046265 owner manual OUT of Service Procedure, ‹ 4.11.1 Removal from Service

Page 20

Section 4 — Maintenance

Guardian Liquid-cooled 40 kW Generator

4.11 OUT OF SERVICE PROCEDURE

‹4.11.1 REMOVAL FROM SERVICE

If the generator cannot exercise every seven days, and it is to be out of service longer than 90 days, prepare the generator for storage as follows:

1.Start the engine and let it warm up.

2.Close the fuel shutoff valve in the fuel supply line and allow the unit to shut down.

3.Once the unit has shut down, it will signal a fault on the control panel.

4.Set the AUTO/OFF/MANUAL switch to OFF and turn off the UTILITY power to the transfer switch.

5.While the engine is still warm from running, drain the oil completely. Refill the crankcase with SAE 15W-40 oil having API Service Class SG, SH or SJ.

6.Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase.

7.Remove the spark plug(s) and spray fogging agent into the spark plug(s) threaded openings. Reinstall and tighten the spark plug(s).

8.Remove the battery and store it in a cool, dry room on a wooden board. Never store the battery on any concrete or earthen floor.

9.Clean and wipe the entire generator.

‹4.11.2 RETURN TO SERVICE

To return the unit to service after storage, proceed as follows:

1.Verify that UTILITY power is turned off to the trans- fer switch and that the AUTO/OFF/MANUAL switch is set to OFF.

2.Check the tag on the engine for oil viscosity and classification. Verify that the correct recommended oil is used in engine, see Section 4.2.1. If necessary, drain and refill with the proper oil.

3.Check the battery. Fill all cells to the proper level with distilled water. DO NOT USE TAP WATER IN THE BATTERY. Remove the battery before charging. Recharge the battery to 100 percent state of charge, or, if defective, replace the battery with a 12-volt DC Group 27F battery rated for 90 amp hours (part # 058665).

4.Clean and wipe the entire generator.

5.Reconnect the battery. Observe battery polarity. Damage may occur if the battery is connected incor- rectly.

6.Open the fuel shutoff valve.

7.Start the unit by moving the AUTO/OFF/MANUAL switch to MANUAL. Allow the unit to warm up thor- oughly.

8.Stop the unit and set the AUTO/OFF/MANUAL switch to AUTO.

9.Turn on the UTILITY power to the transfer switch.

10.The generator is now ready for service.

18 Generac® Power Systems, Inc.

Image 20
Contents Liquid-cooled, Prepackaged Standby Generators Models Introduction Authorized Dealer LocationInstallation Diagram General Hazards Electrical Hazards Prepackaged Transfer Switch UNPACKING/INSPECTIONGenerator Generator AC Connection SystemsEngine Protective Devices SpecificationsMain Circuit Breaker ‹ 1.9.1 Conversion to LP GAS Vapor Fuel Requirements Recommendations‹ 1.8.2 Generator and Load Compatibility ‹ 1.12.1 AIR Fuel Ratio Controller Emissions Control SystemCoolant Standby Generator Installation Basic Standby Electric SystemNfpa Standards Other Published StandardsTransfer Switch Start Signal Connections ‹ 2.6.1 PRE-PACKAGED Type SwitchMethod Grounding the GeneratorBattery Installation ‹ 2.7.1 Vented BatteriesPreparation Before START-UP Using the AUTO/OFF/MANUAL Switch ‹ 3.2.3 Manual Position Sequence of Automatic OperationEngine Heater Weekly Exercise Cycle Checking the Engine OIL LevelChanging the Engine AIR Cleaner ‹ 4.2.2 OIL and Filter Change ProcedureChanging the Engine OIL and Filter ‹ 4.2.1 Engine OIL RecommendationsBattery Maintenance ‹ 4.5.1 Battery ReplacementSpark Plugs Cooling SystemMiscellaneous Maintenance Overload Protection forDC Fuse Engine Coolant‹ 4.11.2 Return to Service OUT of Service Procedure‹ 4.11.1 Removal from Service Service Schedule SYSTEM/COMPONENT Procedure FrequencyTroubleshooting Guide Problem Cause CorrectionInstallation Diagram TS1 Generator D4992-A Guardian Liquid- Panel 4.3L Drawing No Section Wiring Diagram Control Panel Model No KW Generators No D6975 EC1 ACT 18 12 19 11 3529 QTY Description Base Frame Assembly M6 Hinge Panel Face Panel BTM & Back Control Exploded Views and Parts Lists Cover Plate AVR Exploded Views and Parts Lists QTY To Engine Flywheel Washer Lock M12 Exploded Views and Parts Lists Engine 4.3L GM Exploded Views and Parts Lists MOUNT, Engine R & L KIT Radiator Copper Brass DIA. Clamp Assembly 2 Compartment To Engine Front NUT Wing 1/4-20 Nylk To Stepper Motor Support Solenoid NAT GAS Assembly Elbow 90D 3/4NPT Exploded Views and Parts Lists Muffler Catalyst 4.3L Assembly Motor Stepper To Thermostat Housing Guardian Liquid-cooled 40 kW Generators Guardian Liquid-cooled 40 kW Generators PURCHASER’S/OWNER’S Warranty Responsibilities Your Warranty Rights and ObligationsMANUFACTURER’S Emission Control System Warranty Coverage Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule This Warranty Shall not Apply to the Following