Baldor DG6E, DG3E manual Section Operation, Operator Control Panel, Elapsed Time, AC Voltmeter

Page 19

Section 4

Operation

Operator Control Panel

Each operator panel is slightly different, depending on features of the generator you purchased. The Operator Control Panel of Figure 4-1is shown because it has most of the available features. This will be used to explain how the controls operate.

Figure 4-1 Operator Control Panel

Start Switch (not shown) Push to engage the engine starter (if Run Switch is in the ON position). Run Switch (not shown) OFF − Turns off the engine (kill switch).

 

ON − Allows the engine to start and run for normal operation.

 

For DG3E, a Run/Stop lever is used where Run = On, Stop = Off.

Elapsed Time

An hour meter that measures the total hours the generator has been in use (engine

 

running).

AC Voltmeter

Displays the voltage level at the output of the generator (the 230VAC output).

AC Circuit Breakers

Provide overcurrent protection for the generator output. When tripped, the plunger (in

 

center of breaker) will extend out about 3/8 inch. Remove the loads, push the plunger

 

into the breaker to reset the breaker the restore the loads.

WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician has installed an approved transfer switch. The National Electrical Code (NEC) requires that connection of a generator to any elastical circuit normally powered by means of an electric utility must be connected by means of approved transfer switch equipment so as to isolate the electrical circuit from the utility distribution system when the generator is operating. Failure to isolate the electrical circuits by such means may result in injury or death to utility power workers due to backfeed of electrical energy onto the utility lines.

Receptacles − Receptacles are provided to allow easy connection of electrical loads. Never connect this generator to any buildings electrical system unless a licensed electrician has installed an approved transfer switch. Multiple receptacles may be used at the same time provided the total electrical load does not exceed the generators rated output.

120Volts −

NEMA 5−20R GDCI Duplex receptacle provides ground fault protection.

 

 

Rated 125VAC at 20 Amperes.

 

30

Amps 120 Volts −

Twist lock NEMA L5−30R receptacle, rated 125 Volts at 30

Amperes.

30

Amps 120/240 Volts − Twist lock NEMA L14−30R receptacle rated 250Volts at 30

Amperes.

Note: The nominal voltage produced by the generator at each receptacle is 120VAC or 240VAC.

MN2414

Operation 4-1

Image 19
Contents Diesel POW’R Products Generator California Proposition 65 Warning Table of Contents Ii Table of Contents MN2414 Read This Manual Thoroughly Section Product Safety InformationProperty Precaution Statements Used In This ManualOperation Operation Warning Statements Burn Installation Maintenance Product Safety Information MN2414 Section General Information Limited WarrantyLabor Parts General Information MN2414 DG Series Generators Storage Section Receiving & InstallationPhysical Location Frame Ground Connection Receptacle ConnectionsEngine Oil Use of Electric Motor Loads Battery ConnectionsSummer Winter OIL Recommended Amps Cold Recommended Engine Oil and Battery Type Series DGAC Voltmeter Section OperationOperator Control Panel Elapsed TimeStopping Procedure Start−Up Procedure Electric StartGeneral Section Troubleshooting and MaintenanceEngine Troubleshooting Guide Problems and SolutionsService Appendix a DG Series DG3E and DG6E Operator Panel ConfigurationTable A-1 Generator Set Parts List Replacement PartsTable A-1Generator Set Parts List Figure A-5 DG3E Wiring Diagram Figure A-6 DG3E Wiring Diagram with Low Oil & Remote Start Figure A-7 DG6E Wiring Diagram Baldor District Offices California Proposition 65 Warning