Bryant ASPAS1BBL015 Fuel Consumption, Reconfiguring the Fuel System, Torque Specifications

Page 9

Section 1 — General Information

Bryant Liquid-cooled 15 kW Generators

‹1.10.2 ENGINE SPECIFICATIONS

Make

Mitsubishi

Displacement

92 inches3 (1.5 liters)

Cylinder Arrangement

4, in-line

Valve Arrangement

Overhead Cam

Firing Order

1-3-4-2

Number of Main Bearings

5

Compression Ratio

9 to 1

No. of Teeth on Flywheel

104

Ignition Timing

 

at 1800 rpm

35 degrees BTDC

Spark Plug Gap

0.020-0.025 inch

Recommended Spark Plugs

 

Champion

RN11YC4

Oil Pressure

30-50 psi

Crankcase Oil Capacity

3.0 U.S. quarts (2.8 liters)

Recommended Engine Oil

SAE 15W-40

Type of Cooling System

Pressurized, closed recovery

Cooling Fan

Pusher Type

Cooling System Capacity

2 U.S. gallons (7.6 liters)

Recommended Coolant

Use a 50-50 mixture of

 

ethylene glycol base.

1.11 FUEL CONSUMPTION

15 kW Models

Using Natural Gas

........................................277 cu. ft. per hour

Using LP Gas

110 cubic ft.(3.1 gal.) per hour

 

NOTE:

Fuel consumption is given at rated maximum con- tinuous power output when using natural gas rated at 1000 Btu per cubic foot and LP gas rated 2520 Btu per cubic foot. Actual fuel consumption obtained may vary depending on such variables as applied load, ambient temperature, engine condi- tions and other environmental factors.

Fuel pressure for a natural gas set up should be five inches to 14 inches of water column (0.18 to 0.5 psi) at all load ranges.

Fuel pressure for an LP vapor set up should be 11 inches to 14 inches of water column (0.4 to 0.5 psi) at all load ranges.

1.12RECONFIGURING THE FUEL SYSTEM

NOTE:

All models are configured for natural gas from the factory.

To reconfigure the fuel system from NG to LP, follow these steps:

1.Turn the main gas supply off.

2.Remove the carburetor fuel hose from the outlet port (Port 1) of the demand regulator (Figure 1.8).

3.Remove the brass hose fitting from the outlet port (Port 1) of the demand regulator.

4.Remove pipe plug from Port 2.

5.Install brass hose fitting into Port 2.

6.Install pipe plug into Port 1.

7.Connect carburetor gas hose to brass fitting.

8.Tighten all clamps and plugs.

9.Make sure fuel supply is of the proper pressure and type for configuration.

10.Reverse the procedure to convert back to natural gas.

Figure 1.8 — Reconfigure the Fuel System

 

Port 1

 

Port 2

 

FUEL HOSE

FUEL HOSE

 

PLUG

BRASS HOSE

BRASS HOSE

PLUG

FITTING

FITTING

 

 

 

OUT

OUT

 

 

PORT 1

PORT 2

 

 

HOUSING

HOUSING

 

 

PORTS

PORTS

 

 

 

 

NG FUEL SYSTEM

LP FUEL SYSTEM

NOTE:

Port 1 is for NG only and Port 2 is for LP vapor only. No provision for simultaneous fuels has been made.

DANGER

Serious injury or damage may occur if not con-

!figured properly. Please consult a dealer with any questions.

1.13 TORQUE SPECIFICATIONS

Cylinder Head

15 (+ 90° + 90°) ft.lb.

Intake Manifold

13 ft.lb.

Exhaust Manifold

13 ft.lb.

Bryant 7

Image 9
Contents Liquid-cooled, Prepackaged Standby Generators ‹ HOW to Obtain Service ‹ Operation and MaintenanceIntroduction Your Bryant Dealer isIntroduction IFC Safety Rules General Hazards ‹ Standards Index Fire HazardsGenerator Transfer SwitchAutomatic System Operation Generator AC Connection Systems‹ 1.7.2 High Coolant Temperature Switch ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.3 LOW Coolant Level Switch Generator Fuel SystemSpecifications UnpackingLifting the Generator Torque Specifications Reconfiguring the Fuel System‹ 1.10.2 Engine Specifications Fuel ConsumptionEngine OIL Recommendations Before InstallationCoolant Recommendations ‹ 2.1.1 Nfpa StandardsBasic Standby Electric System Generator Mounting SupportGenerator Location ‹ 2.1.2 Other Published StandardsEmergency Circuit Isolation Method Transfer Switch Signal ConnectionsTotal Circuit Isolation Method Generator AC Neutral ConnectionsPreparation Before START-UP Battery Installation‹ 2.10.1 Vented Batteries ‹ 2.11.1 Prior to Initial START-UPControl Console Components ‹ 3.1.5 SET Exercise Time Switch ‹ 3.1.2 Fault Indicator LampManual Transfer START-UP Automatic Operation Weekly Exercise CycleOverload Protection for Engine DC Electrical System Cooling SystemChecking Fluid Levels ‹ 4.5.2 Check Battery ‹ 4.4.2 Battery Fluid ‹ 4.5.7 Inspect Exhaust System‹ 4.4.3 Engine Coolant ‹ 4.5.1 Check Engine OIL Level‹ 4.5.11 Changing the Engine AIR Cleaner Miscellaneous Maintenance‹ 4.6.1 Cleaning the Generator ‹ 4.5.12 Spark Plugs‹ 4.6.2 Battery ‹ 4.6.3 Battery Maintenance‹ 4.6.4 Battery Replacement Service Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsBryant Liquid-cooled 15 kW Generators Installation Diagram Electrical Data Customer Connection DC-VR To Control Panel Terminal Strip Connector Interface Assembly Housing Governor ConnectorCover Connector Housing ASM Motor StepperWasher Shakeproof EXT 5/16 STL Base Mounting 1.5L Stnrd & AcstcDampener Vibration Washer Flat 5/16 ZincPanel for Access GRD Wire Assy 99HSB Assembly BASE-DOOR Ground WireAssembly Cover Access Roof ACSTC&STND Cmprtmnt 1.5LATO Wire Assembly Switch ROC Dpdt ON-OFF-ONPanel Back & Bottom Screw Hhtt M5-0.8 X 12 BPWaterpump Hardware ARM Adjust Alternator Switch OIL PressureGround Wire Starter ENGINE-1.5L14 21 Radiator 1.5L Tank Coolant RecoveryVenturi 1.5L Modine Guard FAN 1.5L ModineVapor Gasket AIR Cleaner Adapter Cover AIR CleanerWeldment Mounting Base Flange Fuel InletOTH Blowgousin re Assy Rotor 10KW Housing BlowerAssy Rotor 15KW Assy Rotor 20KWBOOT, Battery Cable ASSY,WIRE#16 REDBRACKET, Battery Hold Down Battery Post Cover RED+Nipple TOE 1.5NPTX5.5 BLK Iron Manifold Exhaust 1.5LSaddle 2 Inch PIPE,EXHAUST 1.5L STNDRD&ACSTCYour Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyWarranty Schedule

ASPAS1BBL015 specifications

The Bryant ASPAS1BBL015 is a cutting-edge air conditioning unit designed to provide efficient cooling solutions for residential and commercial spaces. As part of Bryant's renowned lineup of HVAC equipment, the ASPAS1BBL015 combines advanced technology with user-friendly features to ensure optimal comfort in any environment.

One of the standout features of the ASPAS1BBL015 is its innovative inverter technology. This technology allows the unit to adjust its cooling output according to the ambient temperature, which enhances energy efficiency and reduces electricity costs. Unlike traditional air conditioning units that operate at a fixed speed, the inverter system ensures that the compressor runs at variable speeds, providing a more stable and comfortable temperature without excessive energy consumption.

Another significant characteristic of the ASPAS1BBL015 is its whisper-quiet operation. Designed with noise-reduction technology, this air conditioning model operates at low decibel levels, making it ideal for environments where silence is paramount, such as bedrooms or office spaces. Users can enjoy a serene atmosphere while still benefiting from effective cooling performance.

The Bryant ASPAS1BBL015 also incorporates a multipurpose filtration system. This advanced filtration mechanism not only cools the air but also filters out dust, allergens, and other airborne pollutants, ensuring that the air circulating in the living space is clean and healthy. This is a crucial feature for those who suffer from allergies or respiratory issues, as it promotes a healthier indoor environment.

Moreover, the unit is built with durability in mind. Constructed using high-quality materials, the ASPAS1BBL015 is designed to withstand various weather conditions and is resistant to corrosion, ensuring that it continues to function efficiently over many years. The compact and sleek design of the unit allows for easy installation and integration into existing setups without being obtrusive.

In terms of control options, the ASPAS1BBL015 is compatible with smart home systems, allowing users to manage temperature settings remotely via mobile apps. This feature adds an extra level of convenience, enabling users to fine-tune their comfort levels from anywhere.

In conclusion, the Bryant ASPAS1BBL015 air conditioning unit is a powerful and efficient solution for those seeking reliable cooling technology. With its inverter technology, whisper-quiet operation, advanced filtration, durability, and smart control features, it stands out as an exceptional choice for anyone looking to enhance their indoor climate experience. Whether for residential or commercial use, the ASPAS1BBL015 delivers outstanding performance and comfort.