Physical Location The mounting location of the system is important. It should be installed in an area that is protected from direct harmful gases or liquids, dust, metallic particles, shock and vibration.

It should be installed in an outdoor location so the exhaust fumes are vented to the atmosphere.

WARNING: An open bottom stationary engine generator set must be installed over noncombustible materials and shall be located such that it prevents combustible materials from accumulating under the generator set.

Outdoor Location with Baldor Supplied Enclosure

If the generator is installed outdoors there should not be a cooling problem. The factory installed enclosure is designed to keep out undesirable weather elements while providing cooling and ventilation. It should be installated on a concrete pad with at least thirty−six (36) inches clearance on all sides for air flow.

1.For effective cooling and maintenance, the system should be installated on a concrete pad with at least thirty−six (36) inches clearance on all sides for air flow and service access.

2.Installation should prevent water levels from reaching the generator. Drainage must be adequate to keep concrete pad free from standing water.

3.Installation should prevent obstructions by buildup of leaves, grass, sand, snow, etc. If these items pose a problem, consider building a small fence or other break to protect the unit from accumulation of debris.

Indoor Location Open Frame Configuration

When the Generator is installed in a building it is essential to provide:

1.Adequate control and exhausting of the heated air.

2.An adequate and constant supply of incoming cooling air.

3.Adequate control and discharge of the engine’s hot exhaust gases.

4.Adequate ventilation of the building when the engine shuts down.

Several other factors should be carefully evaluated when selecting a location for installation:

1.For effective cooling and maintenance, the system should be mounted on a flat, smooth, non-flammable level surface. A concrete pad is ideal and provides a secure installation.

2.Installation should prevent water levels from reaching the generator. Drainage must be adequate to keep concrete pad free from standing water.

3.Installation should prevent obstructions by buildup of leaves, grass, sand, snow, etc. If these items pose a problem, consider building a small fence or other break to protect the unit from accumulation of debris.

4.Installation should place the generator as close as possible to the fuel supply and transfer switch.

5.At least forty−eight (48) inches clearance must be provided on all sides for air flow.

6.Maximum Ambient temperature is 122°F (50°C).

Engine Cooling

A sufficient flow of clean, cool air is required for combustion and to dissipate the heat produced by the engine. Approximately 60% of the heat value of the fuel used is given off as heat (cooling air and exhaust).

The air that will cool the engine must be brought in from outside the building. A sufficient air−flow of rate “Cubic Feet per Minute” (CFM) will allow the incoming fresh air to cool the engine. This requires a power ventilation system of sufficient CFM to be located at the highest possible point of the building to exhaust hot air and draw in cool fresh air. For 8−12KW we recommend an exhaust fan of at least 2000 CFM.

Note: The exhaust fan must not be located where it could easily become blocked by leaves, snow, water, debris, etc.

3-2 Receiving & Installation

MN2415

Image 14
Contents Automatic Emergency Generator California Proposition 65 Warning Table of Contents Appendix C Appendix aAppendix B Appendix DSection Product Safety Information Read This Manual ThoroughlySymbols OperationOperation Warning Statements Burn Installation Maintenance Product Safety Information MN2415 Section General Information Limited WarrantyWarranty Period Generator Series Labor PartsGeneral Information MN2415 AE11 Section Receiving & InstallationAE8 & AE10 AE25Engine Cooling Hot Exhaust Gasses Indoor LocationVentilation Test Guidelines for Exhaust SystemSecure the Generator Physical DimensionsGenerator Height Width Length Weight Model Open Enclosed General Considerations Fuel ConnectionsFuel Consumption Natural and LPG Example Determining Pipe Size for Natural GasNatural Gas Connections Pipe Iron Pipe Size LengthExample Determining Pipe Size for LPG LP Gas Flow Rate Cubic Feet per Hour per Pipe LengthPhase VAC Rating Amps Transfer Switch ConsiderationsBattery Charger Considerations Remote Start and Battery Charger Connections General Wiring ConsiderationsSingle Phase Power Connections AE8 with Enclosure or OpenAE10 with Enclosure AE10 Open AE10 With EnclosureAE11 with Enclosure TBP10 Remote Start & Battery Connections AE25 with Enclosure Natural Gas or LPGFrame Ground Connection Coolant LevelPage 12 Battery Installation Recommended Engine Oil and Battery TypePost Installation Checks Post Installation Checks Receiving & Installation MN2415 Section Operation Display Lamps Master Control SwitchNatural/LP Gas Selector Switch MetersAutomatic Start/Stop All models Automatic Fault Shutdown AE11 and AE25Manual Start/Stop All models Shutdowns AE11 Operating ProceduresAuto Start Operation Editing the Configuration Access Configuration Editor FigureProgrammable Functions and Values 1Programmable Functions and Values Auxiliary Output Garretson Model KN Fuel Valve Considerations General Electrical ConnectionsEngine Controller Terminal Identification Service Garretson KN Fuel ValveSection Troubleshooting and Maintenance EngineProblems and Solutions General Troubleshooting GuideTroubleshooting Guide Digital Controller Only Troubleshooting Guide Analog Controller Only Appendix a Series AE8 Operator Panel ConfigurationMaster Control Switch Controller Fuse Lamp Circuit BreakerFigure A-2 Alternator Assembly Table A-1Generator Set Parts List Figure A-4 AE8 Customer Connection Diagram Figure A-5 AE8 Open Frame Wiring Diagram Figure A-6 AE8 Enclosed Wiring Diagram Appendix B Series AE10 Figure B-1 AE10 Operator PanelFigure B-2 Alternator Assembly Table B-1Generator Set Parts List Figure B-4 AE10 Customer Connection Diagram Figure B-5 AE10 Open Frame Wiring Diagram Figure B-6 AE10 Enclosed Wiring Diagram Appendix C Series AE11 Figure C-1 AE11 Operator PanelReplacement Parts Figure C-2 Alternator AssemblyTable C-1Generator Set Parts List Conversion from LPG to Natural Gas Optional ProcedureFigure C-5 Figure C-7 AE11 Customer Connection Diagram Figure C-8 AE11 Generator Connection Diagram Figure C-9 AE11 Engine Connection Diagram Figure C-10 AE11 Connection Diagram Figure C-11 AE11 Customer Wiring Interface Diagram Series AE11 MN2415 Appendix D Series AE25 Figure D-1 AE25 Operator PanelFigure D-2 Alternator Assembly Table D-1 Generator Set Parts ListTable D-1Generator Set Parts List Figure D-4 AE25 Receptacle Connection Diagram Figure D-5 AE25 Engine Compartment Connection Diagram Figure D-6 AE25 Control Box Connection Diagram Baldor District Offices California Proposition 65 Warning

AE8, AE25, AE10, AE11 specifications

Baldor Electric Company has long been a trusted name in the manufacturing of electric motors and drives. Among their impressive lineup of products, the AE series, which includes the AE11, AE25, AE10, and AE8 models, stands out for their innovative features and robust performance, making them suitable for a variety of industrial applications.

The Baldor AE11 is designed with high efficiency in mind, ensuring that it consumes less energy while delivering optimal performance. This motor features a robust design that enhances durability and reliability, making it ideal for heavy-duty applications. The AE11 also incorporates advanced thermal management technology, ensuring that the motor remains cool even during prolonged use. Its compact size allows for easier integration in tight spaces, making it a versatile choice for many machinery types.

The AE25 model takes performance a step further with its enhanced power output and torque capabilities. This model is built for demanding environments and is engineered to reduce vibration and noise, providing a smoother operational experience. The AE25 also features built-in thermal protection, which automatically shuts down the motor in case of overheating, thereby safeguarding the equipment and reducing maintenance costs.

For those needing a more compact solution, the AE10 offers a balance of power and size. This electric motor is designed with a lightweight yet sturdy build, providing a perfect fit for smaller machines without sacrificing performance. The AE10 is equipped with high-energy efficiency ratings, contributing to lower operational costs and reduced environmental impact. Additionally, it supports various mounting options, enhancing its adaptability for different applications.

Lastly, the AE8 model is a true powerhouse for applications where space is at a premium. It features a minimalist design while still delivering reliable performance. The AE8 is optimized for energy efficiency, boasting a streamlined motor design that minimizes wasted energy. With its quiet operation and low maintenance requirements, this model is ideal for environments where noise reduction is essential.

In summary, the Baldor AE series—including the AE11, AE25, AE10, and AE8—shows a real commitment to efficiency, durability, and versatility. Each model is tailored to meet specific industry needs, whether for demanding heavy-duty applications or compact, energy-efficient setups. With their innovative technologies and engineering excellence, Baldor motors continue to set the standard in the electric motor industry.