IMPORTANT SAFETY INSTRUCTIONS

Bryant Liquid-cooled 15 kW Generators

place before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard.

Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet.

DANGEROUS ELECTRICAL SHOCK MAY RESULT.

If people must stand on metal or concrete while installing, operating, servicing, adjusting or repairing this equipment, place insulative mats over a dry wooden platform. Work on the equipment only while standing on such insulative mats.

The National Electrical Code (NEC), Article 250 requires the frame and external electrically conductive parts of the generator to be connected to an approved earth ground and/or grounding rods. This grounding will help prevent dangerous electrical shock that might be caused by a ground fault condition in the generator set or by static elec- tricity. Never disconnect the ground wire.

Wire gauge sizes of electrical wiring, cables and cord sets must be adequate to handle the maximum electrical current (ampacity) to which they will be subjected.

Before installing or servicing this (and related) equipment, make sure that all power voltage supplies are positively turned off at their source. Failure to do so will result in haz- ardous and possibly fatal electrical shock.

Connecting this unit to an electrical system normally sup- plied by an electric utility shall be by means of a transfer switch so as to isolate the generator electric system from the electric utility distribution system when the generator is operating. Failure to isolate the two electric system power sources from each other by such means will result in dam- age to the generator and may also result in injury or death to utility power workers due to backfeed of electrical energy.

Generators installed with an automatic transfer switch will crank and start automatically when normal (utility) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to per- sonnel, disable the generator’s automatic start circuit (bat- tery cables, etc.) before working on or around the unit. Then, place a “Do Not Operate” tag on the generator control panel and on the transfer switch.

In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not pos- sible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.

Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving components causing injury.

FIRE HAZARDS

Keep a fire extinguisher near the generator at all times. Do NOT use any carbon tetra-chloride type extinguisher. Its fumes are toxic, and the liquid can deteriorate wiring insu- lation. Keep the extinguisher properly charged and be familiar with its use. Consult the local fire department for any questions pertaining to fire extinguishers.

EXPLOSION HAZARDS

Properly ventilate any room or building housing the gener- ator to prevent build-up of explosive gas.

Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.

Bryant generator sets may operate using one of several types of fuels. All fuel types are potentially FLAMMABLE and/or EXPLOSIVE and should be handled with care. Comply with all laws regulating the storage and handling of fuels. Inspect the unit’s fuel system frequently and correct any leaks immediately. Fuel supply lines must be properly installed, purged and leak tested according to applicable fuel-gas codes before placing this equipment into service.

Diesel fuels are highly FLAMMABLE. Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Natural gas is lighter than air, and LP gas is heavier than air. Install leak detectors accordingly.

‹STANDARDS INDEX

In the absence of pertinent standards, codes, regulations and laws, the published information listed below may be used as installation guide for this equipment.

NOTE:

It is essential to use the latest version of any stan- dard to ensure correct and current information.

1.NFPA No. 37, STATIONARY COMBUSTION ENGINES AND GAS TURBINES, available from the National Fire Protection Association, 470 Atlantic Avenue, Boston, MA 02210.

2.NFPA No. 76A, ESSENTIAL ELECTRICAL SYS- TEMS FOR HEALTH CARE FACILITIES, available same as Item 1.

3.NFPA No. 54, NATIONAL FUEL GAS CODE, avail- able same as Item 1.

4.NFPA No. 58, AMERICAN NATIONAL STANDARD FOR STORAGE AND HANDLING OF LIQUEFIED PETROLEUM GAS, available same as Item 1.

5.NFPA No. 70, NFPA HANDBOOK OF NATIONAL ELECTRIC CODE, available same as Item 1.

6.Article X, NATIONAL BUILDING CODE, available from the American Insurance Association, 85 John Street, New York, N.Y. 10038.

7.AGRICULTURAL WIRING HANDBOOK, available from the Food and Energy Council, 909 University Avenue, Columbia, MO 65201.

8.ASAE EP-3634, INSTALLATION AND MAINTE-

NANCE OF FARM STANDBY ELECTRICAL SYS- TEMS, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.

9.NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE, available same as Item 1.

Bryant 3

Image 5
Contents Liquid-cooled, Prepackaged Standby Generators ‹ HOW to Obtain Service ‹ Operation and MaintenanceIntroduction Your Bryant Dealer isIntroduction IFC Safety Rules General Hazards ‹ Standards Index Fire HazardsGenerator Transfer SwitchAutomatic System Operation Generator AC Connection Systems‹ 1.7.2 High Coolant Temperature Switch ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.3 LOW Coolant Level Switch Generator Fuel SystemLifting the Generator SpecificationsUnpacking Torque Specifications Reconfiguring the Fuel System‹ 1.10.2 Engine Specifications Fuel ConsumptionEngine OIL Recommendations Before InstallationCoolant Recommendations ‹ 2.1.1 Nfpa StandardsBasic Standby Electric System Generator Mounting SupportGenerator Location ‹ 2.1.2 Other Published StandardsEmergency Circuit Isolation Method Transfer Switch Signal ConnectionsTotal Circuit Isolation Method Generator AC Neutral ConnectionsPreparation Before START-UP Battery Installation‹ 2.10.1 Vented Batteries ‹ 2.11.1 Prior to Initial START-UPControl Console Components ‹ 3.1.5 SET Exercise Time Switch ‹ 3.1.2 Fault Indicator LampManual Transfer START-UP Automatic Operation Weekly Exercise CycleChecking Fluid Levels Overload Protection for Engine DC Electrical SystemCooling System ‹ 4.5.2 Check Battery ‹ 4.4.2 Battery Fluid ‹ 4.5.7 Inspect Exhaust System‹ 4.4.3 Engine Coolant ‹ 4.5.1 Check Engine OIL Level‹ 4.5.11 Changing the Engine AIR Cleaner Miscellaneous Maintenance‹ 4.6.1 Cleaning the Generator ‹ 4.5.12 Spark Plugs‹ 4.6.4 Battery Replacement ‹ 4.6.2 Battery‹ 4.6.3 Battery Maintenance Service Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsBryant Liquid-cooled 15 kW Generators Installation Diagram Electrical Data Customer Connection DC-VR To Control Panel Terminal Strip Connector Interface Assembly Housing Governor ConnectorCover Connector Housing ASM Motor StepperWasher Shakeproof EXT 5/16 STL Base Mounting 1.5L Stnrd & AcstcDampener Vibration Washer Flat 5/16 ZincPanel for Access GRD Wire Assy 99HSB Assembly BASE-DOOR Ground WireAssembly Cover Access Roof ACSTC&STND Cmprtmnt 1.5LATO Wire Assembly Switch ROC Dpdt ON-OFF-ONPanel Back & Bottom Screw Hhtt M5-0.8 X 12 BPWaterpump Hardware ARM Adjust Alternator Switch OIL PressureGround Wire Starter ENGINE-1.5L14 21 Radiator 1.5L Tank Coolant RecoveryVenturi 1.5L Modine Guard FAN 1.5L ModineVapor Gasket AIR Cleaner Adapter Cover AIR CleanerWeldment Mounting Base Flange Fuel InletOTH Blowgousin re Assy Rotor 10KW Housing BlowerAssy Rotor 15KW Assy Rotor 20KWBOOT, Battery Cable ASSY,WIRE#16 REDBRACKET, Battery Hold Down Battery Post Cover RED+Nipple TOE 1.5NPTX5.5 BLK Iron Manifold Exhaust 1.5LSaddle 2 Inch PIPE,EXHAUST 1.5L STNDRD&ACSTCPURCHASER’S/OWNER’S Warranty Responsibilities Your Warranty Rights and ObligationsMANUFACTURER’S Emission Control System Warranty Coverage Emission Related Parts Include the Following Emission Control System WarrantyWarranty Schedule

ASPAS1BBL015 specifications

The Bryant ASPAS1BBL015 is a cutting-edge air conditioning unit designed to provide efficient cooling solutions for residential and commercial spaces. As part of Bryant's renowned lineup of HVAC equipment, the ASPAS1BBL015 combines advanced technology with user-friendly features to ensure optimal comfort in any environment.

One of the standout features of the ASPAS1BBL015 is its innovative inverter technology. This technology allows the unit to adjust its cooling output according to the ambient temperature, which enhances energy efficiency and reduces electricity costs. Unlike traditional air conditioning units that operate at a fixed speed, the inverter system ensures that the compressor runs at variable speeds, providing a more stable and comfortable temperature without excessive energy consumption.

Another significant characteristic of the ASPAS1BBL015 is its whisper-quiet operation. Designed with noise-reduction technology, this air conditioning model operates at low decibel levels, making it ideal for environments where silence is paramount, such as bedrooms or office spaces. Users can enjoy a serene atmosphere while still benefiting from effective cooling performance.

The Bryant ASPAS1BBL015 also incorporates a multipurpose filtration system. This advanced filtration mechanism not only cools the air but also filters out dust, allergens, and other airborne pollutants, ensuring that the air circulating in the living space is clean and healthy. This is a crucial feature for those who suffer from allergies or respiratory issues, as it promotes a healthier indoor environment.

Moreover, the unit is built with durability in mind. Constructed using high-quality materials, the ASPAS1BBL015 is designed to withstand various weather conditions and is resistant to corrosion, ensuring that it continues to function efficiently over many years. The compact and sleek design of the unit allows for easy installation and integration into existing setups without being obtrusive.

In terms of control options, the ASPAS1BBL015 is compatible with smart home systems, allowing users to manage temperature settings remotely via mobile apps. This feature adds an extra level of convenience, enabling users to fine-tune their comfort levels from anywhere.

In conclusion, the Bryant ASPAS1BBL015 air conditioning unit is a powerful and efficient solution for those seeking reliable cooling technology. With its inverter technology, whisper-quiet operation, advanced filtration, durability, and smart control features, it stands out as an exceptional choice for anyone looking to enhance their indoor climate experience. Whether for residential or commercial use, the ASPAS1BBL015 delivers outstanding performance and comfort.