Generac 0043736, 0046265 owner manual Preparation Before START-UP

Page 13

Section 2 — Installation

Guardian Liquid-cooled 40 kW Generator

2.8 PREPARATION BEFORE START-UP

‹ 2.8.5 BELT TENSION

The instructions in this section assume that the standby generator has been properly installed, serviced, tested, adjusted and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read the “Safety Rules” on Pages 2 and 3, as well as all other safe- ty information in this manual, before attempting to oper- ate this (and related) equipment.

Check the engine fan belt tension and condition prior to placing the unit into service and at recommended intervals. Belt tension is correct when a force of approx- imately 22 pounds (10 kg), applied midway between pulleys, deflects the belt about 3/8- to 5/8-inch (10 to 16 mm).

‹2.8.1 PRIOR TO INITIAL START-UP

Prior to initially starting the generator, it must be

!properly prepared for use. Any attempt to crank or start the engine before it has been properly serviced with the recommended types and quanti- ties of engine fluids (oil, coolant, fuel, etc.) may result in an engine failure.

Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service inter- vals, please refer to Section 4, “Maintenance.”

‹2.8.2 FUEL SYSTEM

Make sure the fuel supply system to the generator (a) delivers the correct fuel at the correct pressure and (b) is properly purged and leak tested according to code. No fuel leakage is permitted. See Section 1.8, “Specifications”, for more information.

‹2.8.6 ELECTRICAL SYSTEM

Make sure the generator is properly connected to an approved earth ground and/or ground rod.

Make sure the generator battery is fully charged, proper- ly installed and interconnected, and ready for use.

Check to ensure that there are no loose electrical con- nections. Restrain any loose wires to keep them clear of any moving generator set components.

‹2.8.7 RODENT PROTECTION

Make sure the four 3-inch diameter cap plugs (part # 0A8785) are properly installed in the tie-down holes in the side rails of the unit’s base frame (Figure 2.3). The cap plugs are shipped in a plastic bag located in the lower connection box. These plugs are needed to pre- vent rodents from accessing the interior of the genera- tor set. On acoustic units, cap plugs also are needed to stay within noise specification limits.

Figure 2.3 - Base Frame Cap Plugs

‹2.8.3 GENERATOR SET LUBRICATION

Check the engine crankcase oil level before operating and add oil to the proper level – the dipstick “FULL” mark. Never operate the engine with the oil level below the dipstick “ADD” mark. See Section 1.8, “Specifications” and Section 1.10, “Engine Oil Recommendations”.

NOTE:

This engine is shipped from the manufacturer with SAE 15W-40 oil. This oil should be changed after 30 hours of operation.

‹2.8.4 ENGINE COOLANT

Have the engine cooling system properly filled with the recommended coolant mixture. Check the system for leaks and other problems. See Section 1.8, “Specifications” and Section 1.11, “Coolant”.

Generac® Power Systems, Inc. 11

Image 13
Contents Liquid-cooled, Prepackaged Standby Generators Models Authorized Dealer Location IntroductionInstallation Diagram General Hazards Electrical Hazards UNPACKING/INSPECTION Prepackaged Transfer SwitchGenerator Generator AC Connection SystemsMain Circuit Breaker SpecificationsEngine Protective Devices ‹ 1.8.2 Generator and Load Compatibility Fuel Requirements Recommendations‹ 1.9.1 Conversion to LP GAS Vapor Coolant Emissions Control System‹ 1.12.1 AIR Fuel Ratio Controller Basic Standby Electric System Standby Generator InstallationNfpa Standards Other Published Standards‹ 2.6.1 PRE-PACKAGED Type Switch Transfer Switch Start Signal ConnectionsMethod Grounding the Generator‹ 2.7.1 Vented Batteries Battery InstallationPreparation Before START-UP Using the AUTO/OFF/MANUAL Switch Engine Heater Sequence of Automatic Operation‹ 3.2.3 Manual Position Checking the Engine OIL Level Weekly Exercise Cycle‹ 4.2.2 OIL and Filter Change Procedure Changing the Engine AIR CleanerChanging the Engine OIL and Filter ‹ 4.2.1 Engine OIL Recommendations‹ 4.5.1 Battery Replacement Battery MaintenanceSpark Plugs Cooling SystemOverload Protection for Miscellaneous MaintenanceDC Fuse Engine Coolant‹ 4.11.1 Removal from Service OUT of Service Procedure‹ 4.11.2 Return to Service SYSTEM/COMPONENT Procedure Frequency Service ScheduleProblem Cause Correction Troubleshooting GuideInstallation Diagram TS1 Generator D4992-A Guardian Liquid- Panel 4.3L Drawing No Section Wiring Diagram Control Panel Model No KW Generators No D6975 EC1 ACT 18 12 19 11 3529 QTY Description Base Frame Assembly M6 Hinge Panel Face Panel BTM & Back Control Exploded Views and Parts Lists Cover Plate AVR Exploded Views and Parts Lists QTY To Engine Flywheel Washer Lock M12 Exploded Views and Parts Lists Engine 4.3L GM Exploded Views and Parts Lists MOUNT, Engine R & L KIT Radiator Copper Brass DIA. Clamp Assembly 2 Compartment To Engine Front NUT Wing 1/4-20 Nylk To Stepper Motor Support Solenoid NAT GAS Assembly Elbow 90D 3/4NPT Exploded Views and Parts Lists Muffler Catalyst 4.3L Assembly Motor Stepper To Thermostat Housing Guardian Liquid-cooled 40 kW Generators Guardian Liquid-cooled 40 kW Generators MANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyThis Warranty Shall not Apply to the Following Warranty Schedule