4

4. Service procedures

(3)Meanings of alarm messages

Possible Cause of Malfunction

 

Alarm

 

message

 

 

 

 

 

• Serial

 

Remote controller is detecting

 

E1

commu-

 

error signal from indoor unit.

 

E2

nication

 

• Indoor unit is detecting error signal from the remote controller.

E3

errors

 

 

(No serial communications signal)

 

Mis-setting

 

 

 

 

 

 

 

 

Indoor unit is detecting error

 

E4

 

 

 

 

 

signal from outdoor unit.

 

E5

 

 

Outdoor unit is detecting error

 

 

 

 

signal from indoor unit.

 

E6

 

 

 

 

 

 

 

Indoor unit is not working

 

 

 

 

 

 

 

correctly.

 

 

 

 

 

 

 

 

 

 

Outdoor unit is transmitting error

 

E7

 

 

signal.

 

 

 

 

 

 

 

 

 

 

 

 

 

Improper setting of indoor unit or

 

E8

 

 

remote controller.

 

E9

 

 

 

 

 

 

 

 

 

 

E12

 

 

 

 

 

 

 

 

When using group control, main indoor unit address setting is duplicated.

E14

 

 

(For single heat pump type.)

 

 

 

 

 

 

 

 

 

 

 

Error in Auto. address setting.

 

E15

 

 

(No. or capacity of judged indoor unit is small.)

 

 

 

 

 

 

 

 

 

 

 

Error in Auto. address setting.

 

E16

 

 

(No. or capacity of judged indoor unit is large.)

 

 

 

 

 

 

 

 

 

 

 

Indoor unit is detecting error signal from another indoor unit.

E18

Activation of

 

Protective device in indoor unit

• Thermal protector in indoor fan motor is activated.

P1

protective

 

is activated.

 

 

device

 

 

 

 

 

 

Protective device in outdoor

 

• Thermal protector in outdoor fan motor is activated.

P2

 

 

 

 

 

unit is activated.

 

• Comp. thermal protector is activated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Incorrect discharge gas temp. of comp.

P3

 

 

 

 

High-pressure switch is activated.

P4

 

 

 

 

Incorrect power supply voltage . Negative phase, defective

P5

 

 

 

 

phase or voltage drop.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Incorrect discharge gas temp. of comp.

P17

 

 

 

 

 

 

 

 

Protective device in indoor unit

 

Improper wiring connections of ceiling panel.

P9

 

 

is activated.

 

Float switch is activated.

P10

 

 

 

 

 

 

 

 

 

 

NOTE

 

 

 

 

 

RCU :

Remote Control Unit (remote controller)

 

R.C. : Refrigerant Circuit

comp. : Compressor

temp. : Temperature

PCB : Printed Circuit Board

SM830082

IV - 6