Bryant ASPAS1BBL015 Overload Protection for Engine DC Electrical System, Cooling System

Page 16

Section 4 — Maintenance

Bryant Liquid-cooled 15 kW Generators

4.1MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES

A. EVERY THREE MONTHS

1.Check battery state of charge and condition. 2.Inspect and test fuel system.

3.Check transfer switch. 4.Inspect exhaust system. 5.Check engine ignition system. 6.Check fan belts.

B. ONCE EVERY SIX MONTHS

1.Test Engine Safety Devices (low oil pressure, low coolant level, high coolant temperature).

The exhaust system parts from this product get extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.

4.3OVERLOAD PROTECTION FOR

ENGINE DC ELECTRICAL SYSTEM

Engine cranking, start up and running are controlled by a solid state Engine Controller circuit board. Battery voltage is delivered to that circuit board via a 15 amp fuse. These overcurrent protection devices will open if the circuit is overloaded.

C. ONCE ANNUALLY

1.Test engine governor. Adjust or repair, if needed. 2.Clean, inspect generator.

3.Flush cooling system.

D. FIRST 100 OPERATING HOURS

1.Change engine oil and oil filter. (After initial change, service engine oil and filter at 150 oper- ating hours or six months, whichever comes first.)

2.Retorque cylinder head. (See Torque Specs, Section 1.13.)

3.Retorque intake and exhaust manifold. (See Torque Specs, Section 1.13.)

E. EVERY 500 OPERATING HOURS

1.Service air cleaner. 2.Check starter.

3.Check engine DC alternator.

F. EVERY 800 OPERATING HOURS

1.Retorque cylinder head. (See Torque Specs, Section 1.13.)

2.Retorque intake and exhaust manifold. (See Torque Specs, Section 1.13.)

3.Check engine compression. 4.Check valve clearance.

4.2COOLING SYSTEM

Air intake and outlet openings in the generator com- partment must be open and unobstructed for contin- ued proper operation. This includes such obstruc- tions as high grass, weeds, brush, leaves and snow.

Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down. (See Section 7 for installation drawings and vent locations.)

If a circuit breaker opens or a fuse element

!melts, find the cause of the overload before resetting the circuit breaker or replacing the fuse.

4.4CHECKING FLUID LEVELS

‹4.4.1 CHECK ENGINE OIL

Check engine crankcase oil level (Figure 4.1) at least every 20 hours of operation, or prior to use.

Remove oil dipstick and wipe dry with a clean, lint-free cloth.

Install oil dipstick, then remove again.

Oil should be between FULL and ADD marks.

If oil level is below the dipstick ADD mark, remove oil fill cap. Add the recommended oil to bring oil level up to the FULL mark. DO NOT FILL ABOVE THE “FULL” MARK. See Section 1.14 for recom- mended oils.

Figure 4.1 - Oil Dipstick and Oil Fill Cap

OIL DIPSTICK

14 Bryant

Image 16
Contents Liquid-cooled, Prepackaged Standby Generators ‹ Operation and Maintenance ‹ HOW to Obtain ServiceIntroduction Your Bryant Dealer isIntroduction IFC Safety Rules General Hazards Fire Hazards ‹ Standards IndexTransfer Switch GeneratorAutomatic System Operation Generator AC Connection Systems‹ 1.7.1 LOW OIL Pressure Switch ‹ 1.7.2 High Coolant Temperature Switch‹ 1.7.3 LOW Coolant Level Switch Generator Fuel SystemUnpacking SpecificationsLifting the Generator Reconfiguring the Fuel System Torque Specifications‹ 1.10.2 Engine Specifications Fuel ConsumptionBefore Installation Engine OIL RecommendationsCoolant Recommendations ‹ 2.1.1 Nfpa StandardsGenerator Mounting Support Basic Standby Electric SystemGenerator Location ‹ 2.1.2 Other Published StandardsTransfer Switch Signal Connections Emergency Circuit Isolation MethodTotal Circuit Isolation Method Generator AC Neutral ConnectionsBattery Installation Preparation Before START-UP‹ 2.10.1 Vented Batteries ‹ 2.11.1 Prior to Initial START-UPControl Console Components ‹ 3.1.2 Fault Indicator Lamp ‹ 3.1.5 SET Exercise Time SwitchManual Transfer START-UP Automatic Operation Weekly Exercise CycleCooling System Overload Protection for Engine DC Electrical SystemChecking Fluid Levels ‹ 4.4.2 Battery Fluid ‹ 4.5.7 Inspect Exhaust System ‹ 4.5.2 Check Battery‹ 4.4.3 Engine Coolant ‹ 4.5.1 Check Engine OIL LevelMiscellaneous Maintenance ‹ 4.5.11 Changing the Engine AIR Cleaner‹ 4.6.1 Cleaning the Generator ‹ 4.5.12 Spark Plugs‹ 4.6.3 Battery Maintenance ‹ 4.6.2 Battery‹ 4.6.4 Battery Replacement Scheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionBryant Liquid-cooled 15 kW Generators Installation Diagram Electrical Data Customer Connection DC-VR To Control Panel Terminal Strip Housing Governor Connector Connector Interface AssemblyCover Connector Housing ASM Motor StepperBase Mounting 1.5L Stnrd & Acstc Washer Shakeproof EXT 5/16 STLDampener Vibration Washer Flat 5/16 ZincPanel for Access Assembly BASE-DOOR Ground Wire GRD Wire Assy 99HSBAssembly Cover Access Roof ACSTC&STND Cmprtmnt 1.5LATO Switch ROC Dpdt ON-OFF-ON Wire AssemblyPanel Back & Bottom Screw Hhtt M5-0.8 X 12 BPWaterpump Hardware Switch OIL Pressure ARM Adjust AlternatorGround Wire Starter ENGINE-1.5L14 21 Tank Coolant Recovery Radiator 1.5LVenturi 1.5L Modine Guard FAN 1.5L ModineVapor Cover AIR Cleaner Gasket AIR Cleaner AdapterWeldment Mounting Base Flange Fuel InletOTH Blowgousin re Housing Blower Assy Rotor 10KWAssy Rotor 15KW Assy Rotor 20KWASSY,WIRE#16 RED BOOT, Battery CableBRACKET, Battery Hold Down Battery Post Cover RED+Manifold Exhaust 1.5L Nipple TOE 1.5NPTX5.5 BLK IronSaddle 2 Inch PIPE,EXHAUST 1.5L STNDRD&ACSTCMANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule

ASPAS1BBL015 specifications

The Bryant ASPAS1BBL015 is a cutting-edge air conditioning unit designed to provide efficient cooling solutions for residential and commercial spaces. As part of Bryant's renowned lineup of HVAC equipment, the ASPAS1BBL015 combines advanced technology with user-friendly features to ensure optimal comfort in any environment.

One of the standout features of the ASPAS1BBL015 is its innovative inverter technology. This technology allows the unit to adjust its cooling output according to the ambient temperature, which enhances energy efficiency and reduces electricity costs. Unlike traditional air conditioning units that operate at a fixed speed, the inverter system ensures that the compressor runs at variable speeds, providing a more stable and comfortable temperature without excessive energy consumption.

Another significant characteristic of the ASPAS1BBL015 is its whisper-quiet operation. Designed with noise-reduction technology, this air conditioning model operates at low decibel levels, making it ideal for environments where silence is paramount, such as bedrooms or office spaces. Users can enjoy a serene atmosphere while still benefiting from effective cooling performance.

The Bryant ASPAS1BBL015 also incorporates a multipurpose filtration system. This advanced filtration mechanism not only cools the air but also filters out dust, allergens, and other airborne pollutants, ensuring that the air circulating in the living space is clean and healthy. This is a crucial feature for those who suffer from allergies or respiratory issues, as it promotes a healthier indoor environment.

Moreover, the unit is built with durability in mind. Constructed using high-quality materials, the ASPAS1BBL015 is designed to withstand various weather conditions and is resistant to corrosion, ensuring that it continues to function efficiently over many years. The compact and sleek design of the unit allows for easy installation and integration into existing setups without being obtrusive.

In terms of control options, the ASPAS1BBL015 is compatible with smart home systems, allowing users to manage temperature settings remotely via mobile apps. This feature adds an extra level of convenience, enabling users to fine-tune their comfort levels from anywhere.

In conclusion, the Bryant ASPAS1BBL015 air conditioning unit is a powerful and efficient solution for those seeking reliable cooling technology. With its inverter technology, whisper-quiet operation, advanced filtration, durability, and smart control features, it stands out as an exceptional choice for anyone looking to enhance their indoor climate experience. Whether for residential or commercial use, the ASPAS1BBL015 delivers outstanding performance and comfort.