Briggs & Stratton 030209 owner manual Using the Generator, System Ground, Generator Location

Page 8

5500W Portable Generator

USING THE GENERATOR

System Ground

The generator has a system ground that connects the generator frame components to the ground terminals on the AC output receptacles.The system ground is connected to the AC neutral wire (the neutral is bonded to the generator frame).

Special Requirements

There may be Federal or State Occupational Safety and Health Administration (OSHA) regulations, local codes, or ordinances that apply to the intended use of the generator. Please consult a qualified electrician, electrical inspector, or the local agency having jurisdiction.

In some areas, generators are required to be registered with local utility companies.

If the generator is used at a construction site, there may be additional regulations which must be observed.

Connecting to a Building’s Electrical System

Connections for standby power to a building’s electrical system must be made by a qualified electrician.The connection must isolate the generator power from utility power, and must comply with all applicable laws and electrical codes.

WARNING

Generator produces powerful voltage.

Failure to isolate generator from power utility can result in death or injury to electric utility workers due to backfeed of electrical energy.

When using generator for backup power, notify utility company. Use approved transfer equipment to isolate generator from electric utility.

Use a ground fault circuit interrupter (GFCI) in any damp or highly conductive area, such as metal decking or steel work.

DO NOT touch bare wires or receptacles.

DO NOT use generator with electrical cords which are worn, frayed, bare or otherwise damaged.

DO NOT operate generator in the rain.

DO NOT handle generator or electrical cords while standing in water, while barefoot, or while hands or feet are wet.

DO NOT allow unqualified persons or children to operate or service generator.

Generator Location

Generator Clearance

WARNING

Running generator gives off carbon monoxide, an odorless, colorless, poison gas.

Breathing carbon monoxide will cause nausea, fainting or death.

Operate generator ONLY outdoors.

Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes or other openings.

DO NOT operate generator inside any building or enclosure, including the generator compartment of a recreational vehicle (RV).

The generator must be at least 5 ft. (152 cm) from structures having combustible walls and/or other combustible materials. Leave at least 3 ft. (92 cm) all around generator including overhead, for adequate cooling, maintenance and servicing.

Place generator in a well ventilated area, which will allow for removal of deadly exhaust gas. DO NOT place generator where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building. Ensure exhaust gas is kept away from any windows, doors, ventilation intakes or other openings that can allow exhaust gas to collect in a confined area (Figure 3). Prevailing winds and air currents should be taken into consideration when positioning generator.

Figure 3 — Generator Clearance

Typical Generator Shown

Exhaust Port

8

Image 8
Contents 030209 5500W Equipment Description Table of ContentsSafety Rules When Adding or Draining Fuel When Starting EquipmentWhen Operating Equipment When Transporting or Repairing EquipmentWhen Adjusting or Making Repairs to Your Generator When Testing for Engine SparkKnow Your Generator Assembly Install Wheel KITCarton Contents Remove Generator From CartonWhen Adding Fuel Install fuel cap and wipe up any spilled fuelBefore Starting the Engine Add Engine OilUsing the Generator Connecting to a Building’s Electrical SystemSystem Ground Generator LocationConnecting Electrical Loads Operating GeneratorStarting the Engine Stopping the EngineReceptacles 120/240 Volt AC, 30 Amp, Locking ReceptacleVolt AC, 20 Amp, Duplex Receptacles HotPower Management Dont Overload GeneratorCapacity ExampleSpecifications General Maintenance RecommendationsEngine Maintenance Generator MaintenanceEngine Storage Other Storage Tips StorageGenerator Storage Troubleshooting Problem Cause CorrectionConsumer Use Years Years or YearTabla DE Contenidos Descripción DEL EquipoInstrucciones DE Seguridad AdvertenciaCuando Añada Combustible O Vacíe EL Depósito Cuando Ponga EN Funcionamiento EL EquipoCuando Opere EL Equipo Cuando Transporte O Repare EL EquipoCuando Pruebe LA Bujía DEL Motor PrecauciónCuando Ajuste O Haga Reparaciones a SU Generador Conozca SU Generador CortacircuitosTuerca Mariposa de Conexion a Tierra Tapa del Depósito del Aceite Llene el motor con aceiteMontaje Instale EL Juego DE RuedasPara Retirar El Generador De La Caja Contenido de la CajaAntes DE Darle Arranque AL Motor Agregar Aceite al MotorAgregue Combustible Coloque la generador sobre una superficie niveladaUSO DEL Generador Tierra del SistemaUbicación del Generador Conexión al Sistema Eléctrico de un EdificioOperando EL Generador Precaución Encienda el MotorConexion De Cargas Electricas Parado Del MotorReceptáculos Precaución 120/240 Voltios AC, 30 Amp, Receptáculo de SeguridadVolt AC, 20 Amp, Receptáculos Dobles Juego de Cable de 4 Alambres 240V 120V Neutro CargadoNo Sobrecargue Generador CapacidadControl de la Energía EjemploEspecificaciones Recomendaciones Generales DE MantenimientoMantenimiento del Motor Para Limpiar el GeneradorDiagnositicos DE Averías AlmacenamientoAlmacenando el Generador Almacenando el MotorGarantía Limitada

030209 specifications

Briggs & Stratton 030209 is a notable product in the power equipment industry, primarily recognized for its robust and efficient performance. This portable generator is specifically designed to meet the demands of both residential and recreational needs, making it a versatile choice for users.

One of the standout features of the Briggs & Stratton 030209 is its compact and lightweight design. Weighing in at just under 100 pounds, it is easy to transport and store, making it a preferred option for camping trips, tailgating, or emergency backup for power outages. The generator comes equipped with a reliable 2100 watt engine that ensures a consistent power supply, operating quietly while delivering excellent performance.

The generator features a 2.8-gallon fuel tank which allows for extended runtime, providing up to 10 hours of continuous operation at a 25% load. This means that users can rely on the Briggs & Stratton 030209 to keep essential devices running for an extended period without frequent refueling.

Equipped with multiple outlets, including two 120-volt household outlets and one 12-volt DC outlet, the generator accommodates a variety of devices, from small appliances to communication tools and even recreational equipment. Furthermore, it incorporates an advanced inverter technology, which supplies clean and stable power. This is particularly important for sensitive electronics, ensuring they operate safely without the risk of damage.

Safety features are also paramount in the design of the Briggs & Stratton 030209. It includes a low oil shutdown system that automatically turns off the engine to prevent damage when oil levels are low. The generator’s durable construction ensures it can withstand outdoor conditions, while an easy-to-read fuel gauge provides users with quick access to fuel status.

Overall, the Briggs & Stratton 030209 is a reliable and efficient portable generator, perfect for those in need of dependable power in various situations. Its combination of portability, powerful performance, and safety features makes it a top choice among consumers who seek quality and durability in their power equipment.