Section 2 — Installation

Bryant Liquid-cooled 15 kW Generators

2.5EMERGENCY CIRCUIT ISOLATION

METHOD

This prevents overloading the generator by keeping electrical loads below the wattage/amperage capacity of the generator. If the generator is powering only crit- ical loads, within the wattage/amperage capacity, dur- ing utility power outages, consider using the emer- gency circuit isolation method.

Critical electrical loads are grouped together and wired into a separate “Emergency Distribution Panel.” Load circuits powered by that panel are with- in the wattage/amperage capacity of the generator set. When this method is used, it is difficult to overload the generator. The transfer switch must meet the fol- lowing requirements:

It must have an ampere rating equal to, or greater than, the total amperage rating of the emergency distribution panel circuit.

Have it installed between the building’s main dis- tribution panel and the emergency distribution panel.

2.6TOTAL CIRCUIT ISOLATION

METHOD

When a generator capable of powering all electrical loads in the circuit is to be installed, use the “Total Circuit Isolation Method.” It is possible for the gener- ator to be overloaded when this isolation method is employed. The following apply to the transfer switch in this type of system.

Ampere rating of the transfer switch must be equal to, or greater than, the ampere rating of the normal incoming utility service.

The transfer switch is installed between the utility service entrance and the building distribution panel.

Proper grounding helps protect personnel against electrical shock in the event of a ground fault condi- tion in the generator or in connected electrical devices. In addition, grounding helps dissipate static electricity that often builds up in ungrounded devices.

Figure 2.2 – Generator Grounding Lug (typical)

2.8GENERATOR AC NEUTRAL

CONNECTIONS

Bryant uses an UNGROUNDED AC neutral. Grounding is recommended only at the main service entrance. If the neutral wire is grounded and one of the phase loads becomes grounded, the excessive current opens the load circuit breaker or collapses the generator field. The actual result depends on the electrical characteristics of the particular installed generator.

Failure to connect the generator neutral prop-

!erly will result in unbalanced line-to-neutral voltages. Resulting high voltages will cause equipment damage.

2.7GROUNDING THE GENERATOR

The National Electrical Code requires the frame and external electrically conductive parts of this equip- ment to be properly connected to an approved earth ground and/or grounding rods. For that purpose, a GROUND LUG (Figure 2.2) is provided on the gener- ator mounting base. Consult a qualified electrician for grounding requirements in the area. Grounding procedures must meet local regulations.

DANGER

Do not connect the ground wire to any pipe that carries a flammable or explosive substance

– FIRE or an EXPLOSION may result.

2.9TRANSFER SWITCH SIGNAL

CONNECTIONS

It is necessary to connect the control wires between the generator and the transfer switch.

Control system interconnections consist of N1, N2, T1, T2 and leads 23 and 194. Control system inter- connection leads must be run in a conduit that is sep- arate from the AC power lead. Recommended wire gauge sizes for this wiring depends on the length of the wire, as recommended below:

 

MAXIMUM WIRE LENGTH

RECOMMENDED WIRE

 

 

 

SIZE

 

 

460 feet (140m)

No. 18 AWG.

 

 

461 to 730 feet (223m)

No. 16 AWG.

 

 

731 to 1,160 feet (354m)

No. 14 AWG.

 

 

1,161 to 1,185 feet (565m)

No. 12 AWG.

 

 

 

 

 

10 Bryant

Image 12
Contents Liquid-cooled, Prepackaged Standby Generators ‹ Operation and Maintenance ‹ HOW to Obtain ServiceIntroduction Your Bryant Dealer isIntroduction IFC Safety Rules General Hazards Fire Hazards ‹ Standards IndexTransfer Switch GeneratorAutomatic System Operation Generator AC Connection Systems‹ 1.7.1 LOW OIL Pressure Switch ‹ 1.7.2 High Coolant Temperature Switch‹ 1.7.3 LOW Coolant Level Switch Generator Fuel SystemSpecifications UnpackingLifting the Generator Reconfiguring the Fuel System Torque Specifications‹ 1.10.2 Engine Specifications Fuel ConsumptionBefore Installation Engine OIL RecommendationsCoolant Recommendations ‹ 2.1.1 Nfpa StandardsGenerator Mounting Support Basic Standby Electric SystemGenerator Location ‹ 2.1.2 Other Published StandardsTransfer Switch Signal Connections Emergency Circuit Isolation MethodTotal Circuit Isolation Method Generator AC Neutral ConnectionsBattery Installation Preparation Before START-UP‹ 2.10.1 Vented Batteries ‹ 2.11.1 Prior to Initial START-UPControl Console Components ‹ 3.1.2 Fault Indicator Lamp ‹ 3.1.5 SET Exercise Time SwitchManual Transfer START-UP Automatic Operation Weekly Exercise CycleOverload Protection for Engine DC Electrical System Cooling SystemChecking Fluid Levels ‹ 4.4.2 Battery Fluid ‹ 4.5.7 Inspect Exhaust System ‹ 4.5.2 Check Battery‹ 4.4.3 Engine Coolant ‹ 4.5.1 Check Engine OIL LevelMiscellaneous Maintenance ‹ 4.5.11 Changing the Engine AIR Cleaner‹ 4.6.1 Cleaning the Generator ‹ 4.5.12 Spark Plugs‹ 4.6.2 Battery ‹ 4.6.3 Battery Maintenance‹ 4.6.4 Battery Replacement Scheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionBryant Liquid-cooled 15 kW Generators Installation Diagram Electrical Data Customer Connection DC-VR To Control Panel Terminal Strip Housing Governor Connector Connector Interface AssemblyCover Connector Housing ASM Motor StepperBase Mounting 1.5L Stnrd & Acstc Washer Shakeproof EXT 5/16 STLDampener Vibration Washer Flat 5/16 ZincPanel for Access Assembly BASE-DOOR Ground Wire GRD Wire Assy 99HSBAssembly Cover Access Roof ACSTC&STND Cmprtmnt 1.5LATO Switch ROC Dpdt ON-OFF-ON Wire AssemblyPanel Back & Bottom Screw Hhtt M5-0.8 X 12 BPWaterpump Hardware Switch OIL Pressure ARM Adjust AlternatorGround Wire Starter ENGINE-1.5L14 21 Tank Coolant Recovery Radiator 1.5LVenturi 1.5L Modine Guard FAN 1.5L ModineVapor Cover AIR Cleaner Gasket AIR Cleaner AdapterWeldment Mounting Base Flange Fuel InletOTH Blowgousin re Housing Blower Assy Rotor 10KWAssy Rotor 15KW Assy Rotor 20KWASSY,WIRE#16 RED BOOT, Battery CableBRACKET, Battery Hold Down Battery Post Cover RED+Manifold Exhaust 1.5L Nipple TOE 1.5NPTX5.5 BLK IronSaddle 2 Inch PIPE,EXHAUST 1.5L STNDRD&ACSTCYour Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule

ASPAS1BBL015 specifications

The Bryant ASPAS1BBL015 is a cutting-edge air conditioning unit designed to provide efficient cooling solutions for residential and commercial spaces. As part of Bryant's renowned lineup of HVAC equipment, the ASPAS1BBL015 combines advanced technology with user-friendly features to ensure optimal comfort in any environment.

One of the standout features of the ASPAS1BBL015 is its innovative inverter technology. This technology allows the unit to adjust its cooling output according to the ambient temperature, which enhances energy efficiency and reduces electricity costs. Unlike traditional air conditioning units that operate at a fixed speed, the inverter system ensures that the compressor runs at variable speeds, providing a more stable and comfortable temperature without excessive energy consumption.

Another significant characteristic of the ASPAS1BBL015 is its whisper-quiet operation. Designed with noise-reduction technology, this air conditioning model operates at low decibel levels, making it ideal for environments where silence is paramount, such as bedrooms or office spaces. Users can enjoy a serene atmosphere while still benefiting from effective cooling performance.

The Bryant ASPAS1BBL015 also incorporates a multipurpose filtration system. This advanced filtration mechanism not only cools the air but also filters out dust, allergens, and other airborne pollutants, ensuring that the air circulating in the living space is clean and healthy. This is a crucial feature for those who suffer from allergies or respiratory issues, as it promotes a healthier indoor environment.

Moreover, the unit is built with durability in mind. Constructed using high-quality materials, the ASPAS1BBL015 is designed to withstand various weather conditions and is resistant to corrosion, ensuring that it continues to function efficiently over many years. The compact and sleek design of the unit allows for easy installation and integration into existing setups without being obtrusive.

In terms of control options, the ASPAS1BBL015 is compatible with smart home systems, allowing users to manage temperature settings remotely via mobile apps. This feature adds an extra level of convenience, enabling users to fine-tune their comfort levels from anywhere.

In conclusion, the Bryant ASPAS1BBL015 air conditioning unit is a powerful and efficient solution for those seeking reliable cooling technology. With its inverter technology, whisper-quiet operation, advanced filtration, durability, and smart control features, it stands out as an exceptional choice for anyone looking to enhance their indoor climate experience. Whether for residential or commercial use, the ASPAS1BBL015 delivers outstanding performance and comfort.